SandP FLEXEO 3V Series Static Heat Recovery Units Instruction Manual

October 30, 2023
SandP

SandP FLEXEO 3V Series Static Heat Recovery Units

Product Information

The FLEXEO 3V Series is a range of static heat recovery units designed for residential and light commercial installations. The series includes two models, FLEXEO BP FL 3V with a cable remote control and FLEXEO BP RD 3V with a radio frequency remote control. The units are highly flexible and can be configured in multiple ways using independent modules. The FLEXEO series is manufactured by Soler & Palau.

Dimensions

The dimensions of the heat recovery module FLEXEO BP (with bypass) are 1372mm x 691mm x 206mm. The fan modules are 691mm x 253mm x 99mm. The maximum airflow at 100Pa is 210 m3/h and the maximum efficiency is 94%.

Technical Characteristics

The FLEXEO BP FL 3V and FLEXEO BP RD 3V models have air connections of 125mm and operate at a voltage of 230V. The absorbed power is 100W and the maximum efficiency is 94%. The sound pressure at 3m distance is between 15.5 to 43 dB(A), depending on the frequency.

Product Usage Instructions

Mounting Flexibility

The FLEXEO series can be installed in single dwellings or multi-dwelling blocks. The independent modules allow for multiple configurations to suit specific applications.

Installation in Single Dwellings

The different parts of the unit, including fans and exchangers, can be installed in different areas to improve performance and reduce noise. The following areas are recommended for installation:

  • Loft
  • Ceiling voids
  • Heated rooms (corridor, bathroom, dining room)
  • Non-heated rooms (garage, laundry room)

Refer to the example installation diagram provided in the user manual for guidance.

Mounting Accessories

The FLEXEO series can be fitted with various mounting accessories including:

  • KIT M5/G4 FLEXEO replacement kit of M5 and G4 filters
  • BARJ BARP self-adjusting calibrated extraction valves
  • BDOP supply and extraction valve
  • RDR self-adjusting damper (50-250 Pa) that fits inside the duct and maintains constant airflow
  • GPR-ISO insulated rigid duct
  • RD BP specific low-pressure (20-100 Pa) and self-adjusting damper with a sleeve to fit directly into the duct. 80mm diameter.
  • Airflow: 15 or 30 m3/h.

STATIC HEAT RECOVERY UNITS. RESIDENTIAL AND LIGHT COMMERCIAL INSTALLATIONS

FLEXEO 3V Series

Heat recovery unit with high-efficiency heat exchanger up to 94%. Its main feature is the possibility to be adapted to all configurations. The construction with independent modules allows high flexibility and several fitting options. It can be mounted on the floor and on the ceiling. On the wall, it can be mounted in vertical or horizontal position. Its low profile (300 mm) allows fitting into a false ceiling. It can be equipped with a 100% bypass, maintaining its low profile. To ensure good air quality, is equipped with a F5 filter on the inlet side and, to protect the core, a G4 on the extraction side. With its remote control, it is possible to manage the boost function, the bypass, and the filter reset alarm.
Models

  • FLEXEO BP FL 3V: Cable remote control.
  • FLEXEO BP RD 3V: Radio frequency remote control.

Configuration

  • Counter flow heat exchanger.
  • EPP body.
  • Spigots pivoting to 90º.
  • Fan modules x 2
  • 100% bypass , automatic or manual.
  • Manual boost function.
  • Inlet filter: M5 (ISO ePM10 50%, at 210m3/h). Option, F7 (ISO ePM1 50%, at 210 m3/h).
  • Extraction filter G4 (ISO coarse 60%, at 210m3/h).
  • Wall or ceiling mounting kit
  • Opening for access to the core by quarter turn fasteners.

MOUNTING FLEXIBILITY

SandP-FLEXEO-3V-Series-StaticHeat-Recovery-Units-fig-2

FLEXEO consists of independent modules, which allow multiple configurations0.

Specific applications

Remote control by cable or wireless:

  • Bypass
  • Boost
  • Absence mode
  • Filter reset

DIMENSIONS (mm)

Heat recovery module FLEXEO BP (with bypass)

Fan modulesSandP-FLEXEO-3V-Series-StaticHeat-Recovery-Units-
fig-6

TECHNICAL CHARACTERISTICS

Model| Air connections (mm)| Voltage (V)| Maximum airflow at 100Pa (m 3 /h)| Absorbed power (W)| Maximum Efficiency (%)
---|---|---|---|---|---
FLEXEO BP FL 3V| 125| 230| 210| 100| 94
FLEXEO BP RD 3V| 125| 230| 210| 100| 94

ACOUSTIC DATA

Sound pressure, at 3 m distance [210 m 3 /h @ 100 Pa]

Hz| 63| 125| 250| 500| 1000| 2000| 4000| 8000| TOTAL dB(A)
OUTLET| 2,4| 12| 15,5| 32,9| 17,6| 10,3| 3| 2,3| 31,8
INLET| 10| 13,5| 17| 27,5| 22,3| 14,5| 5,9| 2,5| 28,4
RADIATED| 4,5| 10,4| 30| 35,6| 28,9| 28| 31,8| 19| 43

PERFORMANCE CURVES

EFFICIENCY CURVE

AIRFLOW DIRECTION

SandP-FLEXEO-3V-Series-StaticHeat-Recovery-Units-fig-9

INSTALLATION IN SINGLE DWELLINGS

The different parts (fans and exchanger) can be installed in different areas in order to improve performance and reduce noise.SandP-FLEXEO-3V-Series-
StaticHeat-Recovery-Units-fig-10

FLEXEO SERIES – EXAMPLE OF INSTALLATION IN SINGLE DWELLINGSSandP-FLEXEO-
3V-Series-StaticHeat-Recovery-Units-fig-11

  1. Wall-mounted air inlet grille TAP.
  2. Supply and extraction valves BDOP.
  3. Self-adjusting extraction valve BARJ / BARP
  4. Flexible insulated duct GP ISO.
  5. Extraction plenum
  6. Supply plenum
  7. VENT-FLEXEO supply motorized fan and VENT-FLEXEO extraction motorized fan.
  8. CADS-FLEXEO: Static heat recovery unit.
  9. Roof terminal cowl CT.

MOUNTING ACCESSORIES

SandP-FLEXEO-3V-Series-StaticHeat-Recovery-Units-
fig-12

Heat recovery units FLEXEO www.solerpalau.com.