PHILIPS WT120C G2 Coreline Waterproof LED Light Installation Guide

October 30, 2023
Philips

PHILIPS WT120C G2 Coreline Waterproof LED Light Installation Guide
PHILIPS WT120C G2 Coreline Waterproof LED Light

What’s In The Box

What's In The Box

Symbols

Dimension

 | System light outputm)| Color tmperature(l)| Power(W)| Energy Efficiency Class of Light Source|
---|---|---|---|---|---
‘WT120C G2 LED195/840 PSU L600| 1900| 4000K| 15| D| 0.8
WT120C G2 LED275/840 PSU L1200| 2700| 4000K| 20.5| D| 1.33
WT120C G2 LED40S/840 PSU L1200| 4000| 4000K| 28.6| D| 1.33
‘WT120C G2 LED345/840 PSU L1500| 3400| 4000K| 24.3| D| 1.65
‘WT120C G2 LED60S/840 PSU L1500| 6000| 4000K| 42.9| D| 1.67
WT120C G2 LED80S/840 PSU L1500| 8000| 4000K| 57.1| D| 1.73
WT120C G2 LED185/840 PSU PCO L600| 1800| 4000K| 15| D| 0.8
‘WT120C G2 LED255/840 PSU PCO L1200| 2500| 4000K| 20.5| D| 1.33
WT120C G2 LED375/840 PSU PCO L1200| 3700| 4000K| 28.6| D| 1.33
WT120C G2 LED315/840 PSU PCO L1500| 3100| 400K| 24.3| D| 1.65
WT120C G2 LED575/840 PSU PCO L1500| 5700| 4000K| 42.9| D| 1.67
‘WT120C G2 LED755/840 PSU PCO L1500| 7500| 4000K| 57.1| D| 1.73
WT120C G2 LED40S/865 PSU L1200| 4000| 6500K| 28.5| D| 1.33
WT120C G2 LED345/865 PSU L1500| 3400| 6500K| 24.5| D| 1.65
WT120C G2 LED60S/865 PSU L1500| 6000| 6500K| 43| D| 1.67
‘WT120C G2 LED375/830 PSU L1200| 3700| 3000K| 28.5| D| 1.33
‘WT120C G2 LED555/830 PSU L1500| 5500| 3000K| 43| D| 1.67

Dimension

Type| Dimension(mm)| NF. ot

clips

---|---|---
A      B      C     D  Emin Emax   F
WT1z0C G2 LEE’19S/840 PSU r600 /             120C G2 rED18S/8‹0 PSU PCO r600| | 665|  |  | 308| 512|  | 6
ML20C G2 LEo27s/810 PSU Li200/ WT120C Gz LEDz5s/840 PSU PCO L 200|  | 1215|  | | 538| 1062|  | 10
WTLZOC G2 LED4O5/840 PSU L1200/  WT120C G2 LED37S/840 PSU PCO L12O0
WT120C G2 LEE’34S/840 PSU L1s00/ WT120C sz LED31S/84O PSU PCO L1500|

76

|

1515

|

80

|

38

|

838

|

1362

|

8S

|

12

WTL20C G2 LED60S/840 PSU L1500/ WT120C sz LED57S/840 PSU PCO L1500
WTLZOC G2 LED8Os/840 PSU rzs00/ WT120C G2 rED75S/84O PsU PCO L1sO0
\^/T120C G2 LED40S/865 PSU L1200/ WT120C G2 LED37S/830 PSU L1200|  | 121S|  | | 538| 1062|  | 10
\^/T120C G2 LED34S/865 PSU L1500 /|  | 1515|  |  | 838| 1362|  | 12
\^/T120C G2 LED60S/865 PSU L1500/ WT120C G2 LED58S/830 PSU L1500

Installation Instructions

Installation Instructions
Installation Instructions
Installation Instructions
Installation Instructions
Installation Instructions

  • Do not stare into LED light beam.
  • The luminaire shall be installed by a qualified electrician and wired in accordance with the latest IEE electrical regulations or the national requirements,
  • The light source contained in this luminaire shall only be replaced by the manufacturer or his service agent or a similar qualified person.
  • Above average concentration of sulfur effects the useful life time of the product. Eg: Light color changes from white to blue. Typically in chicken & pig farms.
  • For use in environments where an accumulation of conductive dust on the luminaire may be expected.
  • Do not install the luminaire on the location where it is exposed to heavily grease, esp. mineral oil and distillates (petroleum), heavy naphthenic treated with hydrogen.
  • This product is not suitable for cold & humid storage areas, especially where obvious temperature gradients are present, such as ventilation opening, door, etc.
  • Do not install the luminaire on locations where itis exposed to direct sunlight. UV radiation will damage the material over time resulting in loss of waterproof sealing and P65 rating.

 | LED19S
LED18S| LED27S
LED25S| LED4OS
LED37S| LED345
LED31S| LED6OS
LED57S| LED8OS
LED75S
---|---|---|---|---|---|---
Driver I peak [A]| 3.58| 3.58| 14.2| 5.16| 14.2| 15
Driver Tref bisl| 40| 40| 222| 47| 222| 240
Max. Nr. of connecting products by MCB type
MCB 16A type B| 80| 80| 36| 60| 36| 31
MCB 10A type B| 50| 50| 22| 37| 22| 19
MCB 16A type C| 136| 136| 60| 102| 60| 52
MCB 10A type C| 80| 80| 37| 62| 37| 32
Max. Nr. of connecting products by through wire cross-section area
1.0 mm2| 45| 33| 23| 27| 16| 11
1.5 mm2| 67| 49| 35| 41| 23| 18
2.5 mm2| 112| 82| 59| 69| 39| 29
According to MCB type & through wire cross-section area, choose the mininum number to connect products.