DELTACO SH-AC02H Smart Portable AC User Manual

October 30, 2023
DELTACO

DELTACO SH-AC02H Smart Portable AC

DELTACO-SH-AC02H-Smart-Portable-AC-PRODUCT

Product Information

SMART PORTABLE A/C

  • Brand A Nordic Brand
  • Model SH-AC02H

Languages

  • Danish
  • German
  • English
  • Estonian
  • Finnish
  • French
  • Hungarian
  • Latvian
  • Lithuanian
  • Dutch
  • Norwegian
  • Polish
  • Spanish
  • Swedish

Safety Instructions

The product contains refrigerant hydrocarbon R290 which is flammable. The product must be installed and used according to the national wiring regulations. The cable should be replaced by the manufacturer, retailer, or authorized electrician if damaged. The packaging should be disposed of according to local regulations.

Features

  • Nominal Voltage: 220-240V ~ 50Hz
  • Safety fuse type: 5ET or SMT, 250V, 3.15A
  • Low Global Warming Potential (GWP of 3)
  • The maximum dosage of refrigerant is 150 grams.

Product Usage Instructions

Installation

The product must be installed according to national wiring
regulations. The recommended placement of the Klettbandes should be
followed. The power cable must not be covered.

Operation

The product has four modes of operation: Entfeuchtungsmodus, Frostschutz, Automatische Auftauen, and Kompressor Schutz. The product has a control panel, wheels, air outlet, upper filter, continuous drainage hole, air ventilation, lower filter, drainage hole, attachment holes for a power plug (for storage and travel), handle, air inlet, power cable, ventilation pipe, and window kit.

Maintenance and Cleaning

The product must be maintained and cleaned regularly. Please refer to the manual for the instructions.

Disposal

The packaging should be disposed of according to local regulations. The product must be disposed of in accordance with the manufacturer’s instructions.

Support

For further product information, please visit www.deltaco.eu.

Safety instructions

Warning

  1. Only connect this product to earthed sockets and matching voltage to prevent electrical shock. Find the voltage information on the product’s rating label. If you feel unsure, or if you are missing a matching socket, contact an authorised electrician for installation help.
  2. Place the product on a sturdy, flat and dry surface, with at least 50 cm to other objects or walls. Keep the product at least 1 meter away from combustible materials.
  3. Ensure that the power plug is firmly connected to the power socket. Do not place the cable under carpets. Do not cover the cable with cable runners or similar covering objects. Do not route the cable underneath furniture or other appliances. Place the cable away from trafficked areas, to ensure that nobody can trip over it.
  4. Keep the product free from obstructions, to ensure proper function and reduce safety hazards.
  5. Ensure that the drainage pipes are properly connected, and are not distorted or bended.
  6. When moving this product, make sure that it is in an upright position. It has wheels to make it easier. Do not roll over objects and be careful on carpets or avoid them, as the product can tip over.
  7. Do not install the product in a location where it may be exposed to combustible gas (For example close to a gas stove). Possible fire hazard.
  8. Don’t disassemble or modify the product, it will cause malfunctions or bring harm to persons and properties. To avoid danger, if a machine failure occurs, ask our support, the retailer or authorised professionals to repair it.
  9. Do not install or use the product in a wet area such as a bathroom or a laundry room. Water may cause short-circuits.
  10. Protect this product from liquids such as condensation, splashes, etc. Do not position it so it could fall or be pulled into water or any other liquids. If this would happen, unplug the product from the mains immediately.
  11. Be sure that the power plug pulls out straight and directly from the wall. Do not pull the cable when disconnecting the product out of the wall. The power plug should always be easy accessible.
    • Caution
  12. If the cable is damaged, it must be replaced by the manufacturer, retailer or authorized electrician in order to avoid hazards.
  13. The product must be installed in accordance with national wiring regulations.
  14. This product can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved.
  15. Children shall not play with this product.
  16. Cleaning and user maintenance should not be made by children unless they are older than 8 years and supervised.
  17. Before cleaning or maintenance, switch off the device and disconnect the product from the mains. Never clean this product when it is connected to power!
  18. Do not use chemical solvents such as gasoline and alcohol to clean the product. Clean it with a half-wet soft cloth. If the product is really dirty, use a mild detergent.
  19. Do not use flammable substances near the product, such as alcohol and insecticide sprays.
  20. Do not cover or obstruct the air inlet or outlet. Keep the inlet and outlet free from obstructions.
  21. Do not pull the power plug to turn off the machine.
  22. When adjusting the plastic air outlet, don’t use objects. Instead use your hands. To avoid damaging the plastic surface.
    • Safety instructions for R290 refrigerant
  23. Do not use cleaning methods or ways to speed up the defrosting process that have not been recommended by the manufacturer.
  24. The appliance shall be stored in a room without continuously operating ignition sources (for example open flames, an operating gas appliance, or an operating electric heater.)
  25. Do not pierce or burn.
  26. Be aware that refrigerants might be odorless.
  27. Appliance shall be installed, operated and stored in a room with a floor area larger than 30m2.
  28. The room’s ventilation openings must be kept clear of obstructions.
  29. Compliance with national gas regulations must be observed.
  30. The appliance must be stored in a well-ventilated area where the room area corresponds to the room area specified for operation (30m2).
  31. Anyone working refrigerant circuits should hold a current valid certificate from an industry-accredited assessment authority, which authorises their competence to handle refrigerants safely in accordance with an assessment specification recognized by the industry.
  32. This product shall only be serviced as recommended by the manufacturer.
  33. Maintenance and repair that requires other authorised personnel shall be carried out under the supervision of the person competent in the use of flammable refrigerants.
  34. This product is only for indoor use.
  • WARNING: Risk of fire/flammable materials (R290)
  • CAUTION: Read this manual carefully before installing or operating this product. Make sure you save this manual for future reference.
  • CAUTION: This symbol indicates that service personnel should handle this equipment, with reference to the installation manual.
  • CAUTION: This symbol indicates that information such as a manual is available.

Transportation, marking and storage (R290)

  1. Transport of equipment containing flammable refrigerants See transport regulations.
  2. Marking of equipment using signs See local regulations.
  3. Disposal of equipment containing flammable refrigerants See national regulations.
  4. Storage of equipment/appliances Equipment should be stored in accordance with the manufacturer’s instructions.
  5. Storage of packed (unsold) equipment Storage package protection should be designed such that mechanical damage to the equipment inside the package will not cause the refrigerant to leak. Local regulations determine the maximum number of items of equipment that can be stored together.
  6. Information on servicing
  7. Checks to the area
  * Before starting any work on systems containing flammable refrigerants, safety checks are necessary to ensure that the risk of ignition is minimised. For repairs to the refrigerating system, the following precautions must be taken with before starting work on the system.
2.  **Work procedure**
  * Work must follow a controlled procedure to minimise the risk flammable gas or vapour being present while the work is in progress.
3.  **General work area**
  * All maintenance staff and others working in the vicinity of the product must be instructed on the nature of work being carried out. Work in confined spaces must be avoided. The area around the workspace must be sectioned off. Ensure that the conditions within the area have been made safe by checking for flammable materials.
4.  **Checking for the presence of refrigerant**
  * The area must be checked using an appropriate refrigerant detector before and during work, to ensure that the technician is aware of any potentially flammable atmospheres. Ensure that the leak detection equipment being used is suitable for use with flammable refrigerants, i.e. non-sparking, adequately sealed or intrinsically safe.
5.  **Fire extinguishers**
  * If any hot work is to be conducted on the refrigeration equipment or any associated parts, appropriate fire extinguishing equipment must be available. Keep a dry powder or CO2 fire extinguisher adjacent to the charging area.
6.  **No ignition sources**
  * Anyone carrying out work on a refrigeration system that involves exposing any pipework that contains or has contained flammable refrigerants must not use any sources of ignition in such a manner that there is potential risk of fire or explosion. All possible ignition sources, including smoking, should be kept sufficiently far away from the site of installation, repair work, removal and disposal as flammable refrigerant may be released into the surrounding atmosphere. Before any work takes place, the area around the equipment must be surveyed to make sure that there are no flammable hazards or ignition risks. No Smoking signs must be displayed.
7.  **Ventilated area**
  * Ensure that the area is in the open or that it is adequately ventilated before opening the system or conducting any hot work. Some ventilation must be provided while the work is in progress. The ventilation should safely disperse any released refrigerant and, ideally expel it to the atmosphere outdoors.
8.  **Checking the refrigeration equipment**
  * Electrical components that are being replaced must be fit for the purpose and to the correct specification. The manufacturer’s maintenance and service guidelines must be followed at all times. If in doubt consult the manufacturer’s technical department for assistance.
  * The following checks shall be applied to installations using flammable refrigerants:
  * The charge size is in accordance with the room size within which the refrigerant containing parts are installed;
  * The ventilation system and outlets are operating adequately and are not obstructed;
  * If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for the presence of refrigerant;
  * The labelling of the equipment is still visible and legible. Labels and signs that are illegible must be replaced;
  * Refrigeration pipes or components are installed in a location where they are unlikely to be exposed to any substance which may corrode components containing refrigerant, unless the components are made of materials which are inherently resistant to corrosion or are suitably protected against corrosion.
9.  **Checking electrical devices**
  * Repair and maintenance of electrical components must include initial safety checks and component inspection procedures. If there is a fault that could compromise safety, no power supply may be connected to the circuit until the fault has been corrected. If the fault cannot be corrected immediately but continuing operation necessary, an adequate temporary solution must be used. This must be reported to the owner of the equipment so that all parties are advised. Initial safety checks must include:
  * Discharge of capacitors: this must be done in a safe manner to prevent sparking;
  * Ensuring that there are no live electrical components or wiring exposed while charging, recovering or purging the system;
  * That there is continuity of earth bonding.
  1. Repairs to sealed components
  2. When repairing sealed components, all power supplies must be disconnected from the equipment being worked upon before any removal of sealed covers, etc. If it is absolutely necessary to maintain a power supply to equipment during servicing, a permanently operating form of leak detection must be located at the most critical point to provide a prior warning of any potentially hazardous situation.
  3. Particular attention must be paid to the following to ensure that working on electrical components does not result in alteration of the casing is in such a way that the level of protection is affected.
  * This must include damage to cables, excessive number of connections, terminals not made to original specification, damage to seals, incorrect fitting of cable glands, etc.
  * Ensure that apparatus is mounted securely.
  * Ensure that seals or sealing materials have not degraded such that they no longer prevent the ingress of flammable atmospheres. Replacement parts must be in accordance with the manufacturer’s specifications.
  *  **NOTE:** The use of silicon sealant may inhibit the effectiveness of some types of leak detection equipment. Intrinsically safe components do not have to be isolated prior to working on them.

Repairing intrinsically safe components

Do not apply any permanent inductive or capacitance loads to the circuit without ensuring that this will not exceed the permissible voltage and current permitted for the equipment in use.
Intrinsically safe components are the only types that can be worked on while live in the presence of a flammable atmosphere. The test apparatus must be at the correct rating.
Replace components only with parts specified by the manufacturer. Other parts may result in the ignition of leaked refrigerant in the atmosphere.

Cabling

Check that cabling will not be subject to wear, corrosion, excessive pressure, vibration, sharp edges or any other adverse environmental effects.
The check must also take into account the effects of aging or constant vibration from sources such as compressors or fans.

Detection of flammable refrigerants

  • Under no circumstances should potential sources of ignition be used when searching for or detecting refrigerant leaks. Halide torches (or any other detector using naked flames) must not be used.

Leak detection methods

  • The following leak detection methods are deemed acceptable for systems containing flammable refrigerants. Electronic leak detectors may be used to detect flammable refrigerants, but the sensitivity may not be adequate or may need re-calibration.
  • (Detection equipment must be calibrated in a refrigerant-free area.) Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used. Leak detection equipment shall be set at a percentage of the LFL of the refrigerant and must be calibrated to the refrigerant used and the appropriate percentage of gas (25 % maximum) must be confirmed.
  • Leak detection fluids are suitable for use with most refrigerants, but the use of detergents containing chlorine must be avoided as the chlorine may react with the refrigerant and corrode the copper pipework.
  • If a leak is suspected, all naked flames must be removed/extinguished.
  • If a leakage of refrigerant is found that requires brazing, all of the refrigerants must be recovered from the system or isolated (by means of shut-off valves) in a part of the system not affected by the leak. Oxygen-free-nitrogen (OFN) must then be passed through the system both before and during the brazing process.

Removal and evacuation

  • Conventional procedures must be used when accessing the refrigerant circuit for repairs or any other purpose. However, it is important that best practice is followed since flammability must be considered. The following procedure must be adhered to:
  • Remove the refrigerant;
  • Purge the circuit with inert gas;
  • Evacuate the circuit;
  • Purge again with inert gas;
  • Open the circuit by cutting or brazing.
  • The refrigerant charge must be recovered into the correct recovery cylinders. The system must be flushed with OFN to render the unit safe. This process may need to be repeated several times. Compressed air or oxygen must not be used for this task.
  • Flushing must be achieved by breaking the vacuum in the system using OFN and continuing to fill until the working pressure is achieved, then venting to the atmosphere, and finally reducing to a vacuum pressure. This process must be repeated until there is no refrigerant left in the system. When the final OFN charge is used, the system must be ventilated to atmospheric pressure to enable work to take place. This operation is absolutely vital if brazing operations are to take place on the pipework.
  • Ensure that the power socket for the vacuum pump is not close to any ignition sources and that there is ventilation available.

Charging procedures

  • In addition to conventional charging procedures, the following requirements must be met.
  • Ensure that there is no contamination of different refrigerants when using charging equipment. Hoses or lines must be as short as possible to minimise the amount of refrigerant contained in them.
  • Cylinders must be kept upright.
  • Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
  • Label the system when charging is complete (unless it is already labelled).
  • Extreme care must be taken not to overfill the refrigeration system.
  • The system must be pressure-tested using OFN prior to recharging. The system must be tested for leaks on completion of charging but prior to commissioning. A follow-up leak test must be carried out prior to leaving the site.

Decommissioning

  • Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its details. It is recommended good practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample must be taken in case analysis is required prior to reuse of reclaimed refrigerant. It is essential that electricity is available before starting the task.
  • a) Familiarise yourself with the equipment and its operation.
  • b) Isolate the system electrically.
  • c ) Before attempting the procedure ensure that:
  • Mechanical equipment is available, if required, for handling refrigerant cylinders;
  • All personal protective equipment is available and being used correctly;
  • The recovery process is supervised at all times by a competent person;
  • Recovery equipment and cylinders conform to the appropriate standards.
  • d) Pump down refrigerant system, if possible.
  • e) If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.
  • f) Make sure that the cylinder is placed on the scales before recovery takes place.
  • g) Start the recovery machine and operate in accordance with manufacturer’s instructions.
  • h ) Do not overfill cylinders. (No more than 80 % liquid charge by volume).
  • i) Do not exceed the maximum working pressure of the cylinder, even temporarily.
  • j) When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from the site promptly and that all isolation valves on the equipment are closed off.
  • k ) Recovered refrigerant must not be charged into another refrigeration system unless it has been cleaned and checked.

Labeling

  • Equipment must be labelled stating that it has been decommissioned and emptied of refrigerant. The label must be dated and signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant.

Recovery

  • When removing refrigerant from a system, either for servicing or decommissioning, ensuring that all refrigerants are removed safely is recommended good practice.
  • When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are used. Ensure that the correct number of cylinders for holding the total system charge are available. All cylinders to be used must be designated for the recovered refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of refrigerant). Cylinders must be complete with pressure relief valves and associated shut-off valves in good working order. Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs.
  • The recovery equipment must be in good working order with instructions concerning the equipment being used and must be suitable for the recovery of flammable refrigerants. A set of calibrated weighing scales must also be available and in good working order. Hoses must be complete with leak-free disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. If in doubt consult the manufacturer.
  • The recovered refrigerant must be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants in recovery units and especially not in cylinders.
  • If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to ensure that flammable refrigerant does not remain within the lubricant. The evacuation process must be carried out prior to returning the compressor to the supplier. Only electric heating to the compressor body shall be used to accelerate this process. Oil must be drained from systems safely.

Fluorinated gases

  • Fluorinated gases are contained in hermetically sealed equipment. For information on the type, quantity and CO2 equivalent in tonnes of fluorinated greenhouse gas, please see the label.
  • Installation, servicing, maintenance and repair of this unit must be performed by a certified technician.
  • The product must be removed and recycled by a certified technician.

Circuit diagram

The maximum dosage of refrigerant is 150 grams. DELTACO-SH-AC02H-Smart-
Portable-AC-FIG-1

  1. Compressor
  2. Condenser
  3. Capillary
  4. Evaporator

Thank you

Thank you for choosing Deltaco!

R290

The product contains the refrigerant hydrocarbon R290. Compared to alternative refrigerants it is more environmentally friendly. Low Global Warming Potential (GWP of 3).

Overview

  1. Control panel
  2. Wheels
  3. Air outlet
  4. Upper filter
  5. Continuous drainage hole
  6. Air ventilation
  7. Lower filter
  8. Drainage hole
  9. Attachment holes for power plug (For storage and travel)
  10. Handle
  11. Air inlet
  12. Power cable (Must not be covered)
  13. Ventilation pipe
  14. Window kit

Controls

When the device is connected to power, the device will enter standby status and play a confirmation sound.

  1. Timer button: The timer can be used to automatically turn on or to turn off the device. Press to turn on the timer, the LED display flashes to confirm. Use the up and down buttons to select time. The settings are 1 to 24 hours. Each press adjusts the time by 1 hour.
  2. Fan speed button: Press to change fan speed. Settings are: High, medium and low. Changing fan speed is not available in dehumidifying mode.
  3. Up and down buttons: Press to change temperature or timer value. Not available in fan or dehumidifying mode.
  4. LED display.
  5. Mode button: Press to switch between cooling / heating / fan / dehumidifying mode.
  6. On/off button : Press to turn the device on or off.
  7. Sleep mode button: On the remote press to turn on sleep mode. On the device press Up + Fan speed button to turn on sleep mode. Fan speed will decrease to low.
  8. Up/down swing button: Press to turn the swinging motion on or off.
  9. Celsius/Fahrenheit button: Press to switch between Celsius and Fahrenheit.

Dehumidifier mode

  • When using this product in dehumidifying mode, use a drainage solution to lead away the accumulating water. See drainage instructions. The LED status for dehumidifier mode shows as active with the letters “dh” on the control panel.

Frost protection

  • In cooling, dehumidifying or sleep mode, the device will automatically enter protection status if the temperature of the ventilation pipe is too low. If the temperature of the ventilation pipe rises again, it will automatically return to normal operation.

Overflow protection

  • When the water exceeds the max level, the device will play a sound, and the control panel will flash the LED with the word “FULL”. You need to empty the water, see the drainage instructions chapter. After the water is emptied, it will automatically return to normal operation.

Automatic defrosting

  • This device has automatic defrosting. Defrosting is achieved through four-way valve reversing.

Compressor protection

  • The compressor has a 3-minute reboot delay that prevents it from starting after it has just been turned off. To increase the lifespan of the compressor.
Installation
  • Warning: before using the device, keep it upright for at least two hours.
  • The device should be kept in the upright position and placed on a flat surface. Do not install or use it in the bathroom or other humid environments.
  • Connect the ventilation pipe to the two plastic adapters. Extend the pipe and rotate them together. Connect the assembled pipe to the air ventilation (6.) of the device.
  • Open the window, and mount the window kit (14.) to the window. Can be mounted horizontally or vertically. Adjust the window kit to fit into the window frame, screw, and fixate the parts.
  • The distance between the product and walls or other objects must be at least 50 cm.
  • Elongate the ventilation pipe and connect it to the hole of the window kit.
  • The ventilation pipe must not be distorted or be bent over 45°.

Cloth window seal

  • Alternatively, you can install the cloth seal:DELTACO-SH-AC02H-Smart-Portable-AC-FIG-8
  1. Mark the middle “M” of the unfolded cloth seal before installing, it to easier find the middle later.DELTACO-SH-AC02H-Smart-Portable-AC-FIG-9
    • Illustrations showing different window types. With suggested “A” and “B” markings. And suggested opening marked with “S”.
  2. Mark the middle on the window’s edge with “A” and “B” for example, or your choice of marks. The marks (“A” and “B”) must be placed exactly in opposite positions of each other.
  3. Place the hook-and-loop fastener tape on the edge of the window (usually 1 cm wide), where the window handles are attached.
  4. Now fasten the seal to the hook-and-loop fastener. First side “A”, then side “B”. Begin in the middle and work all the way to the up and down or left and right depending on window type.
  5. When closing the window take care that the seal does not get stuck on the window’s edge.
  6. Open the zip preferably at the position marked with “S” and attach the exhaust hose.

Important notice

  • The length of the ventilation pipe must be 280-1500 mm, the length is based on the specifications of the product. Do not use extension pipes or replace it with a different type of pipe, or this may cause a malfunction. Do not block the ventilation outlet, otherwise it may cause overheating.

Maintenance and cleaning

  • Before cleaning and maintenance, turn the product off and unplug the power plug.
  • Clean with surface with a wet soft cloth. Don’t use chemicals, such as benzene, alcohol, gasoline. The surface could be damaged or the whole product could be damaged.
  • When the filters are filled with dust, the effectiveness will be reduced. Be sure to clean the filters every two weeks
  1. Upper filter
  2. Screws
  3. Filter protection
  4. Lower filter
  • Pull out the filter protection and take out the upper filter by removing the screws. Pull out the lower filter.
  • Put the filters in about 40℃ / 104℉ warm water with a mild detergent. Rinse clean. Dry them in the shade. Put the filters and the filter protection back on the device.

Storage

  1. Empty the water (See the drainage instructions).
  2. Turn on the device, and set it to low fan speed until the device is dry.
  3. Turn off the device, unplug the power plug, re-plug the water plug and the drainage cover. Remove the ventilation pipe.
  4. Cover the product with a plastic bag to protect it from dust. Put it in a dry place, keep it out of reach of children.
  5. Remove batteries from the remote control.

Drainage instructions

This product has two drainage methods: manual drainage and continuous drainage.

Manual drainage:

  1. To empty the water, turn off the product, and unplug the power plug.

    • Note: Move the product carefully, to avoid internal water leakage.
  2. Place a water container below the drainage hole (8).

  3. Unscrew the drainage cover and unplug the plug, the water will flow into the water container.

    • Note 1: you can tilt the product slightly to empty more water.
      Note 2: if the water container can’t hold all the water, re-plug until you emptied the water container.
  4. When it has been emptied of water, re-plug and screw back the drainage cover.

Continuous drainage:

  1. Unscrew the drainage cover, and unplug the plug.
  2. Connect a drainage pipe to the continuous drainage (5.).
  3. Place a bucket under the drainage pipe.

Troubleshooting

  • Do not repair or disassemble the product by yourself. Unqualified repair will lead to failure and may cause damage to persons or their properties.
  • Problem: The product does not turn on or does not work.
  • Cause 1: There is no electricity from the power socket. Solution 1: Connect to a socket with electricity and turn it on. Cause 2: The control panel’s LED “FULL” is turned on. Solution 2: Empty the water.
  • Cause 3: The ambient temperature is too low or too high. Solution 3: Recommended working temperatures are 7-35℃ (44-95℉).
  • Cause 4. In cooling mode, the room temperature is lower than the set temperature. In heating mode, the room temperature is higher than the set temperature. Solution 4: Change the set temperature.
  • Cause 5. In dehumidification mode, the ambient temperature is low. Solution 5: Place the product in a room with an ambient temperature of greater than 17℃ (62℉).
  • Problem: The cooling effect is not good.
  • Cause 1: There is direct sunlight. Solution 1: Use a curtain.
  • Cause 2: Doors or windows are open, there are a lot of people or other sources of heat. Solution 2: Close doors and windows, add another air conditioner.
  • Cause 3: The filters are dirty. Solution 3: Clean or replace the filters.
  • Cause 4: The air inlet or outlet is blocked. Solution 4: Remove obstructions.

Problem: A lot of noise.

  • Cause 1: The product is not placed on a flat surface. Solution 1: Place the product on a flat and hard surface. Problem: Compressor does not work.
  • Cause 1: Overheat protection starts. Solution 1: Wait for 3 minutes until the temperature is lowered, restart the product. Problem: The remote control does not work.
  • Cause 1: The distance to the product is too far or the remote control is not aligned with the direction of the receiver. Solution 1: Let the remote control get closer and make sure that the remote control faces the direction of the receiver. Cause 2: The batteries are low. Solution 2: Replace the batteries.

Problem: The LED Display shows ‘E1’ or ‘E2’.

  • Cause 1, E1: The pipe’s temperature sensor is abnormal. Solution 1: Check the pipe temperature sensor and related circuitry.
  • Cause 2, E2: The room temperature sensor is abnormal. Solution 2: Check the room temperature sensor and related circuitry.

Install and use

  1. Download and install the app “Deltaco smart home” from Apple App Store or Google Play Store on your mobile device.
  2. Launch the app “Deltaco smart home“.
  3. Create a new account or log in to your existing account.
  4. Tap “+” to add the device.
  5. Choose a category and then the type of product from the list.
  6. Connect the device to power.
  7. Press and hold the fan mode button for about 5 seconds to activate wifi, a confirmation sound will be played, confirming that wifi is activated. Add the device to Deltaco smart home app.
  8. Confirm the Wi-Fi network and password.
  9. Enter the device name.

Properties

  • Rated voltage: 220-240V ~ 50Hz
  • Fuse type: “5ET” or “SMT”, 250V, 3.15A

Support

Disposal of the packaging

  • The carton can be used for storing or moving the product. Dispose of the packing material by recycling it, according to your local regulations.

Disposal of the product

  • Disposal of electric and electronic devices

EC Directive 2012/19/EU

  • This product is not to be treated as regular household waste. It must be returned to a collection point for recycling electric and electronic devices. Further information is available from your municipality, your municipality’s waste disposal services, or the retailer where you purchased your product.
  • Disposal of electric and electronic devices EC Directive 2012/19/EU This product is not to be treated as regular household waste but must be returned to a collection point for recycling electric and electronic devices. Further information is available from your municipality, your municipality’s waste disposal services, or the retailer where you purchased your product.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals