visionLINE Pera Freestanding 3 x Sided Wood Fireplace
visionLINE Pera Freestanding 3 x Sided Wood Fireplace
PERA – AU Freestanding
Product Information
The PERA – AU is a freestanding wood fire appliance manufactured by Burning Technology at Stupkova – 952/18, Nova Ulice, 77900, Olomouc – Czech Republic EU. This product has been tested to AS/NZS4013 for Hardwood by ASFT Report 22021 with a test date of 7 April 2022. The product is compliant with Woodfire Compliance Label. The PERA – AU has an overall average efficiency of 61% and an average particulate emission factor of 1.0 G/KG when tested in accordance with AS/NZS 4012 and AS/NZS 4013 respectively. The maximum average heat output of the product is 9.8 KW. The catalytic combustor is not present in this product. The approved fuel for this product is burning only hardwood with a moisture content less than 20%. Wetbacks are not approved options and must not be fitted.
Product Usage Instructions
Before starting the installation process, please read all instructions carefully as failure to follow these instructions may result in a fire hazard and void the warranty. This product is for use with solid wood fuel only. Other fuels may overfire and generate poisonous gases (i.e. carbon monoxide). The product dimensions and installations must comply with AS/NZS2918:2018, and building consent may be required.
The minimum clearance from the firebox to the rear wall (A) should be 6 inches with 8 solid or mesh casing 150mm (B). The minimum clearance from the firebox to the side wall (B) should be 575mm (C). The minimum distance from the firebox opening to the floor protector front (C) should be 300mm, and the minimum distance from the firebox to the floor protector side (D) should be 139mm. The minimum distance from the centre of the flue to the side wall (E) should be 776mm. The minimum depth of the floor protector (F) should be 670mm, and the width of the floor protector (G) should be 680mm. The hearth thickness should be 6mm thickness floor protector (compressed board) used under and in front of the appliance base when installing the appliance (see joint AS/NZS 2918:2018 3.3.2).
The minimum depth (F) will mean there is space behind the appliance where a floor protector isn’t required but may be desired aesthetically. Add (A) measurement to complete the hearth to the wall behind. If being installed against a fully non-combustible wall, 50mm spacing is recommended for servicing access. The minimum clearance from the firebox to the corner wall (A) should be 6 inches with 8 solid or mesh casing 325mm (B). The minimum distance from the firebox opening to the floor protector front (C) should be 300mm, and the minimum distance from the wall to the floor protector front corner (D) should be 705mm. The width of the floor protector (E) should be 680mm, and the centre of flue to side walls (F) should be positioned parallel to each other as shown in Fig. 1.
Please note that the product requires a minimum hearth projection of 300mm when using an optional wood storage base/pedestal.
WOODFIRE COMPLIANCE LABEL
This appliance has been TESTED TO AS/NZS4013 for Hardwood by ASFT Report 22021
Date tested: 7 April 2022
OVERALL AVERAGE EFFICIENCY
WHEN TESTED IN ACCORDANCE WITH AS/NZS 4012……61%
AVERAGE PARTICULATE EMISSION FACTOR
WHEN TESTED IN ACCORDANCE WITH AS/NZS 4013……1.0 G/KG
MAXIMUM AVERAGE HEAT OUTPUT ……….9.8 KW
CATALYTIC COMBUSTOR ……….NO
APPROVED FUEL ……………………………………………………………………BURN ONLY HARDWOOD WITH A MOISTURE
CONTENT LESS THAN 20%
Wetback – All Models ……………………………………………………………….Wetbacks are NOT approved option
and must
Not be fitted
Manufactured By: …………………………………………………………………….Burning Technology – Stupkova –
952/18, Nova
Ulice, 77900, Olomouc – Czech Republic EU
INSTALLATIONS TO COMPLY WITH AS/NZS2918:2018 AND MAY REQUIRE A BUILDING
CONSENT
IMPORTANT: Read all instructions carefully before starting installation.
Failure to follow these instructions may result in a fire hazard and will void
the warranty.
- Fig. 3,4,5 and Table 1 & 2 relate to installations with tested flue systems; as per AS/NZS 2918:2018 – Appendix F, with a ceiling angle between 0° – 30° inclusive.
- For installations with a ceiling angle greater than 30°, refer to Fig. 6 & 7 and AS/NZS 2918:2018 4.6.3(b)
- Ceiling Plate may vary in size depending on ceiling angle. Please specify ceiling pitch prior to ordering the ceiling plate.
WARNING
Fire Risk For use with solid wood fuel only. Other fuels may over fire and
generate poisonous gases (i.e. carbon monoxide).
WARNING
If the information in these instructions is not followed exactly, a fire could
result causing property damage, personal injury, or death.
- Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
- Do not over fire – If appliance or chimney connector glows, you are over firing. Over firing will void your warranty.
- Comply with all minimum clearances to combustibles as specified. Failure to comply may cause house fire.
UNIT DIMENSIONSA
The VisionLINE Pera may require an insulating Floor Protector depending on the
installation type. It is tested and complies with the minimum Floor Protector
requirements of AS/NZS 2918:2018. See below for Hearth specifications.
Note:
- The minimum Floor Protector sizes are specified in the clearance chart, see Table 1, 2 and 3.
- A Floor Protector can include ceramic tiles with grouted joints fixed directly onto a wooden floor or a Steel panel or any other non combustible material laid directly onto a wooden floor.
- If installed directly onto a concrete slab, the concrete slab can be considered as the floor protector, but must maintain the minimum measurement listed.
PARALLEL POSITIONING
| PERA – AU| Default 6inch with 8” Solid or Mesh CASING
---|---|---
A| Min Clearance from firebox to rear wall| 150mm
B| Min Clearance from firebox to side wall| 575mm
C| Min Distance from firebox opening to floor protector front| 300mm
D| Min distance from firebox to floor protector side| 139mm
E| Min distance from centre of flue to side wall| 776mm
F| Min depth of floor protector| 670mm
G| Width of floor protector| 680mm
Hearth Thickness – 6mm thickness floor protector (compressed board) should be
used under and in front of the appliance base when installing the appliance
(see joint AS/NZS 2918:2018 3.3.2).
Minimum depth (F) will mean there is space behind the appliance where a floor
protector isn’t required but may be desired aesthetically. Add (A) measurement
to complete the hearth to the wall behind.
If being installed against a fully non-combustible wall, 50mm spacing is
recommended for servicing access.
Please note: 300mm hearth projection min. when using optional wood storage base/pedestal
| PERA – AU| Default 6inch with 8” Solid or Mesh CASING
---|---|---
A| Min. Clearance from firebox to corner wall| 325mm
B| Min depth of floor protector| 670mm
C| Min. Distance from firebox opening to floor protector front| 300mm
D| Min distance from wall to floor protector front corner| 705mm
E| Width of floor protector| 680mm
F| Centre of flue to side walls| 575mm
G| Corner wall to overall square hearth| 1175mm
FIREBOX INSTALLATION
- If a separate floor protector is being used position now. Place the firebox on the floor protector that is at least 6mm thick to suit the minimum installation clearances. (See Fig 1,2 and 3).
- Seismically restrain the firebox
and the floor protector to the floor.
WARNING
Fire Risk.
VisionLINE fireplaces disclaims any responsibility for, and the warranty will
be voided by, the following actions:
- Installation and use of any damaged appliance.
- Modification of the appliance.
- Installation other than as instructed by VisonLINE fireplaces.
- installation and/or use of any component part not approved by VisionLINE fireplaces.
- Operating appliance without fully assembling all components.
- Do NOT Over fire – If appliance or chimney connector glows, you are over firing.
Any such action that may cause a fire hazard.
Install Guide
Getting Started
Design and Installation Considerations Consideration must be given to:
- Safety
- Convenience
- Traffic flow
- Chimney and chimney connector required
It is a good idea to plan your installation on paper, using exact measurements
for clearances and floor protection, before actually beginning the
installation. If you are not using an existing chimney, place the appliance
where there will be a clear passage for a factory-built listed chimney through
the ceiling and roof.
We recommend that a qualified building inspector and your insurance company
representative review your plans before and after installation.
If this appliance is in an area where children may be near it is recommended
that you purchase a decorative barrier to go in front of the appliance.
Remember to always keep
children away while it is operating and do not let anyone operate this
appliance unless they are familiar with these operating instructions.
CAUTION
Check building codes prior to installation.
- Installation MUST comply with local, regional, state and national codes and regulations.
- Consult insurance carrier, local building, fire officials or authorities having jurisdiction about restrictions, installation inspection, and permits.
WARNING
Asphyxiation Risk.
- Do NOT connect this appliance to a chimney flue servicing another appliance.
- Do NOT connect to any air distribution duct or system.
May allow flue gases to enter the house.
NOTICE: VISIONLINE FIREPLACES ASSUMES NO RESPONSIBILITY FOR THE IMPROPER PERFORMANCE OF THE APPLIANCE SYSTEM CAUSED BY:
- Inadequate draft due to environmental conditions
- Down drafts
- Tight sealing construction of the structure
- Mechanical exhausting devices
- Over drafting caused by excessive chimney heights
- Ideal performance is with height of chimney between 14-16 feet (4.26-4.88m) measured from the base of the appliance.
Fire Safety
To provide reasonable fire safety, the following should be given serious
consideration:
- Install at least one smoke detector on each floor of your home to ensure your safety. They should be located away from the heating appliance and close to the sleeping areas. Follow the smoke detector manufacturer’s placement and installation instructions, and be sure to maintain regularly.
- A conveniently located Class A fire extinguisher to contend with small fires resulting from burning embers.
- A CO detector should be installed in the room with the appliance.
- A practiced evacuation plan, consisting of at least two
- A plan to deal with a chimney fire as follows: In the event of a chimney fire:
- Evacuate the house immediately
- Notify fire department.
Negative Pressure
WARNING
Asphyxiation Risk.
- Negative pressure can cause spillage of combustion fumes, soot and carbon monoxide.
- Appliance needs to draft properly for safety.
Negative pressure results from the imbalance of air available for the appliance to operate properly. It can be strongest in lower levels of the house.
Causes include:
- Exhaust fans (kitchen, bath, etc.)
- Range hoods
- Combustion air requirements for furnaces, water appliances and other combustion appliances
- Location of return-air vents to furnace or air conditioning
- Imbalances of the HVAC air handling system
- Upper level air leaks such as:
- Recessed lighting
- Attic hatch
- Duct leaks
- To minimize the effects of negative air pressure: • Install optional outside air kit with the intake
- Ensure adequate outdoor air for all combustion appliances and exhaust equipment
- Ensure furnace and air conditioning return vents are not located in the immediate vicinity of the appliance
- Avoid installing the appliance near doors, walkways or small isolated spaces
- Recessed lighting should be a “sealed can” design
- Attic hatches weather stripped or sealed
- Attic mounted duct work and air handler joints and seams taped or sealed
- Basement installations should be avoided
WARNING
Fire Risk.
VisionLINE fireplaces disclaims any responsibility for, and the warranty will
be voided by, the following actions:
- Installation and use of any damaged appliance.
- Modification of the appliance.
- Installation other than as instructed by VisionLINE fireplaces.
- Installation and/or use of any component part not approved by VisionLINE fireplaces. Operating appliance without fully assembling all components.
- Operating appliance without legs attached (if supplied with appliance).
- Do NOT Over fire – If appliance or chimney connector glows, you are over firing.
Any such action that may cause a fire hazard.
Tools And Supplies Needed
Before beginning the installation be sure the following tools and building
supplies are available:
- Reciprocating saw
- Framing material Pliers
- High temp caulking material Hammer
- Gloves
- Phillips screwdriver
- Framing square 1/2-3/4 in. length, #6 or #8 self-drilling screws
- Flat blade screwdriver Electric drill and bits Plumb line
- Safety glasses
- Level
- Tape measure
- Misc. screws and nails 10mm socket or wrench
Inspection of Appliance and Components
- Remove appliance and components from packaging and inspect for damage.
- Report to your dealer any parts damaged in shipment.
- Read all the instructions before starting the installation. Follow these instructions carefully during the installation to ensure maximum safety and benefit.
WARNING
Fire Risk.
Inspect appliance and components for damage. Damaged parts may impair safe
operation.
- Do NOT install damaged components.
- Do NOT install incomplete components. • Do NOT install substitute components. Report damaged parts to dealer.
Install Checklist
Atention Installer
Follow this Standard Work Checklist
This standard work checklist is to be used by the installer in conjuction
with, not istead of, the instructions contained in this installation manual.
- Customer:
- Date Installe: Lot / Address:
- Location of Appliance: Installer:
- Dealer / Distributor Phone #: Serial #:
- Model:
WARNING! Risk of Fire or Exposion! Failure to install appliance according to these instruction can lead to a fire or explosion
Appliance Install
- Verified clearances to combustibles.
- Appliance is leveled and connector is secured to appliance.
- Hearth extension size/height decided.
- Outside air kit installed.
- Floor protection requirements have been met.
- If appliance is connected to a masonry chimney, it should be cleaned and inspected by a professional. If installed to a factory built metal chimney, the chimney must be installed according to the manufacturer’s instructions and clearances.
Chimney
- Chimney configuration complies with diagrams.
- Chimney installed, locked and secured in place with proper clearance.
- Chimney meets recommended height requirements (14-16 feet). Roof
- flashing installed and sealed.
- Terminations installed and sealed.
Clearances
- Combustible materials not installed in non-combustible areas.
- Verified all clearances meet installation manual requirements.
- Mantels and wall projections comply with installation manual requirements.
- Protective hearth strips and hearth extension installed per manual requirements.
Appliance Setup
- All packaging and protective materials removed.
- Firebrick, baffle and ceramic blanket installed correctly.
- All labels have been removed from the door.
- All packaging materials are removed from inside/under the appliance.
- Manual bag and all of its contents are removed from inside/under the appliance and given to the party responsible for use and operation.
VisionLINE fireplaces recommends the following:
- Photographing the installation and copying this checklist for your file.
- That this checklist remain visible at all times on the appliance until the installtion is complete.
- Comments: Further description of the issues, who is responsible (Installer/Builder/Other Trades, etc.) and corrective action needed:
- Comments communicated to party responsible ____ by ___ on _ (Builder / Gen. Contractor) (Installer) (Date)
GENERAL INSTRUCTIONS FOR FLUE SYSTEM
- Flue pipe installed crimp/narrow end down
- Outer casings installed crimped/narrow end up. (Critical when exposed above the roof)
- Inner casings – direction not critical
- Flue pipes – seal all joints including firebox spigot. – fix with a minimum of 3 stainless steel rivets
- Flue pipe spacers – affix to flue pipe
- Flue system termination point – Refer to AS/NZS 2918:2018 4.9.1.
- Flue pipe shall extend not less than 4.6m above top of the floor protector as per AS/NZS 2918:2018 4.9.1 (a)
- Fac;;ade or chase systems – same rule applies as above.
UNIT IS APPROVED WITH EITHER MESH OR SOLID 8″ OUTER SKIN – CLEARANCES
VARY
Note: These instructions apply to 150mm diameter flue pipe systems as
tested to AS/NZS 2918:2018
- Either locate the appliance in position or by measuring at the ceiling mark the flue pipe centre position. Check that the outer casing is unobstructed through the attic space or roof area.
- Spike the centre with a nail. Transfer this position to the next surface above. Plumb bob/laser.
- Cut out the ceiling penetration hole – square or rectangle – short axis equals outer casing diameter plus 50mm, long axis as required. See Table 5 . Perform the same at the roof penetration.
- Frame out the hole with minimum 75 x 50 timber or as required for roofing material. Minimum requirement at roof penetration see NZ Building Code E2 Acceptable Solution (from 01/07/05).
- Install the outer casing so that :-
- lower end is flush with the underside of the ceiling material and
- with the addition of metal “L” brackets, affix to the outer casing at 90 degrees secure the outer casing centrally to the ceiling and roof nogs. Alternatively substitute the “L” brackets for 25mm thick non heat sensitive packers. Secure the outer casing through the packers with horizontal fixings to the nogs. Refer to the General Instruction for termination height. The option of outer casing slips to be taken into account.
- Flash the outer casing to the roof material with the appropriate approved flashing.
- If using an outer/inner casing combination, now install the inner casing ensuring it extends a minimum 200mm above the high side of the roof penetration. If not using a combination see ’11’ below.
- Refer to Firebox Installation, points 1 & 2.
- Prepare the ceiling plate and place upside down over the flue spigot.
- Install the flue pipes by preferred method – either up or down the outer casing. Affix each length per the notes in General Instructions (above). Extend the flue pipe above the outer casing to suit the casing cover/cowl assembly.
- If the inner casing has not been installed, install now. Refer to 7 above for minimum height.
- Install the cowl assembly, i.e. Top spacer, casing cover and cowl.
- Position and secure the ceiling plate with the screws and spacers.
- Wipe the flue pipe to remove finger marks.
- Refer to Firebox Installation, point 3.
- If flue offset is required, refer to AS/NZS 2918:2018 4.1
DEFAULT 6″ FLUE KIT with mesh and solid decorative flue
INSTALLATION INSTRUCTIONS
For connecting into a standard installation:
The following drawing is meant as a guide only. Your wood heater must be
installed by a qualified person whose work conforms with local council
regulations, Australian/New Zealand standards & manufacturer’s
recommendations.
VisionLINE fireplaces recommends using either VisionLINE Default flue kits or VisionLINE AIR insulated flue kits.
MINIMUM HEIGHT OF FLUE SYSTEM EXIT
Installing The Flue
The flue seats over the flue starter spigot, the flue crimp will slide down and
rest in the lower channel. Friction fitment secures the flue on the spigot, no
sealant required
AS/NZS 2918:2018 General Notes
WARNING: THE APPLIANCE AND FLUE SYSTEM SHALL BE INSTALLED IN ACCORDANCE
WITH AS/NZS 2918 AND THE APPROPRIATE REQUIREMENTS OF THE RELEVANT BUILDING
CODE OR CODES.
WARNING: APPLIANCES INSTALLED IN ACCORDANCE WITH THIS STANDARD SHALL
COMPLY WITH THE REQUIREMENTS OF AS/NZS 4013 WHERE REQUIRED BY THE REGULATORY
AUTHORITY, I.E. THE APPLIANCE SHALL BE IDENTIFIABLE BY A COMPLIANCE PLATE WITH
THE MARKING ‘TESTED TO AS/NZS 4013’.
ANY MODIFICATION OF THE APPLIANCE THAT HAS NOT BEEN APPROVED IN WRITING BY THE
TESTING AUTHORITY IS CONSIDERED TO BE IN BREACH OF THE APPROVAL GRANTED FOR
COMPLIANCE WITH AS/NZS 4013.
CAUTION: MIXING OF APPLIANCE OR FLUE SYSTEM COMPONENTS FROM DIFFERENT
SOURCES OR MODIFYING THE DIMENSIONAL SPECIFICATION OF COMPONENTS MAY RESULT IN
HAZARDOUS CONDITIONS. WHERE SUCH ACTION IS CONSIDERED, THE MANUFACTURER SHOULD
BE CONSULTED IN THE FIRST INSTANCE.
CAUTION: THIS APPLIANCE SHOULD NOT BE OPERATED WITH CRACKED AND BROKEN
COMPONENTS, e.g. GLASS PANELS OR CERAMIC TILES, MAY RENDER THE INSTALLATION
UNSAFE.
WARNING: ANY MODIFICATION OF THE APPLIANCE THAT HAS NOT BEEN APPROVED IN
WRITING BY THE TESTING AUTHORITY IS CONSIDERED AS BREACHING AS/NZS 4013.
WARNING: DO NOT USE FLAMMABLE LIQUIDS OR AEROSOLS TO START OR REKINDLE
THE FIRE.
WARNING: DO NOT USE FLAMMABLE LIQUIDS OR AEROSOLS IN THE VICINITY OF THIS
APPLIANCE WHEN ITS OPERATING.
WARNING: DO NOT STORE FUEL WITHIN HEATER INSTALLATION CLEARANCES.
WARNING: OPEN AIR CONTROLS AND DAMPER WHEN FITTED BEFORE OPENING FIRING
DOOR.
WARNING: FOR OPTIMUM PERFORMANCE FUEL MUST BE LOADED SO THE LOGS LAY
“FRONT TO REAR” IN PREFERENCE TO LAYING ACROSS THE WIDTH OF THE FIREBOX.
SPACES SHOULD BE LEFT BETWEEN THE LOGS TO ENABLE OXYGEN TO GET TO AS MUCH OF
THE SURFACE OF THE FUEL AS POSSIBLE.
CAUTION: THIS APPLIANCE SHOULD BE MAINTAINED AND OPERATED AT ALL TIMES IN
ACCORDANCE WITH THESE INSTRUCTIONS.
CAUTION: THE USE OF SOME TYPES OF PRESERVATIVE-TREATED WOOD AS A FUEL CAN
BE HAZARDOUS.
Before lighting the first fire
If the stove was stored in a cold environment (car, store, etc.) before the
first lighting, keep it at room temperature for about 3 hours to equalise
moisture condensation and surface temperature of the parts. Otherwise, there
is a risk of damage to the glass or lining of the stove.
During the first lighting, the paint coating will go through a curing process.
The stove paint will emit an odor for at least 4 hours as it adheres to the
steel. Ensure to ventilate the room during this time.
Note: during this process, the gasket on the door can stick to the firebox
face and make it difficult to open the door. To prevent this, open the door
every 5-10 minutes during the curing fire during the first 2 hours.
Lighting your fire
-
Ensure the Air Slide is in the open or high position. (Towards the right – FIG 1)
-
In firebox lay your fire lighters 10 centimetres apart. Do not use newspaper as a fire lighter.
-
Add a mixture of soft wood and hardwood kindling in a criss cross pattern above the firelighters (FIG 2). Softwood kindling allows for fire to light quicker and burn hotter, mixing in some kindling size hardwood helps the coals retain more heat for longer.
-
Light fire with match or gas lighter, when fire is ablaze close the door, but do not latch the door. Leave for 5 minutes maximum and do not leave unattended.
-
Load pieces of hardwood that are no wider than a drink can in a criss cross pattern.
-
Latch the door and let burn for approx 10-20 minutes.
-
After 30 minutes re-open the door and add the large pieces of hardwood. These pieces should be no bigger than a loaf of bread. Close and latch door after loading.
-
After 45 minutes you can adjust the air slide to slow fire down and find your comfort level.
If too little wood and firelighters are used during lighting or the pieces are
too large, the optimal operating temperature will not be reached. This can
lead to poor combustion, high soot formation and the extinguishing of the fire
after closing the door.
Slow combustion fireplaces with tall door openings are prone to smoke spillage
occassionally when the door is opened during lighting and reloading. This
occurs due to a pressure imbalance when opening the door as cool air rushes
in.
Avoid opening the door when there is visible smoke/flame to reduce this
symptom. It is good practice to only reload when fuel is at coaling phase.
The Visionline Pera is designed and tested as an intermittent heating
appliance and is not intended to be used continuously. Over-use can result in
shortened life of components.
Tips on choosing firewood
How long a tree has been felled or dead for does not indicate how dry the wood
is. The best way to dry wood is to split it and expose the inner core allowing
the sun to dry the wood naturally.
Good wood merchants will split the wood for you, but may not season it for
you.
The amount of you pay for your wood or the appearance of the wood does not
justify how dry the wood is. The only way to know how dry your wood is, is to
use a moisture meter measuring from the inner core after splitting the piece
of wood you are testing.
Only burn wood under 20% moisture.
Anything over 20% and your wood heater will not work efficiently. The energy
from the fire will be used to reduce moisture in your wood and not produce
heat for your house.
Store your wood for at least 12 months after your have purchased it. Optimum
moisture content is between
15-18%. Wood under 15% will have a shorter overall burn time than wood around
20%.
Never burn treated wood or painted wood.
Combustion air
The 3 elements required for fire are Fuel, Heat and Oxygen. When a fire is
started within a slow combustion heater, the heat rises in the flue system
creating a vacuum within the firebox. This vacuum creates positive pressure or
‘draw’ which pulls oxygen in to replace itself and create the balance of air
to keep the fire running.
In tightly sealed homes, fresh air supply to the unit may be insufficient due
to an air pressure imbalance which can affect the operation of the stove.
This stove has the possibility of connecting directly to outside the envelope
of the home to supply combustion air. This is via the 100mm diameter central
air duct neck located on the base of the unit. See below Fig 3 for how to
connect this.
To ensure a central air supply, the duct must not be longer than 3 m and have
too many bends. The air intake duct diameter is 100 mm.
The central air duct must be led outdoors or into a well-ventilated room
inside the building (cellar, utility room, etc.).
VisionLINE fireplaces recommends the VisionLINE AIR insulated flue system to
create a balanced flue ensuring adequate air supply balance. It is critical to
have an air tight sealon the connection to the heater to outside air to ensure
no loss of vacuum to the air intake which could result in starvation of air
and poor performance.
Baffle and Brick Removal
Fig 4
Start by lifting the front of the bottom grate upwards
Fig 5
Then turn it 90 degrees
Fig 6
Then pull the grate out of the stove
Fig 7
Place in a suitable spot
Fig 8
Push the rear brick up together with the top brick to prevent it from falling
down.
Fig 9
Holding the top brick up, pull the lower part of the back brick forwards and
let it rest at the bottom of the combustion chamber.
Fig 10
Then turn the top brick down
Fig 11
Push the top brick towards the back edge of the back brick
Fig 12
When the top brick is released from its resting pins, you can turn it 90°
Fig 13
Then pull out the top brick, and place it a suitable place.
Fig 14
To release the heat shield, lift it straight up and push towards rear edge.
Pull it out and place it in a suitable place.
Troubleshooting
With proper installation, operation, and maintenance your wood appliance will provide years of trouble-free service. If you do experience a problem, this troubleshooting guide will assist you or a qualified service person in the diagnosis of a problem and the corrective action to be taken.
Start Fire Problems | Possible Cause | Solution |
---|
Can not get fire started Excessive smoke or spillage Burns too slowly Not enough heat output
| Not enough kindling/firestaters or no kindling/paper| Use small dry kindling, more firelighters. Arrange kindling & wood for air movement. Try top down method.
Not enough air for fire to ignite
| Check for restricted termination cap.
Check for blockage of outside air kit; if installed.
Check for flue blockage.
Pre-warm flue before starting fire.
Check for adequate vent height.
Open window below the appliance towards the wind.
Wood condition is too wet, too large| Use dry, seasoned wood
Bed of coals not established before adding wood| Start with paper & kindling
to establish bed of coals.
Flue blockage such as birds’ nests or leaves in termination cap| Have chimney
inspected for creosote and cleaned by a certified chimney sweep.
Down draft or negative pressure Competition with exhaust devices| Do not use
exhaust fans during start-up.
Open window below the appliance towards the wind.
Fire burns too fast| Extremely dry or soft wood| Mix in hardwood.
Mix in less seasoned wood after fire is established.
Over drafting| Check for correct vent height; too much vertical height creates
over drafting.
Check location of vent termination.
VisionLINE Wood Stove Warranty
VisionLINE extends the following manufacturer’s warranty for wood hearth
appliances that are purchased from a VisionLINE authorized dealer.
VisionLINE warrants to the original owner of the VisionLINE appliance at the
site of installation, and to any transferee taking ownership of the appliance
at the site of installation within two years following the date of original
purchase, that the VisionLINE appliance will be free from defects in materials
and workmanship at the time of manufacture.
After installation, if covered components manufactured by VisionLINE are found
to be defective in materials or workmanship during the applicable warranty
period, VisionLINE will, at its option, repair or replace the covered
components. VisionLINE, at its own discretion, may fully discharge all of its
obligations under this manufacturer’s warranty by replacing the product itself
or refunding the verified purchase price of the product itself. The maximum
amount recoverable under this warranty is limited to the purchase price of the
product. This warranty is subject to conditions, exclusions and limitations as
described below.
Warranty coverage begins on the date of original purchase. In the case of new
home construction, coverage under this manufacturer’s warranty begins on the
date of first occupancy of the dwelling or six months after the sale of the
product by an independent, authorized VisionLINE dealer/ distributor,
whichever occurs earlier. The warranty period for this manufacturer’s warranty
shall commence no later than 12 months following the date of product shipment
from VisionLINE AU, regardless of the installation or occupancy date.
The term “Limited Lifetime” in the table below is defined as: 10 years from the
beginning date of warranty coverage for wood appliances. These time periods
reflect the minimum expected useful lives of the designated components under
normal operating conditions.
10 year structural warranty on the firebox construction including weldment.
OTHER RIGHTS
The VisionLINE manufacturer’s warranty is in addition to other rights and
remedies that you may have under Australian law.
Our goods come with guarantees that cannot be excluded under the Australian
Consumer Law. You are entitled to a replacement or refund for a major failure
and for compensation for any other reasonably foreseeable loss or damage. You
are also entitled to have the goods repaired or replaced if the goods fail to
be of acceptable quality and the failure does not amount to a major failure.
WARRANTY CONDITIONS AND EXCLUSIONS:
- The VisionLINE manufacturer’s warranty only covers VisoinLINE appliances that are purchased through a VisionLINE authorized dealer or distributor. A list of VisionLINE authorized dealers is available on the VisionLINE branded websites.
- This warranty is only valid while the VisionLINE appliance remains at the site of original installation.
WARRANTY EXCLUSIONS:
This VisionLINE manufacturer’s warranty does not cover the following:
-
Changes in surface finishes as a result of normal use. As a heating appliance, some changes in color of interior and exterior surface finishes may occur. This is not a flaw and is not covered under warranty.
-
Damage to printed, plated, or enamelled surfaces caused by fingerprints, accidents, misuse, scratches, melted items, or other external sources and residues left on the plated surfaces from the use of abrasive cleaners or polishes.
-
Repair or replacement of parts that are subject to normal wear and tear or have contact with fire during the warranty period. These parts include: paint, gaskets, firebricks, grates, glass.
-
Minor expansion, contraction, or movement of certain parts causing noise. These conditions are normal and complaints related to this noise are not covered by this warranty.
-
Damages resulting from: (1) failure to install, operate, or maintain the appliace in accordance with the installation instructions, operating instructions, and listing agent identification label furnished with the appliance;
(2) failure to install the appliance in accordance with local building codes; (3) shipping or improper handling; (4) improper operation, abuse, misuse, continued operation with damaged, corroded or failed components, accident, or improperly/incorrectly performed repairs; (5) environmental conditions, inadequate ventilation, negative pressure, or drafting caused by tightly sealed constructions, insufficient make-up air supply, or handling devices such as exhaust fans or forced air furnaces or other such causes; (6) use of fuels other than those specified in the operating instructions; (7) installation or use of components not supplied with the appliance or any other components not expressly authorized and approved by VisionLINE (8) modification of the appliance not expressly authorized and approved by VisionLINE in writing; and/or (9) interruptions or fluctuations of electrical power supply to the appliance. -
Non VisionLINE venting components, hearth components or other accessories used in conjunction with the appliance.
-
Any part of a pre-existing fireplace system in which an insert appliance is installed.
-
Removal, installation, reinstallation, set up or any other costs associated with a claim including travel and shipping charges for parts.
-
VisionLINE’s obligation under this warranty does not extend to the appliance’s capability to heat the desired space. Information is provided to assist the consumer and the dealer in selecting the proper appliance for the application. Consideration must be given to appliance location and configuration, environmental conditions, insulation and air tightness of the structure.
This warranty is void if:
- The appliance has been over-fired or operated in atmospheres contaminated by chlorine, fluorine, or other damaging chemicals. Over-firing can be identified by, but not limited to, warped plates or tubes, rust coloured cast iron, bubbling, cracking and discoloration of steel finishes.
- The appliance is subjected to prolonged periods of dampness or condensation.
- There is any damage to the appliance or other components due to water or weather damage which is the result of, but not limited to, improper chimney or venting installation.
HOW TO CLAIM
- To make a claim against this warranty, contact your local distributor during regular business hours. See addresses below for a dealer nearest you. (Vic) Pty Ltd ACN 005 872 159 (Jetmaster VIC).
- Additional service fees may apply if you are seeking warranty service from a dealer other than the dealer from whom you originally purchased the product.
- Check with Jetmaster VIC in advance for any costs to you when arranging a warranty call. Travel and shipping charges for parts are not covered by this manufacturers’ warranty.
- VisionLINE and Jetmaster VIC will assess your claim. VisionLINE or Jetmaster VIC may need to inspect the product as part of the assessment of your claim. If the product requires inspection, VisionLINE or Jetmaster will discuss with you the best way for this to occur.
- To make a claim under this manufacturer’s warranty, you must be able to prove when you purchased the product. The easiest way to do this is through your original proof of purchase, for example your invoice or receipt. However, if you do not have your original proof
of purchase VisionLINE or Jetmaster may accept other evidence of the date of purchase.
PO Box 5051 Burnley, 3121 Phone: (03) 9429 5573
Email: info@visionlinefire.com.au Web:
visionlinefire.com.au
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>