Met One Instruments 360-9800 360 Precipitation Gauge Instruction Manual
- June 10, 2024
- Met One Instruments
Table of Contents
Instruments 360-9800 360 Precipitation Gauge
Instruction Manual
General Information
NOTE: Remove screens during winter operation.
Specifications
The Model 360 Precipitation Gauge is an accurate, sensitive and low maintenance sensor designed to measure rainfall on a continuous basis. Water does not collect in the sensor, but is drained each time an internal bucket fills with 0.1mm, 0.2mm or .25mm of rainfall depending on set standard calibration, and a switch closure pulse is also sent to the translator module or data logger for counting. The sensor is calibrated at shipment and requires no adjustments after the mounting.
TABLE 1-1: MODEL 360 PRECIPITATION GAUGE SPECIFICATIONS
Rain Gauges: | 360 Rain | 362 Rain | 364 Rain |
---|---|---|---|
Plastic Tip Bucket Model #: | 360 | 362 | 364 |
Metal Tip Bucket Model #: | 360-1 | 362-1 | 364-1 |
Funnel Area: | 200cm2 | 200cm2 | 200cm2 |
Standard Calibration: | .25mm/tip or .01in/tip | .20mm/tip | .10mm/tip |
Accuracy: | 0 to 30mm/hr ± 1.0% 30 to 120mm/hr ± 5.0% | 0 to 30mm/hr ± 1.0% 30 | |
to 120mm/hr ± 5.0% | 0 to 30mm/hr ± 1.0% 30 to 120mm/hr ± 5.0% | ||
Switch: | Reed Switch, rated at 10mA, 28VDC | Reed Switch, rated at 10mA, 28VDC |
Reed Switch, rated at 10mA, 28VDC
Operating Temperature:| 0°C to +60°C| 0°C to +60°C| 0°C to +60°C
Height/ Weight:| 30.5cm / .92kg| 30.5cm / .92kg| 30.5cm / .92kg
Rain & Snow Gauges:| 365 Rain & Snow| 367 Rain & Snow| 369
Rain & Snow
---|---|---|---
Plastic Tip Bucket Model #:| 365| 367| 369
Metal Tip Bucket Model #:| 365-1| 367-1| 369-1
Funnel Area:| 200cm2| 200cm2| 200cm2
Standard Calibration:| .25mm/tip or .01in/tip| .20mm/tip| .10mm/tip
Accuracy:| 0 to 30mm/hr ± 1.0%
30 to 120mm/hr ± 5.0%| 0 to 30mm/hr ± 1.0%
30 to 120mm/hr ± 5.0%| 0 to 30mm/hr ± 1.0%
30 to 120mm/hr ± 5.0%
Switch:| Reed Switch, rated at 10mA,
28VDC| Reed Switch, rated at 10mA,
28VDC| Reed Switch, rated at 10mA,
28VDC
Operating Temperature:| -25°C to +60°C| -25°C to +60°C| -25°C to +60°C
Thermostat Set Point for Funnel & Base Heater:| 4.4°C| 4.4°C| 4.4°C
Heaters:| Funnel: 24VAC/DC, 75watt
Base: 24VAC/DC, 50watt| Funnel: 24VAC/DC, 75watt
Base: 24VAC/DC, 50watt| Funnel: 24VAC/DC, 75watt
Base: 24VAC/DC, 50watt
Height/ Weight:| 30.5cm / 1.1kg| 30.5cm / 1.1kg| 30.5cm / 1.1kg
1.2. Sensor Signal Cable
The Sensor Cable Is a vinyl-jacketed 2 conductor shielded cable connecting to
the sensor via an internal terminal strip. Cable length is designated in XX
feet on each cable part number label.
1.3. Heater Power Cable
The Heater Power Cable Is a vinyl-jacketed 2 conductor shielded cable
connecting to the sensor via an internal terminal strip. Cable length is
designated in XX feet on each cable part number label.
Installation
2.1. Location
Choose a site where the height of any nearby trees or other objects above the
sensor is no more than twice their distance from the sensor. A uniform
surrounding of objects (such as an orchard) is beneficial as a windbreak.
Non-uniform surroundings (such as a nearby building) create turbulence, which
affects accuracy.
2.2. Setup
-
NOTE: The Rain gauge is designed for installation on a customer-built pedestal mount.
-
Prepare the pedestal for mounting and leveling the rain gauge.
-
Route the #3519 Signal Cable and if applicable the #3517 Heater Power Cable up through the pedestal center tube. (Refer to Figure 2.1)
-
On the rain gauge, remove three screws/washers near bottom of housing that secure housing to base. Slowly and carefully lift the housing straight up from base.
NOTE: If rain gauge is heated carefully disconnect the funnel heater from the heater wiring terminal block. Insure that all wiring is connected properly before closing the housing. -
Connect the #3519 Signal Cable & #3517 Heater Power Cable (if applicable). (Refer to Figure 2.4).
-
While pushing cable down into the pedestal center tube check cable routing under the rain gauge for kinks or binding, correct as required.
-
Connect the #3519 Signal Cable to the logger/counting device. Connect the #3517 Heater Power Cable to the power source.
NOTE: Before turning on power to heated rain gauge insure proper voltage and wattage are being applied. Refer to the heater specifications in section 1.1. -
Level the rain gauge by observing the location of the bubble in the bubble level (adjust as required). Note: This rain gauge has been calibrated at the factory with the bubble centered; any deviation from this could affect accuracy. (Refer to Figure 2.5). CAUTION
Gently remove the foam shipping restraints (Refer to Figure 2.6) from the tipping bucket.
Manually tip the bucket for specified calibration rainfall recorded per each tip. If no output, check connections. -
Insure that all wiring is connected properly before closing the housing.
-
Install the housing onto the rain gauge base.
-
Align holes in housing and captive nuts in base. Re-install three screws and washers to secure housing onto base.
-
Remove both screens from plastic bags and install in funnel as shown below. (Refer to Figure 2.7). Care must be taken at the sharp-edged orifice to avoid personal injury and damage to the thin edge.
-
Rain gauge is now ready for operation.
CAUTION
To avoid possible damage and loss of calibration during any further shipments,
re-insert foam shipping restraints to immobilize the tipping bucket.
Calibration
The sensor is factory calibrated, recalibration is not required unless damage
has occurred or the adjustment screws have loosened. To check or recalibrate,
perform the following steps:
a. Remove housing
b. Check the bubble level to see if the sensor is level.
c. Wet the tipping bucket assembly using a burette or graduated cylinder;
slowly pour the measured quantity of water into the tipping bucket, which
should then tip. Repeat for the alternate bucket. If both buckets tip when
filled with the measured quantity of water, the sensor is properly calibrated.
If they do not, recalibrate as follows:
TABLE 3-1:CALIBRATION QUANTITIES
Tip Calibration | Tip Calibration |
---|---|
0.1mm | 0.1mm |
0.2mm | 0.2mm |
0.25mm or .01in | 0.25mm or .01in |
- Release the lock nuts on the cup adjustment screws.
- Move the adjustment screws down to the position that would place the bucket far out of calibration.
- Allow the measured quantity of water to enter the bucket.
- Turn the cup adjustment screw up until the bucket assembly tips. Tighten the lock nut.
- Repeat steps 3 and 4 for the opposite bucket.
- Measure the quantity of water necessary to tip the bucket several times to ensure proper calibration.
d. After installation and calibration (if necessary), replace the housing on the gauge.
Maintenance*
At six-month intervals, perform the following steps:
a. Clean funnel and buckets.
b. Do NOT lubricate the pivot shaft, as any lubricant may attract dust and
dirt and cause wear or drag.
c. Verify that the bucket moves freely and that translator card or data logger
registers proper calibration for each bucket tip.
*Based on average to adverse environments.
TABLE 4-1: 360 SERIES PART REPLACEMENT
ITEM | DESCRIPTION | PART # | IMAGE |
---|---|---|---|
1 | Screen, 2-9/16 DIA., SST | 2504 | |
2 | Screen, Primary (6″ RG) | 3465 | |
3 | Screen, Base | 3522 (2 PLCS) | |
4 | Circuit Board Assy, Reed | ||
Switch | 3487 | ||
5 | Assy, Tip Bucket (Plastic) | 3554 ,4 | |
6 | Assy, Tip Bucket (Metal) | 3478 , | |
7 | Pivot Shaft | 3477 | |
8 | Heated Funnel Assy | 10159 | |
7 | Pivot Shaft | 3477 | |
8 | Heated Funnel ASSY | 10159 |
Met One Instruments, Inc
Corporate Sales & Service: 1600 NW
Washington Blvd. Grants Pass, OR 97526
Tel541-471-7111 Fax
541-471-7116
www.metone.com –
service@metone.com
Copyright Notice
360 PRECIPITATION GAUGE OPERATION MANUAL
© Copyright 2003 Met One Instruments, Inc. All Rights Reserved Worldwide. No
part of this publication may be reproduced, transmitted, transcribed, stored
in a retrieval system, or translated into any other language in any form by
any means without the express written permission of Met One Instruments, Inc.
Technical Support
Should you require support, please consult your printed documentation or our
website www.metone.com to resolve your problem. If
you are still experiencing difficulty, you may contact a Technical Service
representative during normal business hours; Monday – Friday 7:00 a.m. to 4:00
p.m. Pacific Time.
Voice:541-471-7111
Fax:541-471-7116
E-Mail: service@metone.com
Mail: Technical Services Department
Met One Instruments, Inc.
1600 NW Washington Blvd Grants Pass, OR 97526
360-9800 Manual Rev C
Documents / Resources
| Met
One Instruments 360-9800 360 Precipitation
Gauge
[pdf] Instruction Manual
360-9800 360 Precipitation Gauge, 360-9800, 360 Precipitation Gauge,
Precipitation Gauge, Gauge
---|---
References
- Met One - Precision Air Quality Monitoring Instruments
- Met One - Precision Air Quality Monitoring Instruments
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>