niko 353-651421 Presence Detector User Manual

June 4, 2024
niko

**niko 353-651421 Presence Detector User Manual

**

Wiring

230 V – OFF

Wiring

This product must be secured with a miniature circuit breaker (MCB) of max. 16 A in the electrical cabinet. The MCB rating is limited by national installation rules.

Dimensions

Dimensions

Installation

230 V – OFF

Installation

Installation
Installation
Installation
App settings

230 V – ON

Factory settings

  • Switch ON/OFF

  • 500 lux

  • 15 min

App settings

LED behaviour

230 V – ON

Green LED continuous on| | Connection OK|
---|---|---|---
Green LED breathing| | Connection OK, overrule ON|
Green LED flashing| | Warming up| Wait
Red LED continuous on| | Error| More info _– >

_

detector tool

Red LED breathing| | Warning
Blue LED flashing| | Walk test active

Specifications

  • Article number: 353-651421

  • Configuration: DALI-2 master

  • Input voltage: 230 Vac ± 10 %, 50 Hz

  • Maximum power consumption: 0.6 W

  • Maximum power consumption wireless link active: 0.65 W

  • Short circuit behaviour shutdown trigger: voltage below 12 V, exceeding 1.3 s

  • Short circuit behaviour restart period: every 14 s until success

  • Detector output: DALI Broadcast/DALI Adressable

  • Circuit breaker: maximum MCB rating 16 A*

  • Relay contact: NO (max. µ10 A), potential-free

  • Maximum load incandescent and halogen lamps (cosφ = 1): 2300 W

  • Maximum load fluorescent lamps (cosφ ≥ 0.5): 1200 VA

  • Maximum load economy lamps (CFLi): 350 W

  • Maximum load LED lamps 230 V: 350 W

  • Maximum load LED driver: 500 VA

  • Maximum load electronic transformer: 500 VA

  • Maximum capacitive load: 140 µF

  • Maximum switching current: 165 A/20 ms – 800 A/200 µs

  • Maximum voltage on the DALI bus: 15 Vdc

  • Maximum guaranteed current on the DALI bus: 200 mA

  • Maximum supply current: 250 mA

  • Maximum startup time DALI: < 1200 ms

  • Maximum PIR detection startup time: 70 s

  • Maximum number of dimmable zones: 4

  • Maximum number of control gear on the DALI bus: 64

  • Light intensity range: 20 – 2000 lux, ∞

  • Switch-off delay: pulse, 20 s – 120 min, ∞

  • Detection angle: 360°

  • Detection range (PIR): ø 12 m from a height of 3 m

  • Ambient temperature: -25 – +40 °C

  • Mounting method: flush mounting with SnapFit mounting bracket

  • Mounting height: 2 – 3.5 m

  • Drill diameter: 76 mm

  • Minimum flush mounting depth: 100 mm

  • Colour: white (RAL 9010)

  • Dimensions visible (HxWxD): 100 x 100 x 9.5 mm

  • Dimensions (HxWxD): 120 x 120 x 109.5 mm

  • Wire capacity: 1.5/2.5 mm²

  • Protection degree: IP20

  • Impact resistance: IK02

  • Modification of settings: app (iOS/Android) and 2-way Bluetooth® communication

  • Maximum range Bluetooth® (free field, depending on the device): 50 m

  • Operating frequency: 2.4 GHz

  • Maximum radio frequency power: -2 dBm

  • Halogen-free: yes

  • Marking: CE

  • The MCB rating is limited by national installation rules.

Detection area

Detection area

Troubleshooting

Problem Possible cause Proposed solution
Load does not turn on The wiring is not correct The ambient light is too
strong Check the wiring scheme Check the response value luminosity and raise

the value if necessary
Load does not turn off| The switch-off delay is too long  The detector receives false triggers| Check the switch-off delay and shorten the delay if necessary Check for any objects that may cause false triggering and remove them from the detection range or lower the sensitivity
App cannot connect to the detector| Bluetooth® has been disabled on your mobile device| Enable Bluetooth® on your mobile device

Support & contact

nv Niko sa Industriepark West 40 9100 Sint-Niklaas, Belgium
www.niko.eu

+32 3 778 90 80 support@niko.eu

NL België: +32 3 778 90 80
Nederland: +31 880 15 96 10
support.be@niko.eu
support.nl@niko.eu
FR
Belgique: +32 3 778 90 80
France: +33 820 20 66 25
Suisse: +41 44 878 22 22
support.be@niko.eu
support.fr@niko.eu
support.ch@niko.eu
DE
Deutschland: +49 7623 96697-0
Schweiz: +41 44 878 22 22
Österreich: +43 1 7965514
Belgien: +32 3 778 90 80
support.de@niko.eu
support.ch@niko.eu
support.at@niko.eu
support.be@niko.eu
DK +45 74 42 47 26 support.dk@niko.eu
SE +46 8 410 200 15 support.se@niko.eu
NO +47 66 77 57 50 support.no@niko.eu
IT +41 44 878 22 22 support.ch@niko.eu
PL +48 509 378 373 support.pl@niko.eu
SK +421 2 63 825 155 support.sk@niko.eu

Niko prepares its manuals with the greatest care and strives to make them as complete, correct and up to date as possible. Nevertheless, some deficiencies may subsist. Niko cannot be held responsible for this, other than within the legal limits. Please inform us of any deficiencies in the manuals by contacting Niko customer services at support@niko.eu.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals