IMI TA DN 65-125 TA-Smart Instruction Manual
- June 10, 2024
- IMI TA
Table of Contents
IMI TA DN 65-125 TA-Smart
Intended use
- For measuring and control in heating and cooling systems.
- The water quality requirements described in VDI2035 should be respected
- TA-Smart can be cleansed with a damped cloth and a lenient cleaning agent.
- Insulated wires and cables shall retard flame propagation with a flammability
RATING of UL 2556 VW-1 or equivalent
FEATURE
24 VAC/VDC operating only with safety isolating transformer according EN 61558-2-6.
CAUTION
Service/Repair → IMI Hydronic Engineering
If the TA-Smart is used in any other application than specified by IMI
Hydronic Engineering the protection provided by the equipment may be impaired
.
We reserve the right to introduce technical alterations without prior notice.
Technical specifications
Valid at an altitude of max. 2000 m.
- -20°C – +70°C (-4°F – +158°F) (5-95%RH, non-condensing
- 0°C – +50°C (32°F – +122°F) (5-95%RH, non-condensing
- Input signal
- Output signal
- Control mode
- Flow setting
- Media
- Characteristic
INSTRUCTION
Wiring diagrams
Terminal | Description |
---|---|
L24 | Power supply 24 VAC/VDC. |
M* | Neutral for power supply 24 VAC/VDC and signals. |
XV | Output signal 0(2)-10 VDC, max. 8 mA or min. load resistance 1.25 kΩ. |
Ausgangssignal 0(2)-10 VDC, max. 8 mA bzw. min. Lastwiderstand 1,25 kΩ.
M (0V)*| Neutral for signal.
Y| Input signal 0(2)-10 VDC, 47 kΩ or 0(4)-20 mA, 500 Ω (selectable by jumper
XX).
Ethernet|
RX –| Ethernet connector wire position 6
RX +| Ethernet connector wire position 3
TX –| Ethernet connector wire position 2
TX +| Ethernet connector wire position 1
RS485|
A| RS485 Data +
B| RS485 Data –
M (0V)*| Neutral for signal.
- USB Only for IMI use./Nur für IMI-Gebrauch./Uniquement pour l’utilisation de l’IMI./Solo para uso IMI.
- Serial Debug Only for IMI use./Nur für IMI-Gebrauch./Uniquement pour l’utilisation de l’IMI./Solo para uso IMI
All M terminals are internally connected./Alle M (0V) Klemmen sind intern verbunden!.
To prevent any possible damage to the product caused by incorrect cabling or wiring, we have introduced a version of the TA-Smart PCBA (HW01) with improved electrical wiring. Both PCBA versions are fully functional, but have slightly different wiring configurations. Ensure to choose the correct technical documentation based on the PCBA’s HW version. The PCBA version (HW00 or HW01) can be found on the sticker in the SmartBox and the wiring instruction for each hardware version. HW00 pages 11-13 and HW01 pages 14-16.
HW00 (Standard – Modbus RTU / BACnet MS/TP – Modbus TCP / BACnet IP)
Note:
- A, B and M terminals are NOT isolated from all other terminals.
- GND (M – 0V) is common to power supply, analog signals and RS 485.
- In case of AC power supply, L24 and M should be connected to the same phase for each TA-Smart.
- GND (0V) of analog input/output should be connected to 0 VAC/VDC on the controller side
24 VAC/VDC operating only with safety isolating transformer according EN 61558-2-6.
Modbus RTU / BACnet MS/TP
Note:
- A, B and M terminals are NOT isolated from all other terminals.
- GND (M – 0V) is common to power supply, analog signals and RS 485.
- In case of AC power supply, L24 and M should be connected to the same phase for each TA-Smart.
- GND (0V) of analog input/output should be connected to 0 VAC/VDC on the controller side.
- GND (0V) of RS 485 should be connected to 0 VAC/VDC on the controller side.
24 VAC/VDC operating only with safety isolating transformer according EN 61558-2-6.
Modbus TCP / BACnet IP
Note:
- A, B and M terminals are NOT isolated from all other terminals.
- GND (M – 0V) is common to power supply, analog signals and RS 485.
- In case of AC power supply, L24 and M should be connected to the same phase for each TA-Smart.
- GND (0V) of analog input/output should be connected to 0 VAC/VDC on the controller side.
- Ethernet cable shall be Cat 5e or Cat 6 cable. Wire colour indication is for T568B pinout
24 VAC/VDC operating only with safety isolating transformer according EN 61558-2-6.
HW01 (Standard – Modbus RTU / BACnet MS/TP – Modbus TCP / BACnet IP)
Note:
- A, B and M terminals are isolated from all other terminals.
- GND (M – 0V) is common to power supply and analog signals.
- GND (0V) of analog input/output should be connected to 0 VAC/VDC on the controller si
24 VAC/VDC operating only with safety isolating transformer according EN 61558-2-6.
Modbus RTU / BACnet MS/TP
Note:
- A, B and M terminals are isolated from all other terminals.
- GND (M – 0V) is common to power supply and analog signals.
- GND (0V) of analog input/output should be connected to 0 VAC/VDC on the controller side.
24 VAC/VDC operating only with safety isolating transformer according EN 61558-2-6.
Modbus TCP / BACnet IP
Note:
- A, B and M terminals are isolated from all other terminals.
- GND (M – 0V) is common to power supply and analog signals.
- GND (0V) of analog input/output should be connected to 0 VAC/VDC on the controller side.
- Ethernet cable shall be Cat 5e or Cat 6 cable. Wire colour indication is for T568B pinout.
24 VAC/VDC operating only with safety isolating transformer according EN 61558-2-6.
LED
Operation
Calibration
Identification
HyTune app
For setting of control parameters use HyTune app.
We reserve the right to introduce technical alterations without prior notice.
IMI Hydronic Engineering AB, 524 80 Ljung, Sweden.
www.imi-hydronic.com