RKI INSTRUMENTS 35-3001A-08-XX Sample Draw Detector Instruction Manual

June 11, 2024
RKI INSTRUMENTS

35-3001A-08-XX Sample Draw Detector

Product Information

The 35-3001A-08-XX Sample-Draw Detector is a gas monitor
manufactured by RKI Instruments, Inc. It is sold with a part number
of 71-0630 and a revision of P1. The product is designed to detect
the presence of combustible gases and carbon monoxide in the air.
The detector has both internal and external components that work
together to provide accurate readings. The product comes with a
warranty that covers instruments and parts sold to users by
authorized distributors, dealers, and representatives as appointed
by RKI Instruments, Inc.

Product Usage Instructions

To use the Sample-Draw Detector, follow the below
instructions:

Installation

Mount the Sample-Draw Detector according to the instructions
provided in the manual. Connect the sample lines to the detector
and wire it to a controller.

Start Up

Introduce incoming power to the detector and set the zero
reading.

Maintenance

Calibrate the detector at the recommended frequency. Calibration
instructions are provided in the manual.

35-3001A-08-XX Sample-Draw Detector
Operator’s Manual
Part Number: 71-0630 Revision: P1
Released: 1/31/23
RKI Instruments, Inc. www.rkiinstruments.com

WARNING
Read and understand this instruction manual before operating detector. Improper use of the detector could result in bodily harm or death. Periodic calibration and maintenance of the detector is essential for proper operation and correct readings. Please calibrate and maintain this detector regularly! Frequency of calibration depends upon the type of use you have and the sensor types. Typical calibration frequencies for most applications are between 3 and 6 months, but can be required more often or less often based on your usage.
2 · 35-3001A-08-XX Sample-Draw Detector Operator’s Manual

Product Warranty
RKI Instruments, Inc. warrants gas alarm equipment sold by us to be free from defects in materials, workmanship, and performance for a period of one year from date of shipment from RKI Instruments, Inc. Any parts found defective within that period will be repaired or replaced, at our option, free of charge. This warranty does not apply to those items which by their nature are subject to deterioration or consumption in normal service, and which must be cleaned, repaired, or replaced on a routine basis. Examples of such items are:
· Absorbent cartridges · Fuses · Pump diaphragms and valves · Batteries · Filter elements Warranty is voided by abuse including mechanical damage, alteration, rough handling, or repair procedures not in accordance with the operator’s manual. This warranty indicates the full extent of our liability, and we are not responsible for removal or replacement costs, local repair costs, transportation costs, or contingent expenses incurred without our prior approval.
THIS WARRANTY IS EXPRESSLY IN LIEU OF ANY AND ALL OTHER WARRANTIES AND REPRESENTATIONS, EXPRESSED OR IMPLIED, AND ALL OTHER OBLIGATIONS OR LIABILITIES ON THE PART OF RKI INSTRUMENTS, INC. INCLUDING BUT NOT LIMITED TO, THE WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. IN NO EVENT SHALL RKI INSTRUMENTS, INC. BE LIABLE FOR INDIRECT, INCIDENTAL, OR
CONSEQUENTIAL LOSS OR DAMAGE OF ANY KIND CONNECTED WITH THE USE OF ITS
PRODUCTS OR FAILURE OF ITS PRODUCTS TO FUNCTION OR OPERATE PROPERLY. This warranty covers instruments and parts sold to users by authorized distributors, dealers, and representatives as appointed by RKI Instruments, Inc. We do not assume indemnification for any accident or damage caused by the operation of this gas monitor, and our warranty is limited to the replacement of parts or our complete goods.
35-3001A-08-XX Sample-Draw Detector Operator’s Manual · 3

Table of Contents
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
External Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Internal Components. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Mounting the Sample-Draw Detector. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Connecting the Sample Lines to the Sample-Draw Detector . . . . . . . . . . . . . . . . . . . . . . . . . 16 Wiring the Sample-Draw Detector to a Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Start Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Introducing Incoming Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Setting the Zero Reading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Replacing Components of the Sample-Draw Detector. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Adjusting the Low Flow Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Removing the Particle Filter’s Tubing Stub, if Necessary . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Calibration Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Calibration, IR Combustible Gas Sensor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Preparing for Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Setting the Zero Reading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Setting the Response Reading. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31 Returning to Normal Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Calibration, CO Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Preparing for Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
4 · 35-3001A-08-XX Sample-Draw Detector Operator’s Manual

Setting the Zero Reading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Setting the Response Reading. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 Returning to Normal Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
35-3001A-08-XX Sample-Draw Detector Operator’s Manual · 5

Overview
This operator’s manual describes the 35-3001A-08-XX combustible gas/carbon monoxide sample-draw detector. This manual also describes how to install, start up, maintain, and calibrate the sample-draw detector when using it with a gas monitoring controller. A parts list at the end of this manual lists replacement parts and accessories for the sample-draw detector.

Specifications

Table 1 lists specifications for the combustible gas/carbon monoxide sample- draw detector. See the controller Operator’s Manual for information specific to the controller.
Table 1: Specifications

Target Gases and Detection Range

Combustible Gas: · 35-3001A-08-01: CH4, 0 – 100% LEL · 35-3001A-08-02: General hydrocarbons (propane
calibration standard), 0 – 100% LEL · 35-3001A-08-03: CH4, 0 – 100% volume
Carbon Monoxide: 0 – 300 ppm

Input Power

24 VDC Nominal (18.5 VDC – 30 VDC)

Construction (housing) Fiberglass/polyester (NEMA 4X)

Dimensions

8.5 in. H x 6.5 in. W x 4.25 in. D

Weight

4.5 lbs.

Sampling Method

Sample-draw

Sample Flow

3.0 SCFH typical, with no inlet or exhaust line

Flow to Sensor

1.0 SCFH (nominal)

Low Flow Setpoint

0.6 ± 0.1 SCFH

Maximum Recommended Inlet/ Exhaust Line Length for 1/4″ O.D. x 1/8″ I.D. Tubing

Inlet

Exhaust

50 feet

0 feet

  • RKI Instruments, Inc. does not recommend installing this tubing size on both the inlet and exhaust.

Maximum Recommended Inlet/ Exhaust Line Length for 1/4″ O.D. x 0.170″ I.D. Tubing

Inlet 50 feet 75 feet

Exhaust 50 feet 0 feet

35-3001A-08-XX Sample-Draw Detector Operator’s Manual

Overview · 6

Response Time Accuracy

Table 1: Specifications
90% in 30 seconds
Combustible Gas: ± 5% of reading or ± 2% of full scale (whichever is greater) Carbon Monoxide: ± 5% of reading or ± 5 ppm CO (whichever is greater)

WARNING: When using the 35-3001A-08-XX, you must follow the instructions and warnings in this manual to assure proper and safe operation of the 35-3001A-08-XX and to minimize the risk of personal injury. Be sure to maintain and periodically calibrate the 35-3001A-08-XX as described in this manual.

35-3001A-08-XX Sample-Draw Detector

Specifications · 7

Description

This section describes the components of the combustible gas/carbon monoxide sample-draw detector.

Charcoal Filter
Sensor Flow Control Valve
Fail LED Pilot LED

Flowmeter Circuit Board Connector

Pump Reset Switch
Flowmeter
Pressure Switch Adjustment Screw
(behind PCB) Hydrophobic
Filter

Mounting Foot, 4X IR Amplifier

R

W

G

B

LE L

S P WR / S IG

W

O X

Y

G

B_

E N

+S AMP

+ S AMP 2

RWGB

OXY LEL/ IR

+S

+ S

WG RWGB

AMP 1 AMP 2 OXY

LEL/ IR

Oxygen Sensor Terminal Strip
Pump Connector Pump
CO Sensor (inside block) CO Amplifier
CO Flow Block
IR Sensor (inside block) IRFlow Block
IR Sensor PCB
De tect or/Amp Terminal Strip (Factory Wired)

This End To Inlet Fitting

Interconnect Terminal Strip

Particle Filter

Inlet Fitting
Exhaust Fitting

INLET EXHAUST

3/4″ Conduit Hub

Figure 1: Combustible Gas/Carbon Monoxide Sample-Draw Detector Component Location

8 · Description

35-3001A-08-XX Sample-Draw Detector

External Components
This section describes the sample-draw detector’s external components.
Housing
The sample-draw detector’s fiberglass housing is weather- and corrosion- resistant. It is suitable for installation where general purpose equipment is in use. The housing door is hinged on the left side and is secured by two latches on the right side. The flowmeter and status LEDs are visible through a window in the housing door. Four mounting feet are attached to the back of the housing (one at each corner). Use the mounting feet to install the housing to a vertical surface.
Sample Fittings
The sample fittings are located on the left side of the bottom of the housing. The inlet fitting is near the front of the housing and the exhaust fitting is near the back of the housing. The sample fittings accept 1/4 in. rigid tubing. See the Installation section on page 15 to connect tubing to the sample fittings.
Particle Filter
A particle filter with a tubing stub on one end is shipped with the instrument but it is not factory installed. If the particle filter is installed directly to the inlet fitting, the tubing stub must be used. If the particle filter is installed somewhere else, like at the end of the inlet line, the tubing stub can be used or removed.
Conduit Hub
One 3/4″ conduit hub is located on the right side of the bottom of the housing. It is used for routing wiring into the housing by using conduit or an appropriate cable bushing.

35-3001A-08-XX Sample-Draw Detector

External Components · 9

Internal Components
This section describes the sample-draw detector’s internal components (see Figure 1). Figure 2 illustrates how the gas sample moves through the flow system.

Exhaust

Pressure Switch

Flowmeter

Flowmeter PCB
Sensor Flow Control Valve

Restrictor

Inlet

Carbon Monoxide
Sensor
Charcoal Filter

Particle Filter

Pump

IR Sensor

Hydrophobic Filter
Figure 2: Combustible Gas/Carbon Monoxide Sample-Draw Detector Flow Diagram
Main Circuit Board
The main circuit board includes the detector/amp terminal strip, interconnect terminal strip, oxygen sensor terminal strip, pump connector, and flowmeter circuit board connector (see Figure 1).
Detector/Amp Terminal Strip
The detector/amp terminal strip is the upper twelve-point terminal strip in the bottom right corner of the main circuit board. Use the detector/amp terminal strip to connect the IR combustible gas amplifier and the CO amplifier to the main circuit board.
NOTE: The IR combustible gas amplifier and CO amplifier are factory-wired to the main circuit board. See the “Installation” section on page 15 for all wiring procedures related to the sample-draw detector.
Interconnect Terminal Strip
The interconnect terminal strip is the lower twelve-point terminal strip in the bottom right corner of the main circuit board. Use the interconnect terminal strip to connect the sample-draw detector to a controller.

10 · Internal Components

35-3001A-08-XX Sample-Draw Detector

Oxygen Sensor Terminal Strip
The oxygen sensor terminal strip is a two-point terminal strip in the upper right corner of the main circuit board. This terminal strip is not used in this version of the sample-draw detector.
Pump Connector
The pump connector is the two-point connector below the oxygen terminal strip in the upper right corner of the main circuit board. Use the pump connector to connect the pump to the main circuit board.
NOTE: The pump is factory-wired to the main circuit board. See “Installation” on page 15 for all wiring procedures related to the sample-draw detector.
Flowmeter Circuit Board Connector
The flowmeter circuit board connector is a six-position connector in the upper left corner of the main circuit board. Use the flowmeter circuit board connector to connect the flowmeter circuit board to the main circuit board.
NOTE: The flowmeter circuit board is factory wired to the main circuit board. See “Installation” on page 15 for all wiring procedures related to the sample- draw detector.
Flowmeter Circuit Board
The flowmeter circuit board is mounted to the left side of the main circuit board using standoffs. It includes the flowmeter, sensor flow control valve, status LEDs, pressure switch, and pump reset switch.
Flowmeter
The flowmeter is mounted to the right side of the flowmeter circuit board. You can see it through the window in the door. A ball in the flowmeter column indicates the flow rate to the sensor. The flowmeter measures the flow in the range 0.2 to 2.0 SCFH (Standard Cubic Feet per Hour). The optimum flow rate is 1.0 SCFH.
Sensor Flow Control Valve
The sensor flow control valve is mounted to the flowmeter circuit board above the flowmeter. The sensor flow control valve adjusts the flow rate to the detector. Turn the valve’s knob clockwise to increase the flow and counterclockwise to decrease the flow.
Status LEDs
Two status LEDs are above the flowmeter. They are also visible through the window in the housing door. The green Pilot LED is on when the sample-draw detector is receiving power from the controller. The red Fail LED is on when the sample flow rate is below the low flow level.

35-3001A-08-XX Sample-Draw Detector

Internal Components · 11

Pressure Switch
The pressure switch is mounted to the back of the flowmeter circuit board. The pressure switch monitors the flow rate of the incoming gas sample. If the flow rate falls below the preset low flow level, the pressure switch causes the Fail LED to turn on and interrupts the signal from the detector. The interrupted detector signal causes a fail condition at the controller. The low flow level is factory-set at 0.6 SCFH (±0.1 SCFH). See “Adjusting the Low Flow Setting” on page 28 to adjust this setting.
Pump Reset Switch
The pump reset switch is located to the left of the status LEDs. When a low flow condition occurs, the pump will be shut off. To reset the low flow condition and start the pump again, press and hold the pump reset switch for about 2 seconds, then release.
Hydrophobic Filter
The hydrophobic filter is located toward the bottom left of the main circuit board. The filter prevents particulates and water in the incoming gas sample from damaging the flow and detection systems. Replace the filter when it appears dirty, discolored, or clogged.
Pump
The pump is mounted to the right side of the main circuit board. The pump pulls the gas sample into the sample-draw detector. The pump operates on 24 VAC, which is generated from the 24 VDC supplied by the controller.
Charcoal Filter
A charcoal filter is located at the top of the main circuit board. It scrubs out interfering gases which may cause the CO sensor to respond, such as H2S or certain hydrocarbons. Replace the charcoal filter when false high CO readings are noticed, especially in the presence of H2S.
IR Sensor/IR Sensor PCB
The combustible gas sensor is an infrared type plug-in detector. It is installed in the IR flow block, and the IR flow block is mounted to the middle of the main circuit board. It is the lower of the two flow blocks mounted to the main circuit board. A small circuit board, the IR combustible gas sensor PCB, with a 4-wire cable mates to the IR combustible gas sensor and retains it in the flow block. The cable is wired to the IR combustible gas amplifier. The IR combustible gas sensor PCB allows you to replace the sensor without disconnecting the wiring.

12 · Internal Components

35-3001A-08-XX Sample-Draw Detector

IR Amplifier
The IR amplifier converts the electrical output from the IR sensor to a 4 to 20 mA signal that corresponds to the detection range and transmits the signal to a gas monitoring controller. A label on the amplifier indicates the detector drive current. This drive current is factory set. The amplifier is mounted on the top middle edge of the main circuit board. It consists of the zero pot, span pot, controller terminal strip, detector terminal strip, and test points.

Test Points 100-500 mV Range
Sensor Current 148m A

Factory Set Pots
Zero Pot Span Pot

Detector Terminal Strip

RWG B LEL

S PWR / SIG

Controller Terminal Strip

Figure 3: IR Amplifier Component Location
Zero Pot
The zero pot is located in the upper right corner of the amplifier (see Figure 3). Use a small flat blade screwdriver to turn the zero pot’s adjustment screw and adjust the amplifier’s zero (fresh air) output during the start-up and calibration procedures. Turn the adjustment screw clockwise to increase the fresh air output and counterclockwise to decrease the fresh air output.
Span Pot
The span pot is located below the zero pot (see Figure 3). Use a small flat blade screwdriver to turn the span pot’s adjustment screw and adjust the amplifier’s gas response output during the calibration procedure. Turn the adjustment screw clockwise to increase the span output and counterclockwise to decrease the span output.
CAUTION: The amplifier includes additional pots. They are factory-set. Do not adjust them.
Controller and Detector Terminal Strips
The controller terminal strip and detector terminal strip are three- and four- position plug-in style terminal strips, respectively. The controller terminal strip is located on the right side of the amplifier and the detector terminal strip is to the left of it. Both terminal strips are factory wired to the sensor and main circuit board.

35-3001A-08-XX Sample-Draw Detector

Internal Components · 13

Test Points
The test points are on the left side of the amplifier (see Figure 3). The test points produce a 100 mV to 500 mV output that corresponds to the sample-draw detector’s 4 to 20 mA output. Use the test points and a voltmeter to measure the amplifier’s output during the start-up and calibration procedures. The black test point in the upper left corner is the negative (-) test point and the red test point to the left of the zero and span pots is the positive (+) test point.
Carbon Monoxide Sensor/CO Amplifier
The carbon monoxide sensor is a plug-in sensor that plugs into the back of the CO amplifier. The sensor and amplifier are retained in the flow block by two screws. The flow block is mounted to the middle of the main circuit board. It is the higher of the two flow blocks mounted to the main circuit board.
Through a series of chemical and electronic reactions, the CO sensor produces a millivolt output that is proportional to the detection range of the sample- draw detector. A red wire and a blue wire extend from the CO amplifier and allow connection to the detector/amp terminal strip.

Test Points 100-500 mV Range
Zero Pot Span Pot
Figure 4: CO Amplifier Component Location
Zero Pot
The zero pot is located in the lower right corner of the amplifier (see Figure 4). Use a small flat blade screwdriver to turn the zero pot’s adjustment screw and adjust the amplifier’s zero output during the start up and calibration procedures. Turn the adjustment screw clockwise to increase the zero output and counterclockwise to decrease the zero output.
Span Pot
The span pot is located to the left of the zero pot (see Figure 4). Use a small flat blade screwdriver to turn the span pot’s adjustment screw and adjust the amplifier’s gas response during the calibration procedure. Turn the adjustment screw clockwise to increase the span output and counterclockwise to decrease the span output.
Test Points
The test points are on the top edge of the amplifier (see Figure 4). The test points produce a 100 mV to 500 mV output that corresponds to the sample-draw detector’s 4 to 20 mA output. Use the test points and a voltmeter to measure the amplifier’s output during the start-up and calibration procedures. The black test point (CAL 2) in the upper left corner is the negative (-) test point and the red test point (CAL 1) in the upper right corner is the positive (+) test point.

14 · Internal Components

35-3001A-08-XX Sample-Draw Detector

Installation
This section describes procedures to mount the sample-draw detector in the monitoring environment and wire the sample-draw detector to a controller.

Mounting the Sample-Draw Detector
1. Select the mounting site. Consider the following when you select the mounting site: · Is there enough room to open the housing door and make wiring and tubing connections at the bottom of the housing? · Make sure there is sufficient room to perform start-up, maintenance, and calibration procedures. · Are the flowmeter and status LEDs visible?

1.13 .40

6.50 4.00

Ø .30 x . 50 (4X) MOUNTING

.78

8.50

P ilo t Fail

Sample Drawing Gas Detector

35- 3001

8.88

ww w. rki in st ru me n ts. com
.80 .85
4.50 NOTE: H ousing i s 4.3 inches d eep
Figure 5: Outline and Mounting Dimensions
35-3001A-08-XX Sample-Draw Detector

Installation · 15

2. Close and latch the housing door.
NOTE: The sample-draw detector is shipped with the mounting feet “tucked under” the housing to protect the mounting feet during shipment.
3. Slightly loosen the screw that secures the mounting foot to the housing, then rotate the mounting foot 180 degrees (see Figure 5).
4. Tighten the screw that secures the mounting foot to the housing.
5. Repeat steps 3 and 4 for the remaining three mounting feet.
6. Position the sample-draw housing on a vertical surface at eye level (4 1/2 to 5 feet from the floor).
7. Insert 1/4 inch screws through the slots in the mounting feet to secure the housing to the mounting surface.
Connecting the Sample Lines to the Sample-Draw Detector
See Figure 7 for the fitting layout.
Installing the Inlet Line with Particle Filter Connected to the Inlet Fitting
1. Loosen the nut on the inlet fitting until 3 threads are visible.
2. Push the particle filter’s tubing stub into the inlet fitting until it stops. Be sure the arrow on the particle filter is pointing toward the inlet fitting.
3. Hand tighten the nut on the inlet fitting so the ferrules clamp on the tubing. If the tube nut is removed, see Figure 7 for the arrangement of the fitting components.
4. Connect a length of sample tubing to the other side of the particle filter and route it to the sampling area. 1/4″ O.D. rigid polypropylene, Teflon, or flexible polyurethane tubing may be used. RKI Instruments, Inc. recommends using either 1/4″ O.D. x 1/8″ I.D. or 1/4″ O.D. x 0.170″ I.D. tubing based on your length requirements. See “Specifications” on page 6 for maximum tubing lengths based on tubing size.
CAUTION: If you use flexible sample tubing (polyurethane is acceptable), use an appropriate insert if necessary to provide support to the tubing and ensure a good seal when connecting to the flexible stub on the filter.
CAUTION: Avoid loops or slumps in the incoming sample line. To reduce response time, keep the incoming sample line as short as possible.

16 · Installation

35-3001A-08-XX Sample-Draw Detector

Installing the Inlet Line without Particle Filter Connected to the Inlet Fitting
1. Loosen the nut on the inlet fitting until 3 threads are visible.
2. Push 1/4″ O.D. rigid polypropylene or rigid Teflon sample tubing into the fitting until it stops. Flexible polyurethane tubing may be used with an appropriate insert. RKI Instruments, Inc. recommends using either 1/4″ O.D. x 1/8″ I.D. or 1/4″ O.D. x 0.170″ I.D. tubing based on your length requirements. See “Specifications” on page 6 for maximum tubing lengths based on tubing size.
CAUTION: If you use flexible sample tubing (polyurethane is acceptable), use an appropriate insert to seal the connection between the tubing and the inlet fitting.
3. Hand tighten the nut on the inlet fitting so the ferrules clamp on the tubing. If the tube nut is removed, see Figure 7 for the arrangement of the fitting components.
4. Route tubing from the inlet fitting to the sample area. See “Specifications” on page 6 for maximum tubing lengths based on tubing size.
CAUTION: Avoid loops or slumps in the incoming sample line. To reduce response time, keep the incoming sample line as short as possible.
5. If desired, install the particle filter onto the end of the inlet line. Be sure the arrow on the particle filter is pointed toward the inlet line.
Installing the Exhaust Line
1. Loosen the nut on the exhaust fitting until 3 threads are visible.
2. Push 1/4″ O.D. rigid polypropylene or rigid Teflon sample tubing into the fitting until it stops. Flexible polyurethane tubing may be used with an appropriate insert. RKI Instruments, Inc. recommends using either 1/4″ O.D. x 1/8″ I.D. or 1/4″ O.D. x 0.170″ I.D. tubing based on your length requirements. See “Specifications” on page 6 for maximum tubing lengths based on tubing size.
CAUTION: If you use flexible sample tubing (polyurethane is acceptable), use an appropriate insert to seal the connection between the tubing and the inlet fitting.
3. Hand tighten the nut on the exhaust fitting so the ferrules clamp on the tubing. If the tube nut is removed, see Figure 7 for the arrangement of the fitting components.
4. Route the opposite end of the tubing to an open area where the sample can safely disperse or to an exhaust duct. See “Specifications” on page 6 for maximum tubing lengths based on tubing size.

35-3001A-08-XX Sample-Draw Detector

Installation · 17

Wiring the Sample-Draw Detector to a Controller
WARNING: Always verify that the controller is off and that power to the controller is off before you make wiring connections.
1. Turn off the controller.
2. Turn off power to the controller.
3. Unlatch and open the housing door of the sample-draw detector.
4. Guide a five-conductor, shielded cable or five wires in conduit through the conduit hub at the bottom of the sample-draw housing. A minimum of 18 AWG wire is recommended.
5. Connect the cable to the sample-draw detector’s interconnect terminal strip as shown in Figure 6.
6. Close and latch the housing door of the sample-draw detector.
CAUTION: If using shielded cable, leave the cable shield’s drain wire insulated and disconnected at the sample-draw detector. You will connect the opposite end of the drain wire at the controller.
7. Route the cable or wires in conduit leading from the sample-draw detector through one of the conduit hubs at the controller.
8. Connect the wires to the applicable detector/transmitter terminal strip at the controller as shown in Figure 6. Refer to the controller operator’s manual and the controller detector head specification sheet for the 35-3001A-08-XX for detector/terminal strip connections specific to the controller.

18 · Installation

35-3001A-08-XX Sample-Draw Detector

Se nsor Current 148m A

ZE R O S PA N

R

WG

B

L EL

S P W R / S IG

Not Used on This Version
Red White Black

Red White Green Black
IR Sensor PCB

Blue (S) Red (+)
A M P 1 A M P 2 O XY L EL /I R

PATS2 01

PATS1 01

IR Sensor

+ 24 VDC IR 4/20 Signal
– (DC Ground)

CO

+ 24 VDC

4/20 Signal

AMP 1 AMP 2 O XY

L EL /I R

Controller or Recording Device
Figure 6: Wiring the Sample-Draw Detector to a Controller
9. If shielded cable is used, connect the cable’s drain wire to an available chassis (earth) ground at the controller. RKI controllers typically have a ground stud that can be used to ground the cable’s drain wire.

35-3001A-08-XX Sample-Draw Detector

Installation · 19

Start Up
This section describes procedures to start up the sample-draw detector and place the sample-draw detector into normal operation.
Introducing Incoming Power
1. Complete the installation procedures described earlier in this manual.
2. Verify that the wiring is correct and secure. Refer to the controller operator’s manual for connections at the controller.
3. Turn on or plug in the power to the controller, then turn on the controller.
4. Verify that the sample-draw detector’s Pilot LED is on.
5. Verify that the controller is on and operating properly. Refer to the controller operator’s manual.
NOTE: When first powered up, the sample-draw detector will enter about a one minute period when the 4-20 mA output is stabilizing and may be above the controller alarm points or well below zero momentarily. RKI controllers have a one minute warmup period when the controller does not display any gas reading or give any alarm indication. The CO2 transmitter’s 4-20 mA signal should be stable by the time the controller’s warmup period is over.
6. Verify that the flowmeter indicates a flow rate of approximately 1.0 SCFH. If necessary, use the sensor flow control valve to adjust the flow rate. Turn the valve’s knob clockwise to increase the flow and counterclockwise to decrease the flow.
NOTE: The following step tests for leaks in the sample line. This test will cause a low flow condition at the sample-draw detector and a fail condition at the controller. Be sure to put the controller into its calibration program or disable external alarms before performing this test.
7. Verify that the incoming sample line is not leaking. To test the sample line, press and hold the reset switch and plug the open end of the sample line with your thumb. If the flowmeter ball drops to the bottom of the flowmeter, the incoming sample line is not leaking.
8. Remove your thumb from the sample line, release the reset switch, and verify the flowmeter returns to a normal flow rate.
9. Enable alarms or place the controller in normal operation.
CAUTION: Allow the sample-draw detector to warm up for 5 minutes before you continue with the next section, “Setting the Zero Reading.”

20 · Start Up

35-3001A-08-XX Sample-Draw Detector

Setting the Zero Reading
CAUTION: If you suspect the presence of combustible or toxic gas or an abnormal oxygen concentration in the monitoring environment, use the calibration kit and the zero air calibration cylinder to introduce “fresh air” to the sensor and verify an accurate zero setting. See “Calibration, IR Combustible Gas Sensor” on page 30. and “Calibration, CO Sensor” on page 32 for instructions on using a zero air calibration cylinder for setting the zero reading.
1. Verify that the sample-draw detector is sampling a fresh air environment (environment known to be free of combustible and toxic gas and of normal oxygen concentration, 20.9%).
2. Verify a display reading of 0% LEL or 0% vol depending on the combustible gas sensor and a reading of 0 ppm for the CO channel on the controller display screen. If the display reading is 0% LEL or 0% vol for the combustible gas channel and 0 ppm for the CO channel, start up is complete. The sample-draw detector is in normal operation. If the display reading is not 0% LEL or 0% vol for the combustible gas channel or 0 ppm for the CO channel, continue with step 3.
3. Perform a zero (fresh air) operation at the controller. See “Calibration, IR Combustible Gas Sensor” on page 30 and “Calibration, CO Sensor” on page 32 for instructions to perform a zero (fresh air) operation.
Maintenance
This section describes maintenance procedures. It includes preventive maintenance procedures. This section also includes procedures to troubleshoot the sample-draw detector, replace components of the sample-draw detector, adjust the low flow setting, and remove the particle filter’s tubing stub.
Preventive Maintenance
This section describes a preventive maintenance schedule to ensure the optimum performance of the sample-draw detector. It includes daily, monthly, and quarterly procedures.
Daily Visual Checks
1. Verify that the Pilot LED is on.
2. Verify that the flowmeter indicates a flow rate of approximately 1.0 SCFH. If necessary use the sensor flow control valve to adjust the flow rate to 1.0 SCFH. Turn the valve’s knob clockwise to increase the flow and counterclockwise to decrease the flow.
3. Verify a display reading of 0% LEL or 0% vol depending on the combustible gas sensor and 0 ppm for the carbon monoxide channel at the controller. Investigate significant changes in the display reading.

35-3001A-08-XX Sample-Draw Detector

Maintenance · 21

Quarterly Calibration
Calibrate the sample-draw detector as described in “Calibration, IR Combustible Gas Sensor” on page 30 and “Calibration, CO Sensor” on page 32.
Troubleshooting
The troubleshooting guide describes symptoms, probable causes, and recommended action for problems you may encounter with the sample-draw detector.
NOTE: This troubleshooting guide describes sample-draw detector problems only. See the controller Operator’s Manual if the controller exhibits any problems.
Fail Condition
Symptoms
· The sample-draw detector’s Fail LED is on. · The monitoring device is operating properly but indicates a reading well below zero.
Probable causes
· The sample-draw detector’s flow rate is too low because of an obstructed sample line, failed pump, etc.
· The sample-draw detector is malfunctioning. · The sensor wiring is disconnected or misconnected.
Recommended action
1. At the sample-draw detector, set the correct flow rate with the sensor flow control valve. 2. If you cannot set the correct flow rate, check the sample lines for obstructions or kinks. 3. Verify that the sensor wiring is correct and secure. “Wiring the Sample-Draw Detector to a
Controller” on page 18 describes sensor wiring connections. 4. Calibrate the sample-draw detector as described in “Calibration, IR Combustible Gas Sensor”
on page 30 and “Calibration, CO Sensor” on page 32. 5. If the fail condition continues, replace the sensor(s) as described in “Replacing Components
of the Sample-Draw Detector” on page 24. 6. If the fail condition continues, contact RKI Instruments, Inc. for further instruction.

22 · Maintenance

35-3001A-08-XX Sample-Draw Detector

Slow or No Response/Difficult or Unable to Calibrate
Symptoms
· Unable to accurately set the zero or response reading during the calibration procedure. · The sensor requires frequent calibration.
Probable causes
· The calibration cylinder is low, out-dated, or defective. · If a demand flow regulator calibration kit is used, the demand flow regulator is not
functioning properly. · The sample-draw detector’s flow rate is too low because of an obstructed sample line,
failed pump, etc. · The sample-draw detector is malfunctioning.
Recommended action
1. Verify that the calibration cylinder contains an adequate supply of a fresh test sample.
2. If a demand flow regulator calibration kit is used, use a different demand flow regulator to determine if the original one is functioning properly.
3. If necessary, set the correct flow rate with the sensor flow control valve.
4. If you cannot set the correct flow rate, check the sample line for obstructions or kinks.
5. If the calibration/response difficulties continue, replace the sensor as described later in this section.
6. If the calibration/response difficulties continue, contact RKI Instruments, Inc. for further instruction.

35-3001A-08-XX Sample-Draw Detector

Maintenance · 23

Replacing Components of the Sample-Draw Detector
This section includes procedures to replace the IR combustible gas sensor, IR combustible gas amplifier, carbon monoxide sensor, carbon monoxide amplifier, charcoal filter, hydrophobic filter, and particle filter.
Replacing the IR Sensor
1. Turn off the controller. 2. Turn off power to the controller. 3. Open the housing door of the sample-draw detector. 4. Unscrew and remove the four screws that secure the IR combustible gas sensor PCB, then lift
the IR combustible gas sensor PCB and sensor off of the flow block. There is a gasket at the bottom of the flow block. Be sure the gasket stays in place.
5. Unplug the sensor from the IR combustible gas sensor PCB. 6. Verify that you are using the correct replacement sensor, then plug the sensor into the IR
combustible gas sensor PCB. 7. Place the sensor and sensor PCB in the IR combustible gas sensor cavity. 8. Secure the sensor PCB on the flow block with the four screws you removed in step 4. 9. Close and latch the housing door. 10. Turn on power to the controller. 11. Turn on the controller.
CAUTION: Allow the replacement sensor to warm up for 5 minutes before you continue.
12. Calibrate the replacement sensor as described in “Calibration, IR Combustible Gas Sensor” on page 30.
Replacing the IR Amplifier
1. Turn off the controller. 2. Turn off power to the controller.
3. Open the housing door of the sample-draw detector. 4. Remove the detector and controller plug-in terminal strips by grasping the sides of the strips
with your fingers. Let the terminal strips hang by their connected wires while you replace the amplifier.
5. Unscrew the screw in the lower left corner of the amplifier and remove the screw, lock washer, and flat washer. Be careful not to lose any of these parts.

24 · Replacing Components of the Sample-Draw Detector

35-3001A-08-XX Sample-Draw Detector

6. Remove the old amplifier from the main circuit board.

7. Install the new amplifier in the same orientation as the old amplifier. See Figure 1.

8. Reinstall the screw, lock washer, and flat washer you removed in step 5.

9. Install the detector and controller plug-in terminals strips into their sockets on the new amplifier. If controller leads or detector cable leads were removed from the plug-in terminal strips during this procedure, refer to Table 2 and Table 3 below.
Table 2: Reconnecting the Amplifier to the Detector/Amp Terminal Strip

Amplifier Controller Terminal Strip

Detector/Amp Terminal Strip on Main PCB

PWR/SIG “-”

PWR/SIG “S”

S

PWR/SIG “+”

Table 3: Reconnecting the IR Combustible Gas Sensor to the Amplifier

Amplifier Detector Terminal Strip

Detector Lead

DETECTOR “R”

RED

DETECTOR “W”

WHT

DETECTOR “G”

GREEN

DETECTOR “B”

BLK

NOTE: When the sample-draw detector is first powered up with a new amplifier, the initial output may be either high or below zero depending on the setting of the zero pot. Be sure to make arrangements so that this does not cause unwanted alarms.

10. Turn on power to the controller. 11. Turn on the controller and place it into normal operation. 12. Allow the sample-draw detector to warmup for 5 minutes. 13. Calibrate the IR combustible gas sensor as described in “Calibration, IR Combustible Gas
Sensor” on page 30.

Replacing the CO Sensor
1. Turn off the controller. 2. Turn off power to the controller.

35-3001A-08-XX Sample-Draw Detector

Replacing Components of the Sample-Draw Detector · 25

3. Open the housing door of the sample-draw detector. 4. Unscrew the two screws in the upper right and lower left corners of the CO flow block then
lift the CO amplifier and sensor off of the flow block. There is a gasket at the bottom of the flow block. Be sure the gasket stays in place.
5. Unplug the sensor from the CO amplifier. 6. Verify that you are using the correct replacement sensor, then plug the sensor into the CO
amplifier. 7. Place the sensor and amplifier in the CO sensor cavity. 8. Secure the CO amplifier on the flow block with the two screws you removed in step 4. 9. Close and latch the housing door. 10. Turn on power to the controller. 11. Turn on the controller.
12. Allow the sample-draw detector to warmup for 5 minutes.
13. Calibrate the replacement sensor as described in “Calibration, CO Sensor” on page 32.
Replacing the CO Amplifier
1. Turn off the controller.
2. Turn off power to the controller.
3. Open the housing door of the sample-draw detector.
4. Disconnect the red and blue wires coming from the CO amplifier from the AMP 2 position on the detector/amp terminal strip.
5. Unscrew the two screws in the upper right and lower left corners of the CO flow block then lift the CO amplifier and sensor off of the flow block. There is a gasket at the bottom of the flow block. Be sure the gasket stays in place.
6. Disconnect the sensor from the CO amplifier.
7. Plug the CO sensor into the new CO amplifier.
8. Place the sensor and amplifier in the CO sensor cavity. 9. Secure the CO amplifier on the flow block with the two screws you removed in step 5. 10. Reconnect the wires coming from the CO amplifier to the AMP 2 position on the detector/
amp terminal strip. Connect the red wire to the “+” terminal. Connect the blue wire to the “S” terminal.
NOTE: When the sample-draw detector is first powered up with a new amplifier, the initial output may be either high or below zero depending on the setting of the span pot. Be sure to make arrangements so that this does not cause unwanted alarms.

26 · Replacing Components of the Sample-Draw Detector

35-3001A-08-XX Sample-Draw Detector

11. Turn on power to the controller. 12. Turn on the controller and place it into normal operation. 13. Allow the sample-draw detector to warmup for 5 minutes. 14. Calibrate the sample-draw detector as described in “Calibration, CO Sensor” on page 32.
Replacing the Charcoal Filter
1. Turn off the controller. 2. Turn off power to the controller. 3. Open the housing door of the sample-draw detector. 4. Locate the charcoal filter. It is at the top of the main circuit board. 5. Pull the charcoal filter away from the main circuit board so that it is easier to access. 6. Disconnect the filter from the rubber elbows on each end of the filter, then remove the filter
from the sample-draw detector. 7. Install the new filter. If there is an arrow on the filter, be sure that it’s pointing in the direction
of flow which is toward the tubing that goes to the CO sensor flow block inlet. 8. Arrange the charcoal filter as shown in Figure 1. 9. Turn on power to the controller. 10. Turn on the controller and place it into normal operation. 11. Verify that the flow rate is approximately 1.0 SCFH, then close the housing door.
Replacing the Hydrophobic Filter
1. Turn off the controller. 2. Turn off power to the controller. 3. Open the housing door of the sample-draw detector. 4. Disconnect the filter from the rubber elbows on each end of the filter, then remove the filter
from the sample-draw detector. 5. Install the new filter. Be sure the side of the filter marked “INLET” is connected to the elbow
that is connected to the inlet fitting. 6. Turn on power to the controller. 7. Turn on the controller. 8. Verify that the flow rate is approximately 1.0 SCFH, then close the housing door.

35-3001A-08-XX Sample-Draw Detector

Replacing Components of the Sample-Draw Detector · 27

Replacing the Particle Filter
1. Turn off the controller.
2. Turn off power to the controller.
3. If the particle filter is installed at the inlet fitting: a. Disconnect the tubing routed to the sampling area, if installed, from the particle filter. b. Disconnect the particle filter from the tubing stub. c. Install the new particle filter onto the tubing stub. Be sure the arrow on the particle filter is pointing toward the inlet fitting. d. Reinstall the tubing routed to the sampling area.
4. If the particle filter is installed at the end of the inlet line: a. Remove the particle filter from the tubing stub. b. Install the new particle filter onto the tubing stub. Be sure the arrow on the particle filter is pointing toward the inlet line.
5. Turn on power to the controller.
6. Turn on the controller.
Adjusting the Low Flow Setting
NOTE: Adjusting the low flow setting will cause a low flow alarm at the sample-draw detector and a fail alarm at the controller. Be sure to put the controller into its calibration program or disable external alarms before performing this test.
The factory-set low flow setting is 0.6 SCFH (±0.1). To adjust the low flow setting: 1. Use the sensor flow control valve to set the flow to 0.6 SCFH. Turn the valve’s knob
clockwise to increase the flow and counterclockwise to decrease the flow. If the sample-draw detector goes into low flow alarm before you can adjust the flow down to 0.6 SCFH, adjust the pressure switch adjustment screw 1/4 turn clockwise, then attempt to set the flow again. Repeat this step until you are able to adjust the flow to 0.6 SCFH.
NOTE: The pressure switch adjustment screw is accessible through a circular cutout in the flowmeter circuit board.
2. Slowly turn the pressure switch adjustment screw counterclockwise just until the sample-draw detector goes into low flow alarm.
3. Turn the sensor flow control valve’s knob clockwise to increase the flow until the unit is out of low flow alarm when the reset switch is pressed and released.
4. Decrease the flow very slowly by turning the sensor flow control valve’s knob counterclockwise and verify that the low flow alarm is 0.6 SCFH (±0.1). If the low flow alarm is set too high, turn the pressure switch adjustment screw slightly clockwise. Repeat steps 3 and 4 if necessary.

28 · Replacing Components of the Sample-Draw Detector

35-3001A-08-XX Sample-Draw Detector

5. Use the sensor flow control valve to set the flow to 1.0 SCFH.
6. Make sure the sample-draw detector’s Fail LED is off.
Removing the Particle Filter’s Tubing Stub, if Necessary
A short tubing stub comes factory installed in the particle filter. It is used for connecting the particle filter to the inlet fitting. If you have installed the particle filter and no longer want it installed, you will need to remove the particle filter’s tubing stub from the inlet fitting and replace it with tubing.
1/4″ Tube

O-ring Tube Nut

Inside of Case Outside of Case
Fitting Body Back Ferrule Front Ferrule

1/4″ Tube
Figure 7: Inlet Fitting with Tubing Stub
CAUTION: Do not pull the tubing stub downward to remove it.
1. Remove the particle filter from its tubing stub. 2. Unscrew the outside inlet fitting tube nut from the fitting body. The tubing stub should come
out with the tube nut. Be careful not to lose the O-ring that may come out with the tubing stub. If you do lose the O-ring or if it is damaged, see “Parts List” on page 34 for the spare part number. 3. Push the tubing stub up and out of the front ferrule being careful not to lose the ferrule set. If you do lose the ferrule set or if it is damaged, see “Parts List” on page 34 for the spare part numbers. 4. Push the new tubing up through the inlet fitting tube nut and replace the ferrule set and the Oring, if it came out, in the orientation shown in Figure 7.

35-3001A-08-XX Sample-Draw Detector

Replacing Components of the Sample-Draw Detector · 29

5. Screw the inlet fitting tube nut back onto the fitting body. See “Connecting the Sample Lines to the Sample-Draw Detector” on page 16 for instructions to install a new piece of tubing into the fitting.
Calibration Frequency
Although there is no particular calibration frequency that is correct for all applications, a calibration frequency of every 3 months is adequate for most sample draw detector applications. Unless experience in a particular application dictates otherwise, RKI Instruments, Inc. recommends a calibration frequency of every 3 months for the CO detector and every 6 months for the infrared combustible gas detector. If an application is not very demanding, for example detection in a clean, temperature controlled environment, and calibration adjustments are minimal at calibration, then a calibration frequency of every 6 months is adequate for the CO detector and every 9 to 12 months is adequate for the infrared combustible gas detector. If an application is very demanding, for example if the environment is not well controlled, then more frequent calibration than every 3 months for the CO detector and every 6 months for the infrared combustible gas detector may be necessary.
Calibration, IR Combustible Gas Sensor
This section describes how to calibrate the IR combustible gas sensor of the sample-draw detector. It includes procedures to prepare for calibration, set the zero reading, set the response reading, and return to normal operation. Ensure that you are using the correct target gas for your sensor. Refer to the following calibration gas requirements:
· 35-3001A-08-01 needs to be calibrated with %LEL levels of methane. · 35-3001A-08-02 needs to be calibrated with %LEL levels of the target hydrocarbon gas. · 35-3001A-08-03 needs to be calibrated with %volume levels of methane.
NOTE: This procedure describes calibration using a demand flow regulator.
Preparing for Calibration
1. Follow the instructions in the controller’s operator’s manual for entering calibration mode.
NOTE: If you can verify a fresh air environment, it is not necessary to use the zero air calibration cylinder to set the zero reading.
2. Screw the regulator into a zero air calibration cylinder.
3. Open the housing door.
4. Set a voltmeter to measure in the millivolt (mV) range.

30 · Calibration Frequency

35-3001A-08-XX Sample-Draw Detector

5. Connect the voltmeter to the test points on the IR amplifier. Plug the positive lead into the red (+) amplifier test point; plug the negative lead into the black (-) amplifier test point labeled.
6. Use the following formula to determine the correct test points output for the calibrating sample. Output (mV) = (calibrating sample/fullscale) X 400 + 100 For example, with a calibrating sample of 50% volume and a fullscale setting of 100% volume, the correct output is 300 mV. 300 (mV) = (50/100) X 400 +100
Setting the Zero Reading
1. Connect the sample tubing from the demand flow regulator to the sample- draw detector’s inlet line. This step is not necessary if you verified a fresh air environment earlier in this procedure.
2. Allow the sample-draw detector to draw sample for one minute.
3. Verify a voltmeter reading of 100 mV (± 2 mV).
4. If necessary, use a small flat-blade screwdriver to adjust the zero potentiometer until the voltmeter reading is 100 mV (± 2 mV). If you used a zero air calibration cylinder to set the zero reading, proceed to step 5. If you verified a fresh air environment, proceed to the next section, Setting the Response Reading.
5. Disconnect the sample tubing from the inlet line.
6. Unscrew the regulator from the zero air calibration cylinder.
Setting the Response Reading
1. Screw the regulator into the combustible gas calibration cylinder.
2. Connect the sample tubing from the demand flow regulator to the sample- draw detector’s inlet line.
3. Allow the sample-draw detector to draw sample for one minute.
4. When the reading on the voltmeter stabilizes, verify that the reading matches the response reading (±2 mV) you determined earlier.
5. If necessary, use the span potentiometer on the amplifier to adjust the reading to match the correct response reading.
6. Disconnect the sample tubing from the inlet line.
7. Unscrew the regulator from the combustible gas calibration cylinder.

35-3001A-08-XX Sample-Draw Detector

Calibration, IR Combustible Gas Sensor · 31

Returning to Normal Operation
1. Wait approximately one minute to allow the combustible gas reading to stabilize. 2. Remove the voltmeter leads from the amplifier test points. 3. Close the housing door. 4. Follow the instructions in the controller’s operator’s manual to exit the calibration mode. 5. Store the components of the calibration kit in a safe and convenient place.
Calibration, CO Sensor
This section describes how to calibrate the CO sensor in the sample-draw detector. It includes procedures to prepare for calibration, set the zero reading, set the response reading, and return to normal operation.
NOTE: Calibrating the sample draw detector may cause alarms. Be sure to put the controller into its calibration program or disable external alarms before continuing.
NOTE: This procedure describes calibration using a demand flow regulator.
Preparing for Calibration
NOTE: If you can verify a fresh air environment, it is not necessary to use a zero air calibrating sample to set the zero reading at the controller.
1. Follow the instructions in the controller’s operator’s manual for entering calibration mode. 2. Screw the regulator into the zero air calibration cylinder. 3. Open the housing door. 4. Set a voltmeter to measure in the millivolt (mV) range. 5. Connect the voltmeter to the test points on the CO amplifier.
Plug the positive lead into the red (+) amplifier test point; plug the negative lead into the black (-) amplifier test point. 6. Use the following formula to determine the correct test points output for the test sample.
Output (mV) = (calibrating sample/fullscale) X 400 + 100 For example, with a test sample of 50 ppm and a fullscale setting of 300 ppm, the correct output is 167 mV.
167 (mV) = (50/300) X 400 +100

32 · Calibration, CO Sensor

35-3001A-08-XX Sample-Draw Detector

Setting the Zero Reading
1. Connect the sample tubing from the demand flow regulator to the sample- draw detector’s inlet fitting. This step is not necessary if you verified a fresh air environment earlier in this procedure.
2. Allow the sample draw detector to draw sample for one minute. 3. Verify a voltmeter reading of 100 mV (± 2 mV). 4. If necessary, use a small flat-blade screwdriver to adjust the zero potentiometer until the
voltmeter reading is 100 mV (± 2 mV). If you used a zero air calibration cylinder to set the zero reading, proceed to step 5. If you verified a fresh air environment, proceed to the next section, Setting the Response Reading. 5. Disconnect the sample tubing from the inlet fitting. 6. Unscrew the regulator from the zero air calibration cylinder.
Setting the Response Reading
1. Screw the demand flow regulator onto the carbon monoxide calibration cylinder. 2. Connect the sample tubing from the regulator to the inlet line. 3. Allow the sample-draw detector to draw the calibrating sample for 1 minute. 4. When the reading on the voltmeter stabilizes, verify that the reading matches the response
reading (±2 mV) you determined earlier. 5. If necessary, use the span potentiometer on the amplifier to adjust the reading to match the
correct response reading. 6. Disconnect the sample tubing from the sample-draw detector’s inlet fitting. 7. Reconnect the incoming sample line to the inlet fitting. 8. Unscrew the regulator from the calibration cylinder.
Returning to Normal Operation
1. Wait approximately one minute to allow the carbon monoxide reading to stabilize. 2. Remove the voltmeter leads from the amplifier test points. 3. Close the housing door. 4. Follow the instructions in the controller’s operator’s manual to exit the calibration mode. 5. Store the components of the calibration kit in a safe and convenient place.

35-3001A-08-XX Sample-Draw Detector

Calibration, CO Sensor · 33

Parts List

Table 4 lists replacement parts and accessories for the sample-draw detector.
Table 4: Parts List

Part Number
06-1248RK

Description
Sample tubing, 3/16″ ID x 5/16″ OD, specify length

06-1248RK-03 Sample tubing, 3/16″ ID x 5/16″ OD, 3 feet (for calibration kit)

07-0053RK

Gasket for carbon monoxide flow block

07-0110RK

Gasket for IR flow block

17-2670

Inlet fitting O-ring

17-2671

Inlet fitting front ferrule

17-2672

Inlet fitting back ferrule and tube nut

30-1016RK

Pump

33-0165RK

Hydrophobic filter

33-0167RK

Particle filter

33-6098

Charcoal filter

57-1053RK-10 Amplifier

61-5039RK-CH4 61-5039RK-HC

Infrared CH4 sensor, plug-in type, %LEL range Infrared HC sensor, plug-in type, %LEL range

61-5041RK-CH4 71-0630

Infrared CH4 sensor, plug-in type, %vol range 35-3001A-08-XX Sample-Draw Detector Operator’s Manual (this document)

81-0004RK-01 Calibration cylinder, 50% LEL propane in air, 34 liter steel

81-0004RK-03 Calibration cylinder, 50% LEL propane in air, 103 liter

81-0012RK-01 Calibration cylinder, 50% LEL methane in nitrogen, 34 liter steel

81-0012RK-03 Calibration cylinder, 50% LEL methane in nitrogen, 103 liter

81-0013RK-01 Calibration cylinder, 50% volume methane in nitrogen, 34 liter steel

81-0013RK-05 Calibration cylinder, 50% volume methane in nitrogen, 58 liter

81-0064RK-01 Calibration cylinder, 50 ppm CO in air, 34 liter steel

81-0064RK-03 Calibration cylinder, 50 ppm CO in air, 103 liter

34 · Parts List

35-3001A-08-XX Sample-Draw Detector

Part Number
81-0076RK-01 81-0076RK-03 81-1054RK
81-1055RK
ES-1531-CO

Table 4: Parts List
Description
Zero air calibration cylinder, 34 liter steel
Zero air calibration cylinder, 103 liter
Regulator, demand flow, for 34 liter aluminum, 58 liter, and 103 liter calibration cylinders (cylinders with internal threads)
Regulator, demand flow, for 17 liter and 34 liter steel calibration cylinders (cylinders with external threads)
Carbon monoxide sensor

35-3001A-08-XX Sample-Draw Detector

Parts List · 35

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>