Johnson Controls SE-SPU1001-5 Smart Equipment Controls User Guide

June 11, 2024
Johnson Controls

Johnson Controls SE-SPU1001-5 Smart Equipment™ Controls
3.4 and older Firmware
User Guide

General

Before you begin configuring your unit controller ensure that you understand the application and identify the equipment configuration.

  • Constant Volume
  • Variable Air Volume (VAV)
  • Economizer
  • Hot Gas Reheat
  • Dual Stage
  • Four Stage
  • Heat Pump
  • Thermostat Controls
  • Network Sensor Control
  • Space Sensor Control
  • Discharge Air Control

Understanding the LCD
After you apply power to your rooftop unit (RTU), a start-up sequence begins on the unit control board (UCB) LCD. When the controller is ready, the screen is blank if no faults are present. Use the joystick and the two push buttons below the LCD, to navigate through the menus. See Figure 1.

Move the joystick up and down to move the > cursor and scroll through the selections in the active section of the menu. Each menu selection is either a sub-menu or a property. You can perform the following actions.

  • Press ENTER to display the items in the sub-menu or the values of the selected property.
  • Press ENTER to display the current value of the selected property.
  • Move the joystick up or down to display the values of other properties.

See Figure 2 and Smart Equipment™ 3.4 UCB navigation examples on page 6

CAROMA 300069W Livewell D Shape Family ToiCAROMA 300069W Livewell D Shape
Family Toilet Seat - level menuet Seat - level menu

IMPORTANT
Unit control boards with part numbers SE-SPU10015, SE-SPU1011-5, SE-SPU1002-5, SE-SPU1012-5 have a different hardware component than previous board versions. This new component does not allow downgrading of these boards to any firmware older than 3.3.1.186. If a user attempts to install an older version, the message Info 1025 displays on the LCD screen to indicate that it cannot accept an older firmware version.

CAROMA 300069W Livewell D Shape Family Toilet Seat - ICON
1

Start-up sequence

When you apply power to the unit the UCB begins the following start-up sequence. During the start-up sequence, the joystick, ENTER button, and CANCEL button do not function.

  1. The LCD scrolls the text Johnson Controls on the top line and JCI on the bottom line (Figure 3).
  2. The display backlight and green power LED light and remain lit as long as power is applied to the C and 24V terminals.
  3. The red fault LED lights, goes off briefly, and then flashes throughout the start-up sequence.
  4. The green SA bus LED lights briefly.
  5. The LCD shows a countdown on the top line.CAROMA 300069W Livewell D Shape Family Toilet Seat - Start up countdown
  6. After approximately 15 seconds, the green SA bus LED does one of the following.
  • Lights to indicate that the UCB has not established communication and is awaiting communication from SA bus devices
  • Flashes to indicate the UCB established communication with SA bus devices

After the start-up sequence finishes in 90 – 120 seconds, the display shows the current operating status. For example, idle, startup delay, or cooling on both lines if no alarm is active. The red fault LED stops flashing and turns off. The joystick, ENTER button, and CANCEL button are operational.

Commissioning

Figure 5 shows the Commissioning view second level menus. The Commissioning view consists of 3 three main menus and several sub-menus.

CAROMA 300069W Livewell D Shape Family Toilet Seat - second
level

Commissioning view sub-menus
Your equipment configuration determines which menus appear in the Commissioning view.

  • Use the joystick to move between the menu options.
  • Press ENTER to select an option.

See the Commissioning menu on page 10.
See the pages 8 to 18 for a detailed table of all menus, submenus, and properties.
Validating your configuration
Use the Details > Service menu to ensure that your configuration parameters are correct. This view shows the input values for each input. You can view the Sensors and Coil Sensors values.
If no input value appears, the display shows No Input. This is a convenient way to ensure that all your configuration parameters are set and reading properly.
Important: Save your configuration parameters to a flash drive using the Update > Backup menu before you perform a firmware update.
Connecting your flash drive for a firmware update

  • Connect your flash drive to the USB port on the UCB.
    USB: Wait appears on the LCD. See Figure 6.

Note: If you do not see USB: Wait after you connect your flash drive to the UCB, ensure that it is properly connected. If it is properly connected and you do not see USB: Wait, your flash drive may not be compatible with the UCB or is defective.
After a few seconds, the top line of the LCD displays USB: OK (Figure 7).
The Scan number indicates the files and folders in the top level of the flash drive that are compatible with the UCB.

Figure 7 – USB scan
Keep the flash drive connected to the UCB after the scan completes.
You can press the ENTER button, CANCEL button, or move the joystick up or down to navigate through the display menu.

Performing a system configuration backup

  1. Connect your flash drive to the USB port on the UCB.
  2. When USB OK appears on the LCD, use the joystick on the UCB to select Update and press ENTER.
  3. Select Backup and press ENTER. See Figure 8. BKP: Wait appears while the backup is in progress. During the backup procedure, the colon (:) flashes on the top line and the percentage increases on the bottom line of the display. The backup completes in approximately 30 seconds.
  4. When BKP:OK appears on the LCD and the percentage shows 100, you may remove the flash drive from the USB port.

After the backup completes, a comma separated value (.csv) restoration file is created in the top level of the flash drive. The file name is drawn from the date and time settings in the UCB at the time you create the file. The restoration file size is generally less than 30 KB. Figure 10 shows an example of the .csv file name structure.
Restoration File Name Structure

CAROMA 300069W Livewell D Shape Family Toilet Seat -
Restoration

Use the Upgrade > Restore menu to restore the backup file to the unit and retrieve the configuration after you perform an upgrade or make setpoint changes.
Use the partial cloning feature to take the configuration parameters from the backup file from one unit and update the data on another unit. Use the Upgrade

Part Clone menu on the unit that you want to update.
Note: Only use the Full Cloning feature when you have to replace the UCB board.

Updating Smart Equipment™ software

Auto update – FWU: firmware update
In the release of version 3.3.1.186 1 , an auto update feature was added called firmware update (FWU). This feature determines if there are any mismatches in the firmware versions on all applicable control boards on the unit. For example, on the Economizer, FDD1, FDD2, or 4-Stage boards.
If there are any mismatches, the auto update process begins and automatically pushes the 3.4.1.314 version to all applicable boards on the unit. This may take 7 to 30 minutes
depending on the number of control boards.
Note: Do not use the joystick, ENTER button, or CANCEL button during the auto update process.
The auto update feature required a change to the memory size on the UCB. You can install the 3.4.1.314 firmware revi- sion in an older board with a 4 MB memory, but it cannot per- form the auto update function.2
If the auto update fails for any reason, the LCD displays Firmware mismatch and the fault LED blinks. If this occurs, you must manually update the firmware. See Performing a manual update on page 4

  1. You must perform the firmware update twice back to back
  2. REV. G indicates a 4MB board. REV. H indicates a 8MB board.

Loss of power
If loss of power occurs during the auto update process, the UCB re-attempts the update when the power is restored. The following sequence is performed.

  • 90 seconds after the normal startup sequence is complete the UCB determines whether there are still firmware mismatches.
  • The UCB attempts the auto update up to a maximum of five times.

If the auto update is unsuccessful after five attempts, you must manually update the firmware. Performing a manual update on page 4
Performing a manual update
If you want to update a 3.1 level board (8 MB) with an older 3.0 level firmware, you must perform the update twice.
You require a flash drive with the appropriate software file ending in .pkg to perform the update. You must save the file at the top level of the flash drive.
See Connecting your flash drive for a firmware update on page 3.

  1. Connect your flash drive to the USB port on the UCB.

  2. When USB OK appears on the LCD, use the joystick on the UCB to select Update and press ENTER.
    The first line displays View Ver.
    a. If you want to verify the version in the UCB, push the ENTER button. The current version is displayed.
    b. Press the CANCEL button to return to the Update menu.

  3. Use the joystick to select Backup and press ENTER.

  4. When the top line of the display shows BKP: OK and the second line shows 100, press CANCEL to return to the Update menu and press ENTER.

  5. Use the joystick to select LoadFirm and press ENTER.

  6. The list of firmware versions appears, select 3.4.1.314.secusb.pkg or the firmware version required and press ENTER.
    If the firmware file is not displayed, use the joystick to select the appropriate file.

  7. When Confirm? appears on the LCD, press ENTER. The firmware may take 5 to 15 minutes to load, FWU WAIT appears on the LCD screen. The UCB reboots during the process and the LCD goes blank. When the LCD displays the main menu and the startup timer ends, the upload is finished.

  8. Use the joystick on the UCB to select Update and press ENTER.

  9. Select Restore and press ENTER.

  10. Select RTUxxxx.csv and press ENTER.

  11. When Confirm? appears on the LCD, press ENTER.

The LCD displays RTR:OK and reboots. When the startup timer ends, the configuration is restored.
When the firmware update is complete, proceed with parameter checks.
Viewing the version of the economizer
The economizer board must be connected to the system to view the version.

  1. Use the joystick on the UCB to select Contrler and press ENTER.
    The first line displays Firm.CAROMA 300069W Livewell D Shape Family Toilet
Seat - Display update 2

  2. Use the joystick to select SysCntlrs and press ENTER.
    The first line displays Misc.

  3. Use the joystick to select Econ and press ENTER.
    The first line displays EconMainVer.

  4. Press ENTER.
    The second line displays the version of software installed in the economizer.

Smart Equipment™ 3.4 UCB navigation examples
The following section details the navigation and viewing of the LCD display screen on the Smart Equipment™ control. The control is installed in various commercial Ducted Systems packaged and split system equipment. The following information provides a step-by-step demonstration on how to navigate the basic status menu and how to change basic configuration settings. The navigation steps outlined in this demonstration apply to most menus in the Smart Equipment™ control.
Understanding the Local LCD
After you apply power to your Rooftop Unit (RTU), a start-up countdown begins on the Unit Control Board (UCB) LCD. When the controller is ready, the screen is blank because no faults are present. Use the joystick and the two push buttons below the LCD, to navigate through the menus.

Step 1 – After the start-up countdown is “Startup Delay” screen. Move Joystick. Scroll down to “Details” then press “ENTER”.

CAROMA 300069W Livewell D
Shape Family Toilet Seat - star up coCAROMA 300069W Livewell D Shape Family
Toilet Seat - star up countdown 2untdown 2

Step 5- To adjust the minimum position percentage move the joystick to the right to increase and to left decrease. Then Press “ENTER”. WAIT 5-7 SECONDS FOR VALUE ONSCREEN TO UPDATE!

CAROMA 300069W Livewell D Shape Family Toilet Seat - star up countdoCAROMA
300069W Livewell D Shape Family Toilet Seat - star uCAROMA 300069W Livewell D
Shape Family Toilet Seat - star up countdown 3p countdown 3wn
3

Press the “Cancel” button to exit each menu level. Repeatedly pressing “Cancel” returns the menu to the first “Status, Alarms” screen.
Press the CANCEL button multiple times to exit each menu level. When the LCD returns to the Status, Alarms display the next demonstration can begin. This demonstration shows the Commissioning menu.
Step 1 – After the start-up countdown is “Startup Delay” screen. Move Joystick. Scroll down to “Details” then press “ENTER”.

CAROMA 300069W Livewell D Shape Family Toilet Seat - star up countdown
1

Step 5- To change the selection move the joystick to the right and choose either “YES” or “NO”. Then Press “ENTER”. WAIT 5-7 SECONDS FOR VALUE ONSCREEN TO UPDATE!

These few pages provide a simple demonstration how to navigate the menu’s of the Smart Equipment™ control containing Version 3.4 firmware. Please utilize this document along with the additional information in the Users Guide and detailed navigation menu to adjust the control to customer preferences or job specifications.
NOTE: IF OPERATING THE EQUIPMENT WITH A THERMOSTAT, THE UCB SETPOINTS AND PARAMETERS SHOULD NOT REQUIRE ALTERATION; HOWEVER, THERE MAY BE THE CASE WHERE MINIMUM OUTSIDE AIR, LEAD-LAG OR OTHER CUSTOM SETTINGS ARE REQUIRED. PLEASE READ THIS DOCUMENT IN DETAIL TO UNDERSTAND THE IMPLICATIONS OF MAKING CHANGES BEFORE PROCEEDING. IT IS STRONGLY RECOMMENDED THAT A BACKUP OF PARAMETER SETTINGS BE SAVED ON A USB DRIVE BEFORE MAKING ANY MAJOR CHANGES TO THE CONTROL!

SE UCB DISPLAY MENU GUIDE 3.4

MENU Status ****
SuB MENU Thermostat ****
YI-TSTAT OFF
Y2-TSTAT OFF
Y3-TSTAT OFF
YL-TSTAT OFF
WI-TSTAT OFF
W2-TSTAT OFF
W3-TSTAT OFF
G-TSTAT OFF
Occ-TSTAT ON
MENU Status ****
--- ---
SR ▼ SmokeCtrl ****
OPRPURGECMD FALSE
PURGECMDSRC RATEMP
PURGE FALSE
NETPURGE FALSE
SD NORMAL

Legend

DEFAULT SETTINGS IN RED BLUE = UCB CONDITIONAL PARAMETER
TAN = ECONOMIZER BOARD PRESENCE DKGREEN = ECONOMIZER BOARD

PRESENCE + ANOTHER CONDITION
Joystick navigation|
---|---
Press Enter 1 time|
**Press Enter Scroll Down Press Cancel to return to Previous Menu|
MENU| Status
---|---
SR| Status
UNIT-S| IDLE| (UNIT STATUS)
Econ-S| DisABLED| (ECONOMIZER STATUS)
EXF-S| OFF-IDLE| (EXHAUST FAN STATUS)
FAN-S| OFF-IDLE| (FAN STATUS)
HGR-S| OFF-IDLE| (HOT GAs REHEAT STATUS)
CL6-S| OFF-IDLE| [ (COOLING STATUS)
DFS| NORMAL| (DIRTY FILTER SWITCH)
UCBZLVAC FOROUTP| 3VAC| (UCB 24VAC INPUT)
MENU| Statu
---|---
SR| Status**
ECONCNTLR| NoT PRESENT| (ECON BRD COMM STATUS)
LSTGCNTLR| NOT PRESENT| (FC BUS BACNET NETWORK ADDRESS)
FDDMCNTLR| NoT PRESENT| (REFR CIRC |-2 STATUS)
FDDSCNTLR|  NoT PRESENT| (REFR CIRC 3-4 STATUS)

MENU Alarms ****
No EVENTS (No_ACTIVE ALARM)
ALARM DESCRIPTION (MOST RECENT ALARM)
ALARM DESCRIPTION (2ND MOST RECENT ALARM)
ALARM DESCRIPTION (3RD MOST RECENT ALARM)
ALARM DESCRIPTION (LTH MOST RECENT ALARM)
ALARM DESCRIPTION (5TH MOST RECENT ALARM)

CAROMA 300069W Livewell D Shape Family Toilet Seat - FIGURE
3

MENU Summary
SU-NVENTRE **** Sensors
ST Operational Mode
OPROAT 730F
OPRST 75.0 F
OPRSSO 0F
OPRSH 49.6 %H
OPROAH 199%H
OPRIAQ L77PRM
OPROAQ 990pPM
OPRPURGECMD FALSE
MENU Summary
--- ---
SUB MENU Sensors
SUB MENU Sensors ****
SAT (60.7 F)
RAT (73.0 F)
OAT 75.0 F
OATSRC LocAL INPUT
ST 699 F
STSRe NETWORK SENSOR
STALARMOFFSET (5 F)

SETPONT OFFSET)
STALARMDELAY| (60MIN)| (SPACE TEMPERATURE ALARM
TIME DELAY)
SS0| 0F| (SPACE TEMP SETPOINT OFFSET INPUT)
SSOSRc| NETWORK SENSOR| (SPACE TEMPERATURE SETPOINT OFFSET SOURCE)
MENU| Summary
---|---
SUB MENU| Sensors
SUB MENU| Sensors
SSORANGE| (3.6 F)| (SPACE TEMPERATURE SETPOINT OFFSET RANGE)
RAH| 79.4 %H| (SPACE HUMIDITY RAH INPUT)
SHSRC| LOCAL INPUT| (SPACE HUMIDITY SOURCE)
OAH| 50.2 %H| (OUTDOOR AIR HUMIDITY INPUT)
OAHSRC| LocAL INPUT| (OUTDOOR AIR HUMIDITY SOURCE
1AQ| 477PPM| (IAQ 0-10 VDC INPUT)
1AQSRC| LocAL INPUT|  (INDOOR AIR QUALITY SOURCE)
0AQ| 477PPM| (0AQ 0-l0vDC INPUT)
OAQSRe| LOCAL INPUT| (OUTDOOR AIR QUALITY)
PURGECMDSRC| RATEMP| (PURGECMDS OURCE)
SAH| L9%H| (SAH 0-10 voCINPUT)
MAT| 70F| (MIXED AIR TEMPERATURE)
BLDGPRES| 095″/w| (UILDING STATIC PRESSURE)
DerPrs| 150w| (DucTEREs]0,Svpcy)
MENU| Summary
---|---
SUB MENU|  Sensors
SUB MENU|
Unit
NaME| RTUXXxx| (14 CHARACTER MAX)
MoDEL#| RTUXXXXX| (I CHARACTER MAX)
SERIAL#| DEFAULT_SERIAL| (I4 CHARACTER MAX)
MODELNAME| | (MODEL NAME)
UNIT-S| IDLE| (UNIT STATUS)
UNITEN| ENABLE| (UNIT ENABLE)
HDWRRESET| No| (HARDWARE RESET)
RESETLO| OFF| (RESET Lockours)
Joystick navigation|
---|---
Press Enter 1 time|
Press Enter Scroll Down Press Cancel to return to Previous Menu|

Legend

DEFAULT SETTINGS IN RED BLUE = UCB CONDITIONAL PARAMETER
TAN = ECONOMIZER BOARD PRESENCE DKGREEN = ECONOMIZER BOARD

PRESENCE + ANOTHER CONDITION

CAROMA 300069W Livewell D Shape Family Toilet Seat - FIGURE
4

MENU  Commission
SUB MENU Standard
OccMobE EXTERNAL
TSTAT-ONLY Yes
CLe-EN Yes
#CLGSTGS
HTG-EN Yes
#HTESTS 0
Econ-EN YES
ECON-MINPos 20%
LowSPEEDFAN-MINPOS 25%
FANONOCC YES
SATCOOLLIMIT-EN YES
SATCooLLIMIT-SP 50 F
CLGOATCUTOUT-EN YES
CLGOATCuTOUT 45 F
MENU  Commission
--- ---
SuB MENU Options
FANCTL-TYPE SINGLE
SeeD (ID BLowER TYPE)
EXFTYPE NoNE
#REFRIGSYS 4
LowAMB-EN YES
LEADLAG-EN No
HGP-INST No
HTG-EN YeS
HTG-TYPE STAGED
MENU ▼ Commission
--- ---
SUB MENU ▼Options
SATHTGLIMIT-EN YES
SATHTGLIMIT-SP 140 F
HTGOATCuUTOUT-SP 75 F
APSSETUP NONE
DFSINST (DIRTY FILTER SWITCH INSTALLED)
DVENT-MoDE DisABLED
HGR-EN No
MORNW-EN No
#HTPUMPSTGS 0
LOWAMBFANPRERUNCOOL 60 SEC
PIDTUNRST FALSE
LowAMBSTART NO
SZVAVEN OFF
MENU ▼Commission
--- ---
ST ▼ Network Setup
FCBUSMODE WIRED
ADDRESS 4
DEVICELD I
BAUDRATE AUTO
DEVNAME UCBAPP
ENCODETYPE ANSI X3.4 (US-ASCII)

CAROMA 300069W Livewell D Shape Family Toilet Seat - FIGURE
5

MENU ▼Controller
SUB MENU ▼ Network
DEVNAME UCBAPP
BASCom BACNET
ADDRESS 4
TIMEZONE CENTRAL
DESCRIPT
COMM-S WAITING FOR POLL
FCBusMobE WIRED
OPRBAUDRATE AuTo
BAUDRATE AuTo
DEVICEID I
LANGUAGE ENGLISH
UNITS IP
#NETSENSORS I
RELEARN FALSE
ENCODETYPE ISO I0646(UCS-2)
MENU ▼Controller
SUB MENU Firm
FIRM-S FIRMWARE VERSIONS OK
FIRMVER 3.4.1.314
UCBMAINVER 3.4.1.314
UCBAPPVER 3.4.1.314
UCBHARDVER 001
ECONMAINVER 3.4.1.314
ECONAPPVER 1223_2017.9.6.255
ECONHARDVER 001
4STGMAINVER 3.4.1.314
4STGAPPVER 1223_2017.9.6.255
4STGHARDVER 001
FDDMMAINVER 3.4.1.314
FDDMAPPVER 1223_2017.9.6.255
FDDMHARDVER 1
MENU ▼Controller
SUB MENU ▼Network Inputs
NETST
NETSSO
NETSH
NETOCC NoT SET
NETTEMPOCC FALSE
NETIAQ
NETFANREQ
NETOAT
NETOAH
NETOAQ
NETPURGE
DIRLOADSHD YEs/No
REDLINE Yes/No
MENU ▼Controller
SUB MENU ▼FDD
UNITTYPE
EER
SUBCOOLGOAL
REFRGTYPE
HISIDEPORTLOC
EVAPCOIL-TYPE
CONDCOIL-TYPE
INMETERDEV-TYPE
OUTMETERDEV-TYPE
UNITCAP
FANPOWER
SUPERHEAT GOAL
ALTITUDE
MENU Controller
SuB MENU ▼Time
TIME ZONE CENTRAL
MENU ▼Controller
SuB MENU ▼Description
CNTRLTYPE CV
EQUIPTYPE RTU
▼▲◀▶ Joystick navigation
--- ---

Press Enter 1 time
Press Enter Scroll Down|
Press Cancel to return to Previous Menu|

Legend

DEFAULT SETTINGS IN RED BLUE = UCB CONDITIONAL PARAMETER
TAN= ECONOMIZER BOARD PRESENCE DKGREEN= ECONOMIZER BOARD

PRESENCE + ANOTHER CONDITION

CAROMA 300069W Livewell D Shape Family Toilet Seat - FIGURECAROMA 300069W
Livewell D Shape Family Toilet Seat - FIGURE 6 6

MENU ▼Update
SUB MENU ▼View Ver
3.4.1.314 FiRMWARE OK
MENU ▼Update
SUB MENU ▼LOADFIRM
NO PACKAGE PRESENT ERROR
MENU ▼Update
SUB MENU ▼Backup
BKPWAIT BCFG 0%
MENU ▼Update
SUB MENU ▼Restore

SERIALFLASH/BACKUPCONFIG
MENU| ▼Update
SUB MENU| ▼Full Clone
SERIALFLASH/BACKUPCONFIG
MENU| ▼Update
SUB MENU| ▼Partial Clone
SERIALFLASH/BACKUPCONFIG
MENU| ▼Update
SUB MENU| ▼Factry Default

CONFIRM

▼▲◀▶ Joystick navigation|
---|---
Press Enter 1 time
VPress Enter Scroll Down|
Press Cancel to return to Previous Menu|
MENU| ▼ Update
---|---
RV| ▼Time

Hour| 0| (0 THROUGH 23)
MINUTE| Ⅱ| (0 THROUGH 59)
Day| Ⅰ| (1 THROUGH 31)
MoNTH| Ⅰ| (1 THROUGH 12)
YEAR| 2000| (1900 THROUGH 2155)
MENU| ▼ Update
SR| ▼Export Trend
USB| MISSING|

CAROMA 300069W Livewell D Shape Family Toilet Seat - FIGURE
7

MENU ▼ Details
SUB MENU OCC
OccMobe EXTERNAL
oce UNOC-CUPIED
OpROCC UNOC-CUPIED
OCcSRe LOCAL INPUT
TEMPOCC DISABLE
TEMPOCCTIM-EOUT 120
OFF DURUNOCC No
OPTSTRT-EN No
EARLYSTRTPE-RIOD 60MIN
USEOCCSCHED YES
PREOCCPURGEENA
MENU ▼ Details
--- ---
SUB MENU OCC
PPREOCCCPURGE TIME 60
PREOCCUP-SAT_SP 90
PREOCCLOW- SAT_SP 45
MENU ▼Details
--- ---
SUB MENU ▼Clg
SUB MENU ▼Setup
CLG-EN YES
#CLGSTGS 1
#REFRIGSYS 4
CLGOCC-SP 72F
CLGUNOCC-SP 85F
C1-EN YES
C2-EN YES
C3-EN YES
C4-EN YES
MINRTCOOLSTG 3MIN
CLGADAFTUNEN YES
LOWAMB-EN NO
LOWAMBIOON5OFFSP 45 F
LEADLAG-EN NO
CLGOATCUTOUT-EN YES
CLGOATCUTOUT 45 F
SATCOOLLIMIT-EN YES
SATCOOLLIMIT-SP 45 F
HGP-INST NO
FREEZE-SP 26.0 F
PMPOUT-EN DISABLE
LOWAMBFANPRERUN-COOL. 60SEC

CLGMANUALTUNE
LOWAMBSTART
4PIPEENA| NO
NO
NO| (COOLING MANUAL TUNING)
(LOW AMBIENT START)
(4 PIPE SPLIT ENABLE)
MENU| ▼ Details
---|---
SUB MENU| ▼ CIg
SUB MENU| ▼ Service
SUB MENU| Unit
STGCLGCMD| 0%| (STAGED COOLING COMMAND)
OPRCVCLG-SP| 72 F| (CV COOLING SET PT IN USE)
CLG-S| OFF-IDLE| (COOLING STATUS)
OPROAT| 0,73. F| (OPERATIONAL OUTDOOR AIR TEMPERATURE)
OPRST| 0,73. F| (SPACE TEMPERATURE IN USE)
RAT| 73 F| (UCB RAT THERMISTOR INPUT)
ECON-FREE| NO| (FREE COOLING AVAILABILITY)
SAT| 0,61. F| (UCB SAT THERMISTOR INPUT)
Y I -TSTAT| OFF| (24VAC INPUT TO YI TERM)
Y2-TSTAT| OFF| (24VAC INPUT TO Y2 TERM)
Y3-TSTAT| OFF| (24VAC INPUT TO Y3 TERM)
Y4-TSTAT| OFF| (24VAC INPUT TO Y4 TERM)
CN-FAN| OFF| (CN -FAN 24 VAC OUTPUT)
CF2| OFF| (CF2 24 VAC OUTPUT)
MENU| ▼ Details
---|---
SUB MENU| ▼ CIg
SUB MENU| ▼ Service
SUB MENU| ▼ Stage1
CI-S| OFF – IDLE| (COMPRESSOR STAGE STATUS)
CI| OFF| (CI 24VACOUTPUTSTATUS)
CIONTMR| 180 SEC| (CIMINRUNTIMEREMAIN)
CIASCDTMR| 300 SEC| (CI ASC TIMEREMAIN)
CIRUNTIM| . 0 HR| (CI OUTPTACCUMRUNTIME)
ICI-El| ? %| (EFFICIENCY INDEX I)
CI-CI| ? F| (CAPACITY INDEX I)
CI -CONDTEMPOVRAMB| (CONDENSING TEMP OVER AMBIENT I)
C I – EVA PTE M PVA LUE| (EVAP TEMP VALUE CIRCUIT I)
CLGCKTTESTS- I| (COOLING CIRCUIT TEST STATUS)
CI-SUPERHEAT| (SUPERHEAT)
CI-SUBCOOL| (SuecooLING)
MENU| ▼ Details
---|---
SUB MENU| ▼ CIg
SUB MENU| ▼ Service
SUB MENU| ▼ VStage 2
C2-S| OFF – IDLE| (COMPRESSOR STAGE STATUS)
C2| OFF| (C2 24VAC OUTPUT STATUS)
MENU| ▼ Details
---|---
SUB MENU| ▼ CIg
SUB MENU| ▼ Service
SUB MENU| ▼ Stage 2
C2ONTMR| 180 SEC| (02 MINRUNTIMEREMAIN)
C2ASCDTMR| 300 SEC| (02ASC TIMEREMAIN)
C2RUNTIM| 0 HR| (C2OUTPTACCUMRUNTIME)
02-EI| ? %| (EFFICIENCY INDEX 2)
C2-CI| ? F| (CAPACITY INDEX 2)
C2-CONDTEMPOVRAMB| (CONDENSING TEMP OVER AMBIENT 2)
C2-EVAPTEMPVALUE| (EVAP TEMP VALUE CIRCUIT 2)
CLGCKTTESTS-I| (COOLING CIRCUIT TEST STATUS)
CI-SUPERHEAT| (SUPERHEAT)
CI-SUBCOOL| (SUBCOOLING)
MENU| ▼ Details
---|---
SUB MENU| CIg
SUB MENU| Service
SUB MENU| Stage 3 **
C3-S| OFF – IDLE| (COMPRESSOR STAGE STATUS)
C3| OFF| (03 24VACOUTPUTSTATUS)
C3ONTMR| 180 SEC| (C3MINRUNTIMEREMAIN)
C3ASCDMR| 300 SEC| (C3 ASC TIMEREMAIN)
C3RUNTIM| .0 HR| (03 OUTPTACCUMRUNTIME)
03-E1| ? %| (EFFICIENCY INDEX 3)
03-C1| ? F| (CAPACITY INDEX 3)
C3-CONDTEMPOVRAMB| (CONDENSING TEMP OVER AMBIENT 3)
C3-EVAPTEMPVALUE| (EVAP TEMP VALUE CIRCUIT 3)
CLGCKTTESTS-I| (COOLING CIRCUIT TEST STATUS)
CI-SUPERHEAT| (SUPERHEAT)
CI-SUBCOOL| (SUBCOOLING)
MENU| ▼ Details
---|---
SUB MENU| ▼ CIg
SUB MENU| ▼ Service
SUB MENU| ▼ Stage 3
C4-S| OFF – IDLE| (COMPRESSOR STAGE STATUS)
C4| OFF| (04 24VACOUTPUTSTATUS)
C4ONTMR| 180 SEC| (C4MINRUNTIMEREMAIN)
C4ASCDMR| 300 SEC| (C4 ASC TIMEREMAIN)
C4RUNTIM| .0 HR| (C4 OUTPTACCUMRUNTIME)
06-E1| ? %| (EFFICIENCY INDEX 4)
04-01| ? F| (CAPACITY INDEX 4)
MENU| ▼ Details
---|---
SUB MENU| ▼ CIg
SUB MENU| ▼ Service
SUB MENU| ▼ Stage 4
C4-CONDTEMPOVRAMB| (CONDENSING TEMP OVER AMBIENT 4)
C4-EVAPTEMPVALUE| (EVAP TEMP VALUE CIRCUIT 4)
CLGCKTTESTS- I| (COOLING CIRCUIT TEST STATUS)
CI-SUPERHEAT| (SUPERHEAT)
CI-SUBCOOL| (SUBCOOLING)
MENU| ▼ Details
---|---
SUB MENU| ▼ CIg
SUB MENU| ▼ Sensors
ECI| 42 F| (ECI THERMISTOR INPUT)
CCI| 96 F| (CCI THERMISTOR INPUT)
SLP-I| | (SUCTION PRESSURE I)
LLP-I| | (LIQUID PRESSURE I)
SLT-I| | (SUCTION TEMPERATURE I)
LLT-I| | (LIQUID TEMPERATURE I)
EC2| 42 F| (EC2 THERMISTOR INPUT)
CC2| 96 F| (CC2 THERMISTOR INPUT)
SLP-2| | (SUCTION PRESSURE 2)
LLP-2| | (LIQUID PRESSURE 2)
SLT-2| | (SUCTION TEMPERATURE 2)
LLT-2| | (LIQUID TEMPERATURE 2)
EC3| 42 F| (EC3 THERMISTOR INPUT)
CC3| 96 F| (CC3 THERMISTOR INPUT)
SLP-3| | (SUCTION PRESSURE 3)
LLP-3| | (LIQUID PRESSURE 3)
SLT-3| | (SUCTION TEMPERATURE 3)
LLT-3| | (LIQUID TEMPERATURE 3)
EC4| 42 F| (EC4 THERMISTOR INPUT)
CC4| 96 F| (CC4 THERMISTOR INPUT)
SLP-4| | (SUCTION PRESSURE 4)
LLP-4| | (LIQUID PRESSURE 4)
SLT-4| | (SUCTION TEMPERATURE 4)
LLT-4| | (LIQUID TEMPERATURE 4)
MENU| ▼ Details
---|---
SUB MENU| ▼ CIg
SUB MENU| ▼ Safetiess
HPSI NORMAL| (HPSI 24VAC INPUT STATUS)
HPSI-LO NORMAL| (HIPRESSI SWITCH STATUS)
MENU| ▼ Details
---|---
SUB MENU| ▼ CIg
SUB MENU| ▼ Safeties
LPSI| NORMAL| (LPSI 24VAC INPUT STATUS)
LPSI-LO| NORMAL| (LOPRESSI SWITCH STATUS)
FSI| NORMAL| (FREEZE PROTECTI STATUS)
FSI-LO| NORMAL| (FREEZE PROTECTI STATUS)
HPS2| NORMAL| (HPS2 24vAc INPUT STATUS)
HPS2-LO| NORMAL| (HIPRESS2 SWITCH STATUS)
LPS2| NORMAL| (LPS2 24VAC INPUT STATUS)
LPS2-LO| NORMAL| (LOPRESS2 SWITCH STATUS)
FS2| NORMAL| (FREEZE PROTECT2 STATUS)
FS2-LO| NORMAL| (FREEZE PROTECT2 STATUS)
HPS3| NORMAL| (HPS3 24VAC INPUT STATUS)
HPS3-LO| NORMAL| (HIPRESS3 SWITCH STATUS)
LPS3| NORMAL| (LPS3 34vAc INPUT STATUS)
LPS3-LO| NORMAL| (LOPRESS3 SWITCH STATUS)
FS3| NORMAL| (FREEZE PROTECT3 STATUS)
FS3-LO| NORMAL| (FREEZE PROTECT3 STATUS)
HPS4| NORMAL| (HPS4 44vAc INPUT STATUS)
HPS4-LO| NORMAL| (HIPRESS4 SWITCH STATUS)
LPS4| NORMAL| (LPS4 44vAc INPUT STATUS)
LPS4-LO| NORMAL| (LOPRESS4 SWITCH STATUS)
FS4| NORMAL| (FREEZE PROTECT4 STATUS)
FS4-LO| NORMAL| (FREEZE PROTECTS STATUS)
MENU| ▼ Details
---|---
SUB MENU| ▼ Clg
SUB MENU| ▼ Misc*
MAXTEMPHUMS- POFF| 3.0 F| (MAXIMUM TEMPERATURE / HUMIDITY SETPOINT OFFSET)
TEMPHUM-SP| 50% H| (
EFFECTSOPRCLG-SP)
TEMPHUMC-TRL-EN| NO| (CNTRLOPERENABLE)
OPRSH| 49.6 % H| (SPACE HUMIDITY IN USE)
CLGOCC-SP| 72 F| (CV – OCC COOLING SETPOINT)
ORRCVCLG-SP| 72 F| (CV – OPERATING COOL SET-POINT)
TEMPHUMVALP-ERDEGOFF| 5 % H| (TEMPERATURE / HUMIDITY VALUE PER DEGREE OFFSET)

Legend

DEFAULT SETTINGS IN RED BLUE = UCB CONDITIONAL PARAMETER
TAN = ECONOMIZER BOARD PRESENCE DKGREEN = ECONOMIZER BOARD PRESENCE + ANOTHER

CONDITION
MENU| ▼Details
---|---
SUB MENU| ▼ Htg
SUB MENU| ▼ Setup
HTG-EN| YES| (HEATING OPER ENABLED)

HTGSTGS

HT6-TYPE| I
STAGED| (# OF HEATING STAGES)
(HEATINGCONTROLMETHOD)
CVHTGOCC-SP| 68 F| (CV – OCC HEATING SET- POINT)
CVHTGUNOCC-SP| 60 F| (CV – UNOCCC HEATING SETPOINT)
HTGADAPTUNEN| YES| (HEATING AUTO TUNE ENABLE)
SATHTGLIMIT-EN| YES| (SA HTGLIMITENABLED)
SATHTGLIMIT-SP| 135 F| (SA HTGLIMITSETPT)
HTGOATCUTOUT-SP| 75F| (OUTDOOR AIR TEMP HEATING CUTOUT SETPOINT)

GASVLVS| O| (#HTPMPSTGS = 0)

LIMSWTCHS| I| (#HTPMPSTGS = 0)

LL_ENABLE| DISABLE| (LOW LIMIT ENABLE)
LL_UPSAT_SP| 80 F| (LOW LIMIT UPPER SAT SETROINT)
LL_LOWSAT_SP| 80 F| (LOW LIMIT LOWER SAT SETPOINT)
HTGMANUALTUNE| NO| (HEATING MANUAL TUNING)
MENU| ▼Details
SUB MENU| ▼Htg
SUB MENU| ▼Service
STGHTGCMD| 0%| (STAGED HEATING COMMAND)
CVOPRHTG-SP| 68 F| (CV – OPERATING HEAT SETPOINT)
HT6-S| OFF-IDLE| (HEATING STATUS)
OPROAT| 73.0 F| (OPERATIONAL OUTDOOR AIR TEMPERATURE)
OPRST| 73.0 F| (SPACE TEMPERATURE IN USE)
RAT| 70.4 F| (UCB RAT THERMISTORINPUT)
W1-TSTAT| OFF| (2LVAC INPUT TO WI TERM)
W2-TSTAT| OFF| (2LVAC INPUT TO W2 TERM)
W3-TSTAT| OFF| (2LVAC INPUT TO W3 TERM)
G-TSTAT| OFF| (2LVAC INPUT TO G TERM)
HI-S| OFF-IDLE| (HEATING STAGE STATUS)
HI| OFF| (IST STG HEAT OUTPUT STATUS)
HIONTHR| 0 SEC| (RERANIRRINTINE)
HIASCDTMR| 0 SEC| (REMAIN ASCD TiME)
HIRUNTIM| .0 HR| (ACCUM HI RUNTIME)
MENU| Details
---|---
SUB MENU| ▼Htg
SUB MENU| ▼Service
H2| OFF| (2ND STG HEATINGOUTPUTSATUS)
H2-S| OFF-IDLE| (HEATING STAGE STATUS)
H20NTMR| 0 SEC| (REMAIN MIN RUNTIME)
H2ASCDTMR| 0 SEC| (REMAIN ASCDTIME)
H2RUNTIM| 0 HR| (ACCUM H2 RUNTIME)
H3| OFF| (3RD STG HEATINGOUTPUTSATUS)
H3-S| OFF-IDLE| (HEATING STAGE STATUS)
H3ONTMR| 0 SEC| (REMAIN MIN RUNTIME)
H3ASCDTMR| 0 SEC| (REMAIN ASCDTIME)
H3RUNTIM| 0 HR| (ACCUM H3 RUNTIME)
MENU| ▼Details
SUB MENU| ▼Htg
SUB MENU| ▼Safeties
LIMIT| NORMAL| (LIMIT 24VAC INPUT STATUS)
LMITLO| NORMAL| (HEAT LIMIT STATUS)
LIM2| NORMAL| (LIMIT 24VAC INPUT STATUS)
LIM2LO| NORMAL| (HEAT LIMIT STATUS)
LIM3| NORMAL| (LIMIT 24VAC INPUT STATUS)
LIM3LO| NORMAL| (HEAT LIMIT STATUS)
GV2| OFF| (GV2 PIN 24VAC INPUT STATUS)
GV3| OFF| (GV3,4 PIN 24VAC INPUT STATUS)
MENU| ▼Details
SUB MENU| ▼Htg
SUB MENU| ▼Prop
SUB MENU| Setup
HYDHISA-SP| 120 F| (HYD HI SAT SETPT)
HYDH2SA-SP| 150 F| (HYD H2 SAT SETPT)
SAT TEMPHYDHT-EN| NO| NO(HYDHTGSA TEMPER)
SAT TEMPHYDHT-SP| 40| (HYD HEAT TEMP SP)
HYDREVERSE| NO| (MODHT 2-10VDCACTION)
MENU| ▼Details
SUB MENU| ▼Htg
SUB MENU| ▼Prop
SUB MENU| ▼Service
CVHTGOCC-SP| 68 F| (CV OCC HEATING SET POINT)
MENU| ▼Details
---|---
SUB MENU| ▼Htg
SUB MENU| ▼Prop
SUB MENU| ▼Service
CVHTGUNOCC-SP| 60 F| (CV_UNOCC COOLING SET POINT)
CVOPRHTG-SP| 68 F| (CV_HEATING SET PT IN USE)
VAVOPRHTG-SP| 68F| (VAV_OPERATING HEAT SETPOINT)
OPR ST| 73.0 F| (SPACE TEMPERATURE IN USE)
SAT| (60.7 F)| (S A TEMP THERMISTER INPUT)
W1-TSTAT| OFF| (24VAC INPUT TO WI TERM)
W2-TSTAT| OFF| (2LVAC INPUT TO W2 TERM)
HWV| 0%| (HWV VDC OUTPUT)
HYDREVERSE| NO| (MODHT 2-10VDCACTION)
FSHW| NORMAL| ( )
MENU| ▼Details
SUB MENU| ▼Fan
SUB MENU| Setup
FANCTL-TYPE| SINGLE SPEED| (ID BLWR/UNIT OP MODE)
FANON OCC| YES| (CV CONSTANT FAN IN OCCUPIED MODE)
FANONDLYHEAT| 30SEC| (HEATFANONDELAY)
FANOFFDLYHEAT| 60SEC| (HEATFANOFFDELAY)
FANOFFSTARTHE-AT| YES| (FANOFF ATHEATSTART)
FANONDLYCOOL| 0 SEC| (COOLFANONDELAY)
FANOFFDLYCOOL| 30SEC| (COOLFANOFFDELAY)
Fan ONLY-0% CMD| 50%| (CV IS FAN ONLY)
1CLGST6-% CMD| 70%| (CV IS I ST6 COOL)
2CLGST6-% CMD| 80%| (CV IS 2 ST6 COOL)
3CLGSTG-%CMDT| 90%| (CV IS 3 STG COOL)
4CLGSTG-% CMD| 100%| (CV IS 4 ST6 COOL)
1HT6ST6-%CMD| 100%| (OCCUPIED: ONE STAGE OF HEAT% COMMAND)
2HT6STG-%CMD| 100%| (OCCUPIED: TWO STAGE OF HEAT % COMMAND)
SHTGSTG-%CMP| 100%| (OCCUPIED: THREE STAGE OF HEAT % COMMAND)
LOWAMBFANPRE-RUNCOOL| 60 SEC|
APSSETUP| NONE| (AR PROVING SWITCH OPERATION)
DFS| NORMAL| (DFS 2LVAC INPUT STATUS)
MENU| ▼Details
---|---
SUB MENU| Fan
SUB MENU| ▼Service
G-TSTAT| OFF| (24VAC INPUT TO G TERM)
FAN-S| OFF-IDLE| (FAN STATUS)
FAN| OFF| (FAN 24VAC OUTPUT STATUS)
FAN -RT| .0 HR| (ACCUMULATED FAN RUNTIME)
OPRFANREQ| OFF| (OPERATING FAN REQUEST)
FANREQSRC| LOCAL INPUT| (FAN REQUEST SOURCE)
APS| OFF| (APS INPUT STATUS)
FANOVERLOAD| NORMAL| (FANOVRINPTSTATUS)
FANV FD FLT| NORMAL| (FLT24VACINPTSTATUS)
MENU| ▼Details
SUB MENU| ▼Econ
SUB MENU| Setup
ECON-EN| YES| (ECONOFREECOOLINGENABLE)
---|---|---
ECON-MINPOS| 10%| (ECONOMIZER MINIMUM POSITION SETPOINT)
LOWSPEEDFAN-MINPOS| 25%| (OCCLOFANPOS)
LOWAMB-MINPOS| 0%V| (OCCLOAMBMINPOS)
LOWAMB-SP| 0 F| (LOAMBMINPOSSSETPT)
FREECLG-SEL| AUTO| (FRECLGCHNGOVRMETHOD)
FREECLG-MODE| DRY BULB| (CHNGOVERMODE)
ALLCOMPOFF-ECON| N0| (ALL COMPRESSORS OFF IN FREE COOLING)
ECONOAT-SpEN| 55 F| (DRYBLBCHGOVRSETPT)
ECONOAENTH-SP| 27 B/#| (ENTHCNGOvRSETPT)
DVENT-MODE| DISABLED| (DMAND VENT MODE SELECT)
DVENTMAXECONPOS| 50%| (MAX ECON POSITION)
DVENTIAQ-SP| 1000PPM| (DEMAND VENT IAQ SETPT)
DVENTDIFF-SP| 600ppm| (IAQ-OAQ DIFFERENCESETPT)
IAQRANGE| 2000pipm| (ID SETPT W/CO2 SENSOR INST)
OAQRANGE| 200OPPM| (OD SETPT W/CO2 SENSOR INST)
ECONLOAD-EN| NO| (ECONLOADINGENABLED)
MOAFLOW-SP| IOCFM| (FRESH AIR INTAKE SET-POINT)
MOA-RANGE| 10000CFM| (FRESH AIR INTAKE MAX SENSOR RANGE)
ECONMECHSTP| OPTION B| (ECON MECH SETUP)
ECONFLTDETECTEN| DISABLE| (ECON FAULT DETECTION EN)
MENU| ▼Details
---|---
SUB MENU| ▼Econ
SUB MENU| ▼Service
CLG-S| OFF-IDLE| (COOLING STATUS)
ECON-S| DISABLED|
ECON-FREE| NO| (FREECOOLING AVAILABLE)
ECON| 0%| (ECON 2-10VDC OUTPUT STATUS)
SAT| 60.7. F| (UCB SAT THERMISTORINPUT)
OPROAT| 73.0 F| (OPERATIONAL OUTDOOR AIR TEMPERATURE)
OA-ENTH| 20 B/#| (CALCOA ENTHALPYINPUT)
RA-ENTH| 20B/#| (RA ENTHALPY INPUT)
OPRIAQ| 477PPM| (INDOOR AIR QUALITY INPUT)
OPROAQ| 990PPM| (OUTDOORAIRQUALITY IN USE)
FR AIR| 7940CFM| (FRESH AIR INTAKE ENABLE)
ECONDAMRPOS| 38| (Al-IN 0-10VDC INPUT)
ECONALRMDLY| 600 SEC| (FDD ECON ALARM DELAY)
ECONPOSERR| 8%| (FDD ECON DAMPER ALLOW ERROR)
ECONMINERR| 5%| (FDD DAMPER MIN POS TOLERANCE)
MENU| ▼Details
---|---
SUB MENU| ▼Dvent
ECON-EN| YES| (ECONOFREECOOLINGENABLE)
DVENT-MODE| DISABLED| (DEMANDVENTIMODE)
DVENTMAXECONPOS| 50%| (IAQ EcoN-MAxPos)
DVENTIAQ-SP| 1000PPm| (OCCIAQECONOPERSETPT)
DVENTDIFF-SP| 600PPm| (OCC DIFF IAQ/OAQ SETPT)
IAQRANGE| 2000PPm| (PPm@l0vDclAQ OUTPUT)
OAQRANGE| 2000PPM| (PPM@IOVDCOAQ OUTPUT)
OPRIAQ| 477PPM| (IAQ 0-IOVDCINPUT IN USE)
OPROAQ| 990PPM| (OUTDOORAIRQUALITY IN USE)
ECONDAMPPOS| 38| (Al-IN 0-IOVDC INPUT)
MENU| ▼Details
---|---
SUB MENU| ▼AirMonStation
ECON-EN| YES| (ECONOFREECOOLINGENABLE)
FRAIR-EN| DISABLE| (FRESH AIR INTAKE ENABLE)
MOAFLOW-SP| IOCFM| (FRESH AIR INTAKE SETPOINT)
MOA-RANGE| 10000CFM| (FRESH AIR INTAKE MAX SENSOR RANGE)
FR AIR| 7953CFM| (FRESH AIR INTAKE ENABLE)
ECONDAMPPOS| 38| (Al-IN 0-10VOC INPUT)
CONTROL| 40CFM| (FRESH AIR RANGE)
MENU| ▼Details
---|---
SUB MENU| ▼PowerEx
SUB MENU| Setup
EXFTYPE| NONE| (PWREXFANMODESELECTION)
ECONDMPPOSFANON| 60%| (FANONPOSITION)
ECONDMPPOSFANOFF| 20%| (FANOFFPOSITION)
EXDMPPOSFANON| 80%| (FANONPOSMON)
EXDMPPOSFANOFF| 20%| (FANOFFPOSN-ION)
BLDG-SP| 100″/A| (EXDMPRBLDGPRESSETPT)
DCTPRS| | (DUCT STATIC PRESSURE)
MENU| ▼Details
---|---
SUB MENU| ▼PowerEx
SUB MENU| ▼Service
E XF-S| OFF|
EXFAN| OFF| (EX-FAN 24VACOUTPUTSTATUS)
BLDGPRES| .164″/W| (BLDGPRES 0-5VDC INPUT)
EAD- 0| 0%| (EXVFD2-10VDCOUTPTSTATUS)
ExFANVFD| 0%| (EX VFD2-10VDC OUTPUT)
EXFAN-RUNTIME| .0 HR| (24VACOUTPUTACCRUNTIME)
ExFANVFDFLT| NORMAL| (VFD FLT24VACINPUT)
MENU| ▼Details
---|---
SUB MENU| ▼FanVFD
SUB MENU| ▼Setup
FANCTL-TYPE| SINGLE SPEED| (UNITOPMODE)
DCTPRS-SP| 1.50″/w| (VAV SUPPLYDUCTPRESS SETPOINT)
DCTSHUTDOWNSP| 4.5″/W| (DUCTPRESSLIMIT)
SATUP-SP| 60 Fc| (VAV OCC UPPRCOOLING SAT SETPT)
SATLO-SP| 55 F| (VAV OCC LOWR COOLING SAT SETPT)
SATRST-SP| 72 F| (VAV OCC COOL SAT RESET SETPT)
VAVCLGUNOCC-SP| 85 F| (FANCTL-TYPE = VARIABLE SPEED)
MORNW-EN| NO| (VAVMORNWRMUPENABLE)
MORNWRAT-SP| 71 F| (MORNWRMUPRA SETPT)
HTGOcc-EN| YES| (VAV OCC HEATING ENABLED)
VAVHTGOcc-SP| 85 F| (VAV OCC HEATING SETPOINT)
HTGUNOCC-EN| NO| (VAV UNOCC HEATING ENABLED)
VAVHTGUNOCC-SP| 60 F| (VAV UNOCC HTG SETPOINT)
MORNC-EN| NO| (MORNING COOLDOWN ENABLED)
MORNCRAT-SP| 74 F| (MORNING COOLDOWN SP)
MENU| ▼Details
---|---
SUB MENU| ▼FanVFD
SUB MENU| ▼Setup
OPTSTRT-EN| NO| (OPTIMAL START ENABLED)
EARLYSTRTPERIOD| 60MIN| (EARLY START PERIOD)
USEOCCSCHED| YES| (USE OCCUPANCY SCHEDULE)
LPSI| NORMAL| (LPSI 24VAC INPUT STATUS)
LPS2| NORMAL| (LPS2 24VAC INPUT STATUS)
TIME| |
TIME| |
HTGOCC-EN| | (VAV OCC HEATING ENABLED)
MENU| ▼Details
---|---
SUB MENU| ▼FanVFD
SUB MENU| ▼Service
FANVFD| 0%| (VFD 2-10 VDC OUTPUT)
DCTPRS| 1.50″/W| (DCT PRS 0-5VDCINPUT)
DCTPRS-SP| 1.5″/W| (DUCTPRESSLIMIT)
OPRVAVCLG-SP| 55 F| (VAV COOLING SAT SETPT IN USE)
SAT| 60.7 F| (UCB SAT THERMISTORINPUT)
STGCLGCMD| 0%| (STAGED COOLING COMMAND)
CLG-S| YES| (COOLING STATUS)
ECON-FREE| NO| (FREE COOLING AVAILABILITY)
C1| OFF| (UCB CI 24 VAC OUTPUT STATUS)
C2| OFF| (DEMAND VENT SET POINT)
C3| OFF| (4STG C3 24 VAC OUTPUT STATUS)
C4| OFF| (4STG C4 24 VAC OUTPUT STATUS)
VAVOPRHTG-SP| 68 F| (VAV HEATING SETPT IN USE)
STGHTGCMD| 0%| (STAGED HEATING COMMAND)
OPRST| 73.0 F| (SPACE TEMPERATURE IN USE)
HTG-S| OFFIDLE| (HEATING STATUS)
H1| OFF| (CV IS 1 STG HEAT)
H2| OFF| (CV IS 2 STG HEAT)
H3| OFF| (CV IS 3 STG HEAT)
VAV Box| OFF| (VAV BOX)
MENU| ▼Details
---|---
SUB MENU| ▼SZVAV
SUB MENU| ▼Setup
SZVAVEN| NO| (SINGLE ZONE VAV ENABLED)
SZVAVMINFANSPD| 66%| (MINIMUM FAN SPEED)
SZVAVCLGOcc-Sp| 72 F| (SZ VAV Occ CLG SP)
SZVAVLGUNocc-Sp| 85 F| (SZ VAV UNOCC CLG SP)
VAVHTGOcc-SP| 68 F| (VAV – OCC HEATING SETPOINT)
VAVHTGUNOCC-SP| 60 F| (VAV UNOCC HEATING SETPT)
DATMAxHTGSP| 105 F| (DAT HEATING MAX SP)
DATSATSP| 70 F| (DAT SATISFIED SP)
DATCLGMINSP| 54c| (DAT COOLING MIN SP)
MENU| ▼Details
---|---
SUB MENU| ▼SZVAV
SUB MENU| ▼Service
OPRSZVAVCLG-SP| 72 F| (SZ VAV OPERATING CLG SP)
SZVAVCLGLD| 0%| (SZ VAV COOLING LOAD)
SZVAVHTGLD|  | (SZ VAV HEATING LOAD)
OPRVAVCLG-SP| 60 F| (VAV OPERATING COOL SETPOINT)
OPRST| 73. F| (SPACE TEMPERATURE IN USE)
SAT| 0,61. F| (SAT THERMISTOR INPUT)
FANVFD| 0%| (VFD 2-10VDC OUTPUT STATUS)
ECON| 0%| (ECON 2-10 VDC OUTPUT STATUS)
C1| OFF| (1ST COOL 24 VAC OUTPUT)
C2| OFF| (2ND+ COOL 24 VAC OUTPUT)
C3| OFF| (3RD+ COOL 24 VAC OUTPUT)
C4| OFF| (4TH+ COOL 24 VAC OUTPUT)
MENU| ▼Details
SUB MENU| ▼ HGR
SUB MENU| Setup
HGR-EN| NO| (HOT GAS REHEAT ENABLED)
HGRALT-EN| NO| (HGR ALTERNATE ENABLED)
HGRALTWRITE| NO| (HGR ALTERNATE WRITEABLE)
HGRHUM-SP| 60DEGF| (HOT GAS REHEAT HUMIDIDTY SETPOINT)
HGRUNOCC-EN|  | (HGR UNOCC ENABLED)
HGRUNOCCHUM-SP| 70DEGF| (HGR UNOCC HUM SP)
HGR-DIFF|  | (HGR HUMIDITY SETPOINT DIFFERENTIAL)
MODE|  | (AUX MODE)
MENU| Details
---|---
SUB MENU| HGR
MENU| Service **
STGCLGCMD| 0%| (STAGED COOLING COMMAND)
OPRCVCLG-SD| 72 F| (CV COOLING SET PT IN USE)
OPRST| 0,73. F| (SPACE TEMPERATURE IN USE)
HGRHum-Sp| 60-| (HOT GAS REHEAT HUMIDIDTY SETPOINT)
OPRSH| 4.9.6 %H| (SPACE HUMIDITY IN USE)
HGR-S| Opp-DisABLED| (HGR STATUS)
HGR| OFF| (HOT GAS REHEAT)
CI| OFF| (CI 24VACOUTPUTSTATUS)
C2| OFF| (UCB CI 24. VAC OUTPUT STATUS)
C3| OFF| (C3 24VACOUTPUTSTATUS)
C4| OFF| (4STG C4 24. VAC OUTPUT STATUS)
RAH| (49.6 %H)| (R A HUMIDITY 0-10 VDC INPUT)
MENU|
Details
---|---
SUB MENU|
Heat Pmp **

HTPUMPSTGS| 0| (# OF HEAT PUMPS)

TESTDEFROSTENABLE|  | (TEST DEFROST ENABLE)
COMPDELAYENABLE| No| (COMPRESSOR DELAY ENABLE)
DEFROSTCURVESEL| CURVE I| (DEFROST CURVE SELECT)
REVVLV| OFF| (REVERSING VALVE)
AUXHTG| OFF| (AUXILIARY HEAT)
MODE| COOLING| (MODE)
MENU| ▼ Details
---|---
SUB MENU| ERV-En **
ERV-EN|  | (EcoNapwREXINTRGRATIONWI ERV)
ERVUNoccFAN-EN|  | (ERV UNOCCUPIED FAN ENABLED)
FANCTL-TYPE| SINGLE SPEED| (UNITOPMODE)
FAN| OFF| (UCB FAN 24 VAC OUTPUT STATUS)
ECON-FREE| No| (FREECOOLING AVAILABLE)
EXFAN| OFF| (EX-FAN 24 VAC OUTPUT)
MENU| ▼ Details
---|---
SUB MENU|
T24LoadShed **
LOADSHEDRATELIM| 0.066| (RATE LIMITER)
LOADSHEDADJUST| 4.0 F| (LOAD SHED ADJUST)
LOADSHEDENABLE| No| (LOAD SHED ENABLE)

CAROMA 300069W Livewell D Shape Family Toilet Seat - FIGURE
8

MENU ▼ Self Test ****
START (BEGINS THE SELF TEST SEQUENCE)
PAUSE (CAUSES THE SEQUENCE TO HOLD ANY OUTPUTS ON FOR 10 MINUTES.)
CANCEL (STOPS THE SELF TEST SEQUENCER AND RETURNS THE SEC TO NORMAL

OPERATION.)
TESTSTATUS| (DISPLAYS CURRENT STATE OF THE SELF TEST SEQUENCER)
RESET| (ERASES THE PREVIOUS SELF TEST RESULTS AND PREPARES THE SELF TEST SEQUENCER FOR ANOTHER TEST RUN)

CAROMA 300069W Livewell D Shape Family Toilet Seat - FIGURE
9

MENU ▼ View Result ****
FANRESULT PASS-FAIL
CIRESULT PASS-FAIL-WARNING
C2RESULT PASS-FAIL-WARNING
C3RESULT PASS-FAIL-WARNING
C4RESULT PASS-FAIL-WARNING
HIRESULT PASS-FAIL-WARNING
H2 RESULT PASS-FAIL-WARNING
H3RESULT PASS-FAIL-WARNING
ECONRESULT PASS-FAIL
EXHRESULT WARNING-PASS

1136326-USG-G-0119
Supersedes: 1136326-USG-F-1117
Subject to change without notice. Printed in U.S.A.
Copyright
® 2018 by Johnson Controls, Inc. All rights reserved
York International Corporation
5005 York Drive
Norman, OK 73069

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Johnson Controls User Manuals

Related Manuals