Casper LC Series Air Conditioner User Guide

June 11, 2024
CASPER

Casper LC Series Air Conditioner

Casper-LC-Series-Air-Conditioner-product-img

ERROR CODE LC MODEL

LC-09FS32-IM/OM

Error code Remark:★Light    o Flash   x OFF
Content Remark

__

__

__

E4

| __

When the indoor fan speed is lower than 200 rpm, the error code will display

|  | a.    There is something blocking

the indoor fan motor;

b.  The fan motor cord connects loosely;                             c. The

fan motor is a failure;

d. The indoor control board is a failure

__

__

__

EA

| the error code will display when the communication between the display board and the control board have in trouble|  | __

a. The connection between the display board and the control board is loose; b. The indoor control board is a failure.

c. The wiring of the display board is a failure.

E9(suitable for

some models))

| __

When there is a leak in the product, the error code will display

|  | a.            There is a leak in the indoor

b.          There is a leak in the outdoor

c.            There is a leak in the connecting pipe

Error code Remark: Light     o Flash x OFF
Content Remark

__

1

| The failure of the temperature sensor of the outdoor coil| __

Heat pump

| a.    The outdoor temperature sensor is loose;

b.    The outdoor temperature sensor is a failure;

c.     The indoor control board is a failure

__

__

33

| The failure of temperature sensor in an indoor room|  | a.    The indoor room temperature sensor is loose;

b.    The indoor room temperature sensor is failing;

c.     The indoor control board is a failure.

__

34

| The failure of the temperature sensor of the indoor coil temperature|  | a. The indoor coil temperature sensor is loose;

b.    The indoor coil temperature sensor is failing;

c.     The indoor control board is a failure.

---|---|---|---
38| Indoor EEPROM failure|  | a.    The EEPROM chip is loose;

b.    The indoor control board is a failure

__

__

39

| __

The indoor fan motor runs abnormally

|  | a.    There is something blocking the indoor fan motor;

b.  The fan motor cord connect loose;

c.  The fan motor is a failure;

d.  The indoor control board is a failure

__

41

| The failure for

Indoor grounding protective

|  | __

The indoor control board is a failure

__

__

__

__

__

42

| __

__

__

__

__

Overcooling protection

|  | a.     It is normally for protection When the indoor pipe temperature is below T<-1℃(- 7℃). The outdoor fan motor and compressor will stop running. When the Indoor pipe temperature is higher than -1(-7℃),the unit will restart normally

b.    The indoor coil temperature sensor is loose;

c.     The indoor coil temperature sensor is failing;

d.    The indoor control board is a failure.

__

__

__

__

__

__

43

| __

__

__

__

__

__

Overheating protection

|  | a.     It is normally for protection, When the indoor pipe temperature is between 53℃<T<63℃, the outdoor fan motor will stop running. When the indoor coil temperature is higher than 63℃, the error code will display. After the indoor pipe temperature is lower than 49℃, the air conditioner will restart normally.

b.    The indoor coil temperature sensor is loose;

c.     The indoor coil temperature sensor is failing;

d.    The indoor control board is a failure.

LC-12FS32-IM/OM

Casper-LC-Series-Air-Conditioner-fig-1 Casper-
LC-Series-Air-Conditioner-fig-2 Casper-
LC-Series-Air-Conditioner-fig-3 Casper-
LC-Series-Air-Conditioner-fig-4 Casper-
LC-Series-Air-Conditioner-fig-5 Casper-
LC-Series-Air-Conditioner-fig-6 Casper-
LC-Series-Air-Conditioner-fig-7 Casper-
LC-Series-Air-Conditioner-fig-8

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

CASPER User Manuals

Related Manuals