CAUTION: For safety and proper operation, read and follow instructions carefully before installation.
FIELD INSTALLABLE FLUORESCENT BATTERY PACK IS UNIVERSALLY COMPATIBLE WITH ALL BALLASTS OPERATING LAMP(S) IN THE LAMP COMPATIBILITY TABLE.
IMPORTANT NOTES:
Make sure that branch circuit feeds are derived from a common phase for both
normal lighting ballast and Battery Pack prior to installation. Notice: To
ensure proper grounding, mount unit only with metal cutting screws (not
provided). The Battery Pack can be used with a switched or unswitched (night)
circuit. When used with a switched fixture it is important to note that the
power to the Battery Pack must be provided by an unswitched circuit
IMPORTANT SAFEGUARDS
-
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
-
Before wiring to power supply, turn off electricity at fuse or circuit breaker.
-
To reduce the risk of electrical shock, disconnect AC power and unplug Test switch/pilot light connector Before servicing.
-
All servicing should be performed by qualified personnel.
-
Consult your local building code for approved wirin and installation.
-
Do not use standard product outdoors. This product is for use with indoor fixtures sealed or unsealed, except air handling heated outlets or hazardous location applications. Battery packs with DW option are UL Listed for installation (0-50°C ambient) in:
· Dry or damp locations, sealed or unsealed luminaires
· Wet Locations, only if installed in a sealed and/or gasketed wet location listed luminaire Note: DW option does not make the product suitable for mounting outside the fixture in wet location applications. -
The emergency ballast must be connected to an unswitched AC power source (120 or 277).
-
Do not mount near gas or electric heater.
-
Do not attempt to service the battery. A sealed nomaintenance battery is used that is not field replaceable. Contact manufacturer for service information. 10.Equipment should be mounted in location and at heights where it will not readily be subjected to tampering by unauthorized personnel.
-
The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
-
Do not use this equipment for other than intended use.
PARTS DESCRIPTION (FIG 1A & B)
- HOUSING
- MOUNTING HOLES or SLOTS
- TEST SWITCH/PILOT LIGHT (TS/PL)
- MOUNTING CLIP
- TS/PL CONNECTOR
- CHARGE INDICATOR STICKER
- LAMP SELECTOR (ORANGE) PS1400 ONLY
INSTALLATION
-
Inspect Battery Pack and make sure the Test Switch/Pilot Light Connector is not connected. If so, disconnect it before installation.
-
Position unit in fixture wireway and fasten securely through keyed slots or Mounting Holes or Slots . If necessary, drill holes and mount with metal cutting screws (not provided).
-
Refer to appropriate wiring diagram. Connect unit to ballast and lamp(s) and A.C. power leads as indicated in appropriate wiring diagram.
-
Drill or punch a 1/2 dia. hole in fixture wall or wireway
cover. -
Insert one side of TSPL into the hole from the back and snap in the other side. Slide mounting clip firmlyonto mounting post with the TSPL assembly secured in place.
-
Connect the Test Switch/Pilot Light Connector .
-
Apply continuous power to Battery Pack.
INSPECTION AND MAINTENANCE
NOTE: Emergency lighting systems should be tested as often as local codes require, or at least quarterly to insure that all components are operational. Perform all test required by local codes
-
Check equipment rating to be sure that fixture will receive proper line voltage.
-
Be sure pilot light is on. If pilot light does not operate, check to see that:
A. Test Switch/Pilot Light Connector is connected.
B. AC power is on.
C. Voltage on branch circuit to Battery Pack is rated at line voltage (120V or 277V). If no line voltage can be measured, locate problem in branch circuit and correct. -
Engage test switch. The pilot light should be off. One or two fluorescent lamps should be operating at a reduced light output.
LAMP COMPATIBILITY TABLE
LAMP TYPE| WATTAGE| PS300 (350-450 lumens)| PS600 (600-700
lumens)| PS1400 (1100-1400 lumens)
---|---|---|---|---
24” – 48” T5| 14-28| | | 1
24” – 48” HO T5| 24-54| | | 1
U-LAMP T8| 16-31| 1| 1,2| 1,2
24″-48″ T8| 17-32| 1| 1,2| 1,2
60″-96″ T8| 40-59| | 1| 1
96″ HO T8| 86| | 1| 1
CIRCLINE T9| 20-40| 1| 1| 1
U-LAMP T12| 34-40| 1| 1,2| 1,2
24″-48″ T12| 20-40| 1| 1,2| 1,2
60″-96″ T12| 50-75| | 1| 1
24″-48″ HOT12| 35-60| | 1| 1
60″-96″ HO T12| 70-110| | 1| 1
24″-48″ VHO T12| 74-115| | 1| 1
60″-96″ VHO T12| 135-215| | 1| 1
PL TWIN-TUBE (4-PIN)| 9-13| | | 1
PL QUAD-TUBE (4-PIN)| 13-26| | | 1,2
TRIPLE-TUBE (4-PIN)| 18 – 32| | | 1,2
TRIPLE-TUBE (4-PIN)| 42| | | 1
LONG COMPACT (4-PIN)| 18-40| 1| 1| 1
LONG COMPACT (4-PIN)| 50-55| | 1| 1
- Indicates one lamp operation in emergency mode
- Indicates two lamp operation in emergency mode
WIRING DIAGRAMS IMPORTANT NOTES: Before connecting TS/PL Connector or wiring unit to fixture, refer to INSTALLATION PROCEDURE and IMPORTANT SAFEGUARDS for safety information and mounting procedures.
LAMP SELECTOR (ORANGE) TABLE-PS1400 ONLY
LAMP DIAMETER| BASE TYPE| POWER (LENGTH)| NUMBERS OF
LAMPS EMERGENCY| ORANGE CONNECTOR
5/8”, 1″, 1-1/4″, 1-1/2″ (T5, T8, T10, T12)| SINGLE OR BIPIN| 14-24W (2’-4’)|
1| CLOSED
2| OPEN
5/8”, 1″, 1-1/4″,1-1/2″(T5, T8, T10, T12)| SINGLE OR BI PIN| 28-40W(2′-4′)| 1|
CLOSED
2| OPEN
40-215W(5′-8′)| 1| OPEN
LONG COMPACT| 4-PIN (G11)| 18-39W| 1| CLOSED
2| OPEN
40-55W| 1| OPEN
COMPACT| 4-PIN| 13 -26W (QUAD TUBE)| 1| CLOSED
2| OPEN
COMPACT| 4-PIN| 18 -26W TRT (TRIPLE TUBE)| 1| CLOSED
2| CLOSED
COMPACT| 4-PIN| 32W TRT (TRIPLE TUBE)| 12| CLOSEDOPEN
COMPACT| 4-PIN| 42W TRT (TRIPLE TUBE)| 1| OPEN
T5HO| SINGLE| 24-54W (2’-4’)| 1| OPEN
ONE LAMP RAPID START BALLAST
Documents / Resources
|
ACCUPRO PS300 Emergency Fluorescent Battery
Pack
[pdf] Instruction Manual
PS300, PS600, PS1400, PS300 Emergency Fluorescent Battery Pack, PS300,
Emergency Fluorescent Battery Pack, Fluorescent Battery Pack, Battery Pack
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>