BSLBATT BSL_8_2 8.2KWH Lithium ion Battery User Manual
- June 9, 2024
- BSLBATT
Table of Contents
BSL_8_2 8.2KWH Lithium ion Battery
User Manual 8.2KWH Lithium-ion battery
SAFETY GUIDELINES
Work or maintenance on the BSL battery should be carried out by qualified
personnel only.
Do not attempt to open or dismantle battery and/or cells.
The electrolyte contained in the battery cells is highly corrosive. In the
event of any damage to or leakage from the cells, treat contents with care, do
not allow contact with exposed skin or eyes. DO NOT INGEST.
The terminals of the BSL battery should always be considered live, therefore
do not place tools or any other items across the terminals. Do not pierce,
short or damage the terminals in any way. Do not touch the terminals of the
battery.
Fire Hazard: Do not discharge battery below specified minimum level as this poses an increased fire risk. Do not attempt to charge a swollen or damaged battery. In the event of fire, a CO2 or Dry Powder extinguisher should be used. Class D extinguishers are not suitable.
Dispose of batteries through the proper local regulations. Not suitable for regular refuse/recycling.
Pin out diagram
Figure 1: Pin-out diagram for 8.2kWh BSL battery.
A- Power indicator light
B- Run light (battery activity)
C- Alarm indicator light
D- State of charge indicator lights
E- Reset switch (BMS Power button)
F- Dip switches for parallel connection
G- Dry Contacts (mostly unused)
H- RS485 Left port (Port 1)| I- CAN Port (Port 2)
J- RS232 Port (Unused)
K- RS485 Right Ports (Ports 4 & 5)
L- Circuit breaker (terminal power)
M- Positive terminal
N- Negative terminal
O- Carry handles
P- Mounting holes
---|---
Battery set-up
2.1 General
2.1.1 Turning battery on and off
The battery can be switched on or off by holding down the small recessed
button marked “RESET”.
2.1.2 CAN communication
A VE. Can to CAN-bus BMS “Type B” cable is required for CAN-Bus communication
between the BSL battery and the Victron GX device. Some inverters will use
different cable configuration, please check this with inverter
suppliers.(Black to inverter/GX device, red to battery).
Function | Victron VE. Can Side (GX) | Battery side |
---|---|---|
GND | Pin 3 | Pin 2 |
CAN – L | Pin 8 | Pin 5 |
CAN – H | Pin? | Pin 4 |
2.1.3 Smart shunt
A Battery Monitoring Device (Victron BMV/Smarts hunt) is not required as State
of Charge (SOC) is sent to the GX device via the CAN-Bus cable.
2.1.4 Dry contacts
Dry Contacts are mostly unused, but for communication with some non-smart
systems please see the table below. Working current should be less than 2A,
mainly to connect
with an external indicator light or buzzer.
PIN I to PIN2 | Always open, will close with low battery signal |
---|---|
PIN3 to PIN4 | Always Open, will close with fault/protection signal. |
2.1.5 Other ports
Port 1 (RS485) and port 3 (RS232) are used for programming and retrieving
information only and must be left open.
2.2 Multiple batteries
2.2.1 Max number of parallel batteries
A maximum of 20 batteries can be connected in parallel. Each battery will
require a unique binary address which can be setup via the dip-switches
located on the front of the battery.
2.2.2 Installing multiple batteries
When installing more than one battery in parallel, a standard RJ45 patch
network cable will be required for inter-battery communication. These cables
will need to be connected to port 4 or 5 between all the connected batteries.
The ports are paralleled therefore any port can be used for in or out
connection.
2.2.3 Cable sizing with multiple batteries
It is recommended to make use of a common rail bus-bar when more than 4
batteries are to be installed.All positive cables running between the battery
and bus-bar must be the same length and all negative cables must be the same
length. The batteries should be evenly grouped where possible. The recommended
battery cable sizes from the batteries (going to the inverter) in parallel
are as follows: 1 battery – 50mm 2 , 2 batteries – 70mm 2 , 3 batteries – 95mm
2 or 2 2 × 50mm , 4 batteries – 120mm 2 or 2 × 70mm
2 2.2.4 Dip switch settings for multiple batteries
Address | Dial switch position | Remark |
---|---|---|
#1 | #2 | #3 |
0 | OFF | OFF |
1 | ON | OFF |
2 | OFF | ON |
3 | ON | ON |
4 | OFF | OFF |
5 | ON | OFF |
6 | OFF | ON |
7 | ON | ON |
8 | OFF | OFF |
9 | ON | OFF |
10 | OFF | ON |
11 | ON | ON |
12 | OFF | OFF |
13 | ON | OFF |
14 | OFF | ON |
IS | ON | ON |
Inverter set-up
3.1 Batteries per inverter size
Inverter size 15kVA | Recommended N.O. batteries | Minimum N.O. of batteries |
---|---|---|
10kVA | 3 | 2 |
8kVA | 2 | 2 |
5kVA | 2 | 1 |
3kVA | 1 | 1 |
1 | 1 |
3.2 Battery set-up on Victron GX device
- The VE. Can to CAN-bus BMS Type B cable needs to be connected to the VE-Can port on the GX device and the second unused VE. Can port needs to be terminated with the Victron blue terminator. Ensure that the cable is marked CCGX at the end.
- Press the enter button on the GX device. This should take you to the device list page. Scroll down to settings, press enter, and scroll to services and press enter again. Navigate to the CAN settings and change the CAN speed from 250 KB to 500 KB.
- Scroll to DVCC and select Switch DVCC on. Flag SHARED VOLTAGE SENSE and CHARGE LIMIT. Set CCL (charge current limit) to 80 amps/battery.
- Navigate back to the device list and the BSL battery should appear on the device list.
- Select the BSL battery set the parameters as follows:
• Charge Voltage 54.5V.
• Charge Current Limit: 90A per battery (recommended 80A).
• Discharge Current Limit: 180A per battery (constant 150A).
Inverter settings (Victron)
4.1 General Tab
4.2 Grid Tab
4.3 Inverter Tab
4.4 Charger Tab
4.5 Assistant tab (a)
4.6 Assistant tab (b)
4.7 Assistant tab (c)
4.8 Assistant tab (d)
4.9 Assistant tab (e)
4.10 Assistant tab (f)
4.11 Assistant tab (g)
4.12 Assistant tab (h)
Other specifications
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>