iSMACONTROLLI SfAR-1M-2DI2DO Expansion Module 2 Digital Inputs 2 Digital Outputs User Manual

June 9, 2024
iSMACONTROLLI

iSMACONTROLLI logo SfAR-1M-2DI2DO
Expansion Module – 2 Digital Inputs, 2
Digital Outputs
User Manual
iSMACONTROLLI SfAR 1M 2DI2DO Expansion Module 2 Digital Inputs 2 Digital
Outputs

Introduction

Thank you for choosing our product.
This manual will help you with proper handling and operating of the device.
The information included in this manual have been prepared with utmost care by our professionals and serve as a description of the product without incurring any liability for the purposes of commercial law. This information does not discharge you from the liability of your own judgement and verification.
We reserve the right to change product specifications without notice.
Please read the instructions carefully and follow the recommendations concluded therein.
WARNING!
Failure to follow instructions can result in equipment damage or impede the use of the hardware or software.
1.1 Revision History

Rev. Date Description
3.1 25-May-22 Rebranded

Table 1. Revision history

Safety Rules

  • Improper wiring of the product can damage it and lead to other hazards. Make sure that the product has been correctly wired before turning the power on.

  • Before wiring or removing/mounting the product, make sure to turn the power off.
    Failure to do so might cause an electric shock.

  • Do not touch electrically charged parts such as power terminals. Doing so might cause an electric shock.

  • Do not disassemble the product. Doing so might cause an electric shock or faulty operation.

  • Use the product only within the operating ranges recommended in the specification (temperature, humidity, voltage, shock, mounting direction, atmosphere, etc.). Failure
    to do so might cause a fire or faulty operation.

  • Firmly tighten the wires to the terminal. Failure to do so might cause a fire.

  • Avoid installing the product in close proximity to high-power electrical devices and cables, inductive loads, and switching devices. Proximity of such objects may cause an uncontrolled interference, resulting in an instable operation of the product.

  • Proper arrangement of the power and signal cabling affects the operation of the entire control system. Avoid laying the power and signal wiring in parallel cable trays. It can cause interferences in monitored and control signals.

  • It is recommended to power controllers/modules with AC/DC power suppliers. They provide better and more stable insulation for devices compared to AC/AC transformer systems, which transmit disturbances and transient phenomena like surges and bursts to devices. They also isolate products from inductive phenomena from other transformers and loads.

  • Power supply systems for the product should be protected by external devices limiting overvoltage and effects of lightning discharges.

  • Avoid powering the product and its controlled/monitored devices, especially high power and inductive loads, from a single power source. Powering devices from a single
    power source causes a risk of introducing disturbances from the loads to the control devices.

  • If an AC/AC transformer is used to supply control devices, it is strongly recommended to use a maximum 100 VA Class 2 transformer to avoid unwanted inductive effects, which are dangerous for devices.

  • Long monitoring and control lines may cause loops in connection with the shared power supply, causing disturbances in the operation of devices, including external communication. It is recommended to use galvanic separators.

  • To protect signal and communication lines against external electromagnetic interferences, use properly grounded shielded cables and ferrite beads.

  • Switching the digital output relays of large (exceeding specification) inductive loads can cause interference pulses to the electronics installed inside the product. Therefore, it is recommended to use external relays/contactors, etc. to switch such loads. The use of controllers with triac outputs also limits similar overvoltage phenomena.

  • Many cases of disturbances and overvoltage in control systems are generated by switched, inductive loads supplied by alternating mains voltage (AC 120/230 V). If they do not have appropriate built-in noise reduction circuits, it is recommended to use external circuits such as snubbers, varistors, or protection diodes to limit these effects.

Module Features

3.1 Purpose and Description of the Module
The SfAR-1M-2DI2DO module is an innovative device that provides a simple and costeffective extension of the number of lines of input in popular PLCs.
The module has 2 digital inputs with configurable timer/counter option, which allows to connect one encoders. All inputs are isolated from the logic with optocouplers. Each
channel can be individually configured in one of several modes.
The module is connected to the RS485 bus with a twisted-pair wire. Communication is via Modbus RTU or Modbus ASCII. The use of 32-bit ARM core processor provides fast processing and quick communication. The baud rate is configurable from 2400 to 115200.
The module is designed for mounting on a DIN rail in accordance with DIN EN 5002.
The module is equipped with a set of LEDs to indicate the status of inputs and outputs which is useful for diagnostic purposes and helping to find errors.
Module configuration is done via USB by using a dedicated computer program. It also allows for changing the parameters using the Modbus protocol.

3.2 Technical Specification

Power Supply Voltage 10-38 V DC; 10-28 V AC

Power consumption (with active Modbus transmission and high state on all inputs)| 1 W at 24 V DC
2 VA at 24 V AC
Digital Inputs| No. of inputs| 2
Voltage range| 0-36 V
Low state “0”| 0-3 V
High state “1”| 6-36 V
Input impedance| 4 kΩ
Isolation| 1500 Vrms
Input type| PNP or NPN
Counters| No.| 2
Resolution| 32-bit
Frequency| 1 kHz (max.)
Impulse width| 500 μs (min.)
Digital Outputs| No. of outputs| 2
Max. voltage| 55 V
Max. current| 250 mA
Output type| PNP
Isolation| 1500 Vrms
Temperature| Work| -20°C to +65°C
Storage| -40°C to +85°C
Connectors| Power supply| 3 pin
Communication| 3 pin
Inputs| 2 x 3 pin
Configuration| mini USB
Size| Height| 90 mm
Length| 56.4 mm
Width| 17.5 mm
Interface| RS485| Up to 128 devices

Table 2. Technical specification

3.3 Dimensions
The appearance and dimensions of the module are shown below. The module is mounted directly to the rail in the DIN industry standard. Power connectors, communication and IOs are at the bottom and top of the module. USB connector configuration and indicators located on the front of the module.

iSMACONTROLLI SfAR 1M 2DI2DO Expansion Module 2 Digital Inputs 2 Digital
Outputs - Dimensions Figure 1. Dimensions

Communication

4.1 Grounding and Shielding
In most cases, I/O modules will be installed in an enclosure along with the other devices, which generate electromagnetic radiation. Relays, contactors, transformers, motor invertors, etc., are examples of such devices. Radiation can induce electrical noise into both power and signal lines, as well as direct radiation into the module. Whether or not the SfAR modules are immune to such effects, the interferences must be suppressed at their source if possible to ensure the proper functioning of the entire system. Appropriate grounding, shielding and other protective steps should be taken at the installation stage to prevent these effects. It is recommended to at least follow the rules below:

  • line power cables must be routed with spatial separation from signal and data transmission cables;
  • analog and digital signal cables should also be separated;
  • it is recommended to use shielded cables for analog signals, cable shields should not be interrupted by intermediate terminals;
  • the shielding should be earthed directly after the cable enters the cabinet.

It is recommended to install interference suppressors when switching inductive loads (e.g., coils of contactors, relays, solenoid valves). RC snubbers or varistors are suitable for AC voltage and freewheeling diodes for DC voltage loads. The suppressing elements must be connected as close to the coil as possible.
4.2 Network Termination
Transmission line effects often present problems for data communication networks.
These problems include reflections and signal attenuation. To eliminate the presence of reflections of signal from the end of the cable, the cable must be terminated at both ends with a resistor across the line adequate to its characteristic impedance. Both ends must be terminated since the propagation is bidirectional. In case of an RS485 twisted pair cable, this termination is typically 120 Ω.
4.3 Types of Modbus Functions
There are 4 types of Modbus functions supported by the SfAR modules.

Type| Beginning Address| Variable| Access| Modbus Command
---|---|---|---|---
1| 00001| Digital Outputs| Bit Read/write| 1, 5, 15
2| 10001| Digital Inputs| Bit Read| 2
3| 30001| Input Registers| Registered Read| 3
4| 40001| Output Registers| Registered Read/write| 4, 6, 16

Table 3. Types of Modbus functions supported by the module

4.4 Communication Settings
The data stored in the module’s memory is given in the 16-bit registers. The access to registers is via Modbus RTU or Modbus ASCII.
4.4.1 Default Settings

Parameter Name Value
Address 1
Baud rate 19200
Parity No
Data bits 8
Stop bits 1
Reply delay [ms] 0
Modbus type RTU

Table 4. Default settings

4.5 Configuration registers

Modbus Address| Decimal Address| Hex Address| Name| Values
---|---|---|---|---
40003| 2| 0x02| Baud Rate| 0 – 2400
1 – 4800
2 – 9600
3 – 19200
4 – 38400
5 – 57600
6 – 115200
other – value * 10
40005| 4| 0x04| Parity| 0 – none
1 – odd
2 – even
3 – always 0
4 – always 1
40004| 3| 0x03| Stop Bits| 1 – one stop bit
2 – two stop bits
40004| 3| 0x03| Data Bits| 7 – 7 data bits
8 – 8 data bits
40006| 5| 0x05| Response Delay| Time in ms
40007| 6| 0x06| Modbus Mode| 0 – RTU
1 – ASCII

4.6 Watchdog
This 16-bits register specifies the time in milliseconds to watchdog reset. If the module does not receive any valid message within that time, all digital and analog outputs will be set to the default state.
This feature is useful if there is an interruption in data transmission and for security reasons. Output states must be set to the appropriate state in order to reassure the safety of persons or property.
The default value is 0 milliseconds, which means the watchdog function is disabled.

Indicators

iSMACONTROLLI SfAR 1M 2DI2DO Expansion Module 2 Digital Inputs 2 Digital
Outputs - Indicators

Indicator Description
ON The LED indicates that the module is correctly powered
TX The LED lights up when the unit received the correct packet and sends the

answer
DI1, DI2| The LED indicates that on the input is high state
DO1, DO2| The LED indicates that the output is on

Table 6. Description of indicators

Connections

6.1 Block DiagramiSMACONTROLLI SfAR 1M 2DI2DO Expansion Module 2 Digital
Inputs 2 Digital Outputs - Block Diagram 6.2 Power Supply Connection
6.2.1 DC Power Connection

Figure 4. DC power connection

6.2.2 AC Power Connection

Figure 5. AC power connection

6.3 Communication Bus Connection

iSMACONTROLLI SfAR 1M 2DI2DO Expansion Module 2 Digital Inputs 2 Digital
Outputs - Communication bus connection Figure 6. Communication bus connection

6.4 Connection of Outputs

iSMACONTROLLI SfAR 1M 2DI2DO Expansion Module 2 Digital Inputs 2 Digital
Outputs - Connection of outputs Figure 7. Connection of outputs

6.5 Connection of Inputs

iSMACONTROLLI SfAR 1M 2DI2DO Expansion Module 2 Digital Inputs 2 Digital
Outputs - Connection of inputs Figure 8. Connection of inputs

Modules Registers

7.1 Registered Access

Modbus Address| Decimal Address| Hex Address| Register Name| Access| Description
---|---|---|---|---|---
30001| 0| 0x00| Version/Type| Read| Version and type of the device
30002| 1| 0x01| Address| Read| Module address
40003| 2| 0x02| Baud Rate| Read/write| RS485 baud rate
40004| 3| 0x03| Stop Bits & Data Bits| Read/write| No of stop bits & data bits
40005| 4| 0x04| Parity| Read/write| Parity bit
40006| 5| 0x05| Response Delay| Read/write| Response delay in ms
40007| 6| 0x06| Modbus Mode| Read/write| Modbus mode (ASCII or RTU)
40009| 8| 0x08| Watchdog| Read/write| Watchdog
40013| 12| 0x0C| Default Output State| Read/write| Default output state (after power on or watchdog reset)
40033| 32| 0x20| Received Packets LSR (Least Significant Register)| Read/write| No. of received packets
40034| 33| 0x21| Received Packets MSR (Most Significant Register)| Read/write
40035| 34| 0x22| Incorrect Packets LSR| Read/write| No. of received packets with error
40036| 35| 0x23| Incorrect Packets MSR| Read/write
40037| 36| 0x24| Sent Packets LSR| Read/write| No. of sent packets
40038| 37| 0x25| Sent Packets MSR| Read/write
30051| 50| 0x32| Inputs| Read| Inputs state
40052| 51| 0x33| Outputs| Read/write| Output state
40053| 52| 0x34| Counter 1 LSR| Read/write| 32-bit counter 1
40054| 53| 0x35| Counter 1 MSR| Read/write
40055| 54| 0x36| Counter 2 LSR| Read/write| 32-bit counter 2
40056| 55| 0x37| Counter 2 MSR| Read/write|
40061| 60| 0x3C| CCounter 1 LSR| Read/write| 32-bit value of captured counter 1
40062| 61| 0x3D| CCounter 1 MSR| Read/write|
40063| 62| 0x3E| CCounter 2 LSR| Read/write| 32-bit value of captured counter 2
40064| 63| 0x3F| CCounter 2 MSR| Read/write|
40069| 68| 0x44| Counter Config 1| Read/write| Counter configuration
+1 – time measurement (if 0 counting impulses)
+2 – autocatch counter every 1 sec
+4 – catch value when input low
+8 – reset counter after catch
+16 – reset counter if input low
+32 – encoder
40070| 69| 0x45| Counter Config 2| Read/write|
40073| 72| 0x48| Catch| Read/write| Catch counter
40074| 73| 0x49| Status| Read/write| Captured counter

Table 7. Registered access

7.2 Bit Access

Modbus Address| Dec Address| Hex Address| Register Name| Access| Description
---|---|---|---|---|---
193| 192| 0x0C0| Default State of Output 1| Read/write| Default state of output 1
194| 193| 0x0C1| Default State of Output 2| Read/write| Default state of output 2
10801| 800| 0x320| Input 1| Read| Input 1 state
10802| 801| 0x321| Input 2| Read| Input 2 state
817| 816| 0x330| Output 1| Read/write| Output 1 state
818| 817| 0x331| Output 2| Read/write| Output 2 state
1153| 1152| 0x480| Capture 1| Read/write| Capture counter 1
1154| 1153| 0x481| Capture 2| Read/write| Capture counter 2
1169| 1168| 0x490| Captured 1| Read/write| Captured value of counter 1
1170| 1169| 0x491| Captured 2| Read/write| Captured value of counter 2

Table 8. Bit access

Configuration Software

The SfAR Configurator is the type of software, which is designed to set the communication module registers over Modbus network as well as to read and write the current value of other registers of the module. It is a convenient way to test the system as well as to observe real-time changes in the registers.
Communication with the module is via the USB cable. The module does not require any drivers.iSMACONTROLLI SfAR 1M 2DI2DO Expansion Module 2 Digital
Inputs 2 Digital Outputs - PC connectionThe SfAR Configurator is a universal software, where it is possible to configure all available modules.

iSMACONTROLLI SfAR 1M 2DI2DO Expansion Module 2 Digital Inputs 2 Digital
Outputs - The SfAR Configurator Figure 10. The SfAR Configurator

iSMACONTROLLI logowww.ismacontrolli.com
DMP267en | 3rd Issue rev. 1 | 05/2022

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

iSMACONTROLLI User Manuals

Related Manuals