Optonica LED SDM230 Series Single Phase Two Wires Multifunction Din Rail Meter User Manual

June 9, 2024
OptonicaLED

Optonica-logo

OptonicaLED SDM230 Series Single Phase Two Wires Multifunction Din Rail

Meter

Optonica-LED-SDM230-Series-Single-Phase-Two-Wires-Multifunction-Din-Rail-
Meter-fig-1

Introduction

  • The SDM230 series, manufactured by Eastron Electronic Co., Ltd., measures and displays the characteristics of a single-phase two-wire (1p2w) network. The series includes five models:
    • SDM230-Modbus
    • SDM230-Pulse
    • SDM230Mbus
    • SDM230-2T
    • SDM230M-DI
  • The bi-directional measurement makes the meter suitable for import and export energy and power monitoring applications, and also perfect for solar PV measurements. With RS485 Modbus and M-bus ports, the meter is easy to remotely communicate with other AMR/SCADA systems.

Key Characteristics

  • The SDM230 series measures:
    • Voltage (U)
    • Current (I)
    • Active power (P)
    • Reactive power (Q)
    • Apparent power (S)
    • Power factor (PF)
    • Frequency (Hz)
    • Demand (Dmd)
    • Energy (kWh)
    • Reactive energy (kVArh)
    • Import energy
    • Export energy
  • The SDM230 series also includes:
    • RS485 Modbus communication
    • Pulse outputs (configurable and non-configurable)
    • Multi-tariffs (SDM230-2T only)
    • Dual-source measurement (SDM230-Pulse only)

Pulse Output

The meter provides two pulse outputs. Both pulse outputs are passive type. Pulse output 1 can be set to generate pulses to represent total / import/export kWh or kVArh. The pulse constant can be set to generate 1 pulse per: 0.001/0.01/0.1/1kWh/kVArh (default is 0.001 export kWh). Pulse width: 200/100/60ms Pulse output 2 is non-configurable. It is fixed with active kWh (Imp). The constant is 1000imp/kWh.

Communication

The SDM230 series includes RS485 Modbus communication and M-bus communication (SDM230-Mbus only). Both ports provide a means of remotely monitoring and controlling the unit. Set-up screens are provided for setting up the RS485 port and M-bus port.

Usage Instructions

Before using the SDM230 series, please read the safety instructions provided in the user manual carefully.
To use the SDM230 series:

  1. Install the meter according to the installation instructions provided in the user manual.
  2. Connect the meter to the power supply.
  3. Configure the pulse outputs (if applicable) and communication ports using the set-up screens provided in the user manual.
  4. Use the RS485 Modbus or M-bus protocol to remotely monitor and control the unit.
    Note that the SDM230-Pulse model can measure energy from two different power supplies. For example, when the public grid is powered off and an electric generator is on, the meter switches to tariff 2 measurement automatically.

Safety Instruction

  • The Installation instructions do not include a complete list of all safety measures necessary for operating the device. Special operating conditions may require additional measures. The installation instructions contain notes that must be observed for your personal safety to prevent property damage.
  • Safety instructions in this document are highlighted with a warning triangle and are presented as follows depending on the level of risk.
  • The General warning symbol calls attention to possible risks of injury. Observe all the instructions listed under the symbol to prevent injuries or even death
  • This additional symbol indicates any electrical danger that can result in serious injuries or death
    Attention
    Warns of an imminently dangerous situation that can result in property damage or environmental damage in the event of noncompliance.

Introduction

  • This document provides operating, maintenance and installation instructions of SDM230 series made by Eastron Electronic Co., Ltd. The SDM230 series measure and display the characteristics of single phase two wires (1p2w) network. The SDM230 series covers 5 models:SDM230-Modbus,SDM230-Pulse,SDM230- Mbus, SDM230-2T and SDM230M-DI.
  • The bi-directional measurement makes the meter suitable for import and export energy and powe r monitoring applications, and also perfect for solar PV measurements. With RS485 Modbus and M-bus port, the meter is easy to remote communicate with other AMR/SCADA systems.
    Model| Measurements| Communi- cation| Pulse Outputs| Multi Tariffs
    ---|---|---|---|---
    __

SDM230-

Modbus

| __

U, I, P, Q, S, PF, Hz,

Dmd, kWh, kVArh, Import, Export

| __

RS485

Modbus

| 1:

configurable 2:

1000imp/kwh

| __

__

NO

__

SDM230-

Mbus

| __

U, I, P, Q, S, PF, Hz,

Dmd, kWh, kVArh, Import, Export

| __

M-bus EN13757-3

| 1:

configurable 2:

1000imp/kwh

| __

__

NO

__

SDM230-

Pulse

| __

U, I, P, Q, S, PF, Hz,

Dmd, kWh, kVArh, Import, Export

| __

__

NO

| 1:

configurable 2:

1000imp/kwh

| __

__

NO

__

SDM230- 2T

| __

U, I, P, Q, S, PF, Hz,

Dmd, kWh, kVArh, Import, Export

| __

RS485

Modbus

| 1:

configurable 2:

1000imp/kwh

| __

2 Tariffs (Dual source)

__

SDM230 M-DI

| __

U, I, P, Q, S, PF, Hz,

Dmd, kWh, kVArh, Import, Export

| __

RS485

Modbus

| __

__

NO

| __

__

NO

Key Characteristics

  • Bi-directional measure and display
  • Multi-function measurements
  • Two pulse outputs
  • RS485 Modbus / M-bus
  • 100A direct connection
  • Two module size (35mm)
  • Password protected set-up
  • Backlighted LCD display
  • 2 tariffs dual power source
  • 2 Digital Inputs

Pulse Output

  • The meter provides two pulse outputs. Both pulse outputs are passive type.
  • Pulse output 1 can be set to generate pulses to represent total / import/export kWh or kVArh.
  • The pulse constant can be set to generate 1 pulse per: 0.001/0.01/0.1/1kWh/kVArh (default is 0.001 export kWh).
  • Pulse width: 200/100/60ms
  • Pulse output 2 is non-configurable. It is fixed with active kWh (Imp). The constant is 1000imp/kWh.

RS485 Serial – Modbus RTU
RS485 serial port with Modbus RTU protocol to provide a means of remotely monitoring and controlling the unit. Set-up screens are provided for setting up the RS485 port.

Mbus for SDM230-Mbus
This unit has an M-BUS serial port with M-BUS protocol to provide a means of remotely monitoring and controlling the unit. Set-up screens are provided for setting up the M-bus port.

Dual Source Measurement for SDM230-2T

  • This unit can measure energy from two different power supplies. For example, when public grid is power off and electric generator is on, the meter switches to tariff 2 measurement automatically.
  • The meter can also be used as a tariff meter. The tariff is controlled by an external time relay.

Operation

LCD Display

NO. Descriptions
1 7 digits used to display measured values
2 Total value
3 Tariff information
4 Import information, Export information
5 Max. Demand for power or current.
6 Pulse output 1and Pulse output 2
7 Measurement units
8 PF = power factor Hz = frequency
9 Bar display of power
10 Communication indicator
13 Lock symbol

Initialization Display

Optonica-LED-SDM230-Series-Single-Phase-Two-Wires-Multifunction-Din-Rail-
Meter-fig-3

Scroll Display by Buttons
After initialization and self-checking program, the meter display the measured values. The default page is total kWh. If the user wants to check other information, he needs to press the scroll button on the front panel.
The display order by scroll button :

  • For SDM230-Modbus:
    Total kWh→ Import kWh→Export kWh→ Resettable kWh→ Total kVArh→Import kVArh→ Export kVArh→Resettable kVArh → Max. Power Demand→ Voltage →Current→W→ VAr → VA→ Power Factor→Frequency →Pulse Constant→ Modbus ID → Baud Rate →Continuous Running Time Display No:1,4~7,10~24.

  • *For SDM230-Pulse:
    Total kWh→ Import kWh→Export kWh→ Resettable kWh→ total kVArh→Import kVArh→ Export kVArh→resettable kVArh → Max. Power Demand→ Voltage →Current→W VAr →VA→ Power Factor→Frequency →Pulse Constant Display No:1,4~7,10~21.

  • For SDM230-2T:
    Total kWh→ T1 total kWh→ T2 total kWh→Import kWh→ Export kWh →resettable kWh→Total kVArh→T1 total kVArh→T2 total kVArh→Import kVArh→ Export kVArh→ resettable kVArh→Max. Power Demand→ Voltage → Current→W→ Var →VA→ Power Factor → Frequency → Pulse Constant → Modbus ID →Baud Rate → Continuous Running Time Display No: 1~24.

  • For SDM230-Mbus:
    Total kWh→ Import kWh→Export kWh→ Resettable kWh→Total kVArh→Import kVArh→ Export kVArh→ Resettable kVArh→ Max. Power Demand→ Voltage → Current→W→ VAr →VA→ Power Factor → Frequency → Pulse Constant→ Mbus Primary Address→Mbus Secondary Address→ Baud Rate→Continuous Running Time Display No:1,4~7,10~24.

  • For SDM230M-DI:
    Total kWh→ Import kWh→Export kWh→ Resettable kWh →Total kVArh→Import kVArh→ Export kVArh→ Resettable kVArh→ Max. Power Demand → Voltage → Current → W → VAr → VA → Power Factor → Frequency → DI1 → DI2 → Modbus ID → Baud Rate → Continuous Running Time Display No:1,4~7,10~20,22~26.

Scroll display by buttons:

Optonica-LED-SDM230-Series-Single-Phase-Two-Wires-Multifunction-Din-Rail-
Meter-fig-6 Optonica-LED-SDM230-Series-Single-Phase-Two-Wires-Multifunction-Din-Rail-
Meter-fig-7 Optonica-LED-SDM230-Series-Single-Phase-Two-Wires-Multifunction-Din-Rail-
Meter-fig-8 Optonica-LED-SDM230-Series-Single-Phase-Two-Wires-Multifunction-Din-Rail-
Meter-fig-9 Optonica-LED-SDM230-Series-Single-Phase-Two-Wires-Multifunction-Din-Rail-
Meter-fig-10 Optonica-LED-SDM230-Series-Single-Phase-Two-Wires-Multifunction-Din-Rail-
Meter-fig-11 Optonica-LED-SDM230-Series-Single-Phase-Two-Wires-Multifunction-Din-Rail-
Meter-fig-12

Set-up Mode
To get into Set-up Mode, the user needs to press the “Enter” button for 3 seconds.

Optonica-LED-SDM230-Series-Single-Phase-Two-Wires-Multifunction-Din-Rail-
Meter-fig-15 Optonica-LED-SDM230-Series-Single-Phase-Two-Wires-Multifunction-Din-Rail-
Meter-fig-16 Optonica-LED-SDM230-Series-Single-Phase-Two-Wires-Multifunction-Din-Rail-
Meter-fig-17 Optonica-LED-SDM230-Series-Single-Phase-Two-Wires-Multifunction-Din-Rail-
Meter-fig-18 Optonica-LED-SDM230-Series-Single-Phase-Two-Wires-Multifunction-Din-Rail-
Meter-fig-22

Specifications

General Specifications
  • Voltage AC (Un): 230V

  • Voltage range: 176~276V AC

  • Base current (Ib/Iref): 10A

  • Max. current (Imax): 100A(65A for ETL version)

  • Mini current (Imin): 0.5A

  • Starting current: 0.4% of Ib/Iref

  • Power consumption: <2W/10VA

  • Frequency:

    • 50Hz(for MID version)
    • 50/60Hz ± 2% (for non-MID version)
  • AC voltage withstand: 4KV for 1 min

  • Impulse voltage withstand: 6KV-1.2uS waveform

  • Over current withstand: 30Imax for 0.01s

  • Pulse 1 output rate: configurable, default 1000i/kWh

  • Pulse 2 output rate: non-configurable,1000i/kWh

  • Display: LCD with backlit

  • Max. reading: 999999.9kWh

Accuracy
  • Voltage: 0.5% of range maximum
  • Current: 0.5% of nominal
  • Frequency: 0.2% of mid-frequency
  • Active power: 1% of range maximum
  • Reactive power: 1% of range maximum
  • Apparent power: 1% of range maximum
  • Active energy:
    • Class 1 IEC62053-21
    • Class B EN50470-1/3
  • Reactive energy: Class 2 IEC62053-23
Environment
  • Operating temperature: -25 C to +55 C
  • Storage/transportation temperature: -40 C to +70 C
  • Reference temperature: 23 C ± 2 C
  • Relative humidity: 0 to 95%, non-condensing
  • Installation category: CAT III
  • Mechanical environment: M1
  • Electromagnetic environment: E2
  • Degree of pollution: 2
    Maximum operating and storage temperatures are in the context of typical daily and seasonal variation.

Pulse Output
*Not for SDM230M-DI

  • The pulse output 1 can be set to generate pulses to represent total kWh, total kVArh,import kWh, export kWh,import kVArh, export kVArh.
  • Constant can be set to 1000/100/10/1 impulse per kWh or kVArh.
  • Pulse width 200/100/60mS.

ATTENTION: Pulse output must be fed as shown in the wiring diagram on the left. Scrupulously respect polarities and the connection mode. Opto-coupler with potential-free SPST-NO Contact.

  • Contact range: 5~27VDC Max. current Input:27mA DC.

Digital Inputs
*For SDM230M-DI only
The meter equipped with two digital inputs. An input signal is detected on a digital input if a voltage of at least 5V and maximum 24V [email protected] is applied.

RS485 Output for Modbus RTU
*Not for SDM230-Pulse or SDM230-Mbus

  • The meter provides a RS485 port for remote communication. Modbus RTU is the protocol applied. For Modbus RTU, the following RS485 communication parameters can be configured from the set-up menu.
  • Baud rate: 1200, 2400, 4800, 9600, 19200, 38400 bps
  • Parity: NONE/ODD/EVEN
  • Stop   bits: 1 or 2
  • Modbus Address: 1 to 247

Mbus
*For SDM230-Mbus only

  • The meter provides a Mbus Port for remote communication. the meter adopts EN13757-3 Mbus communication protocol.
  • The communication parameters can be configured via the set-up mode.
  • Baudrate: 300,600,1200,2400,4800,9600 bps
  • Parity: NONE/ODD/EVEN
  • Stop bits: 1 or 2
  • Primary address: 001~250
  • Secondary address: 00000001~99999999
Mechanics
  • Din rail dimensions: 36x100x63 (WxHxD) Per DIN 43880
  • Mounting: DIN rail 35mm
  • Ingress protection: IP51 (indoor)
  • Material: Self-extinguishing UL94V-0

DIMENSION

Optonica-LED-SDM230-Series-Single-Phase-Two-Wires-Multifunction-Din-Rail-
Meter-fig-26

Installation and Sealing

Declaration of Conformity(for the MID approved version meter only)

  • We Zhejiang Eastron Electronic Co.,Ltd.
  • Declare under our sole responsibility as the manufacturer that the single phase multi-funtion electrical energy meter “SDM230 Series” correspond to the production model described in the EU-type examination certificate and to the requirements of the Directive 2014/32/EU EU type examination certificate number 0120/SGS0206.
  • Identification number of the NB0598

Wiring Diagram

SDM230-V1

Optonica-LED-SDM230-Series-Single-Phase-Two-Wires-Multifunction-Din-Rail-
Meter-fig-28

SDM230-V2

Optonica-LED-SDM230-Series-Single-Phase-Two-Wires-Multifunction-Din-Rail-
Meter-fig-29

Definitions of other terminals

Optonica-LED-SDM230-Series-Single-Phase-Two-Wires-Multifunction-Din-Rail-
Meter-fig-30

Terminals Capacity

| COMM / Pulse / 2T| 0.5~1.5mm²
---|---|---
Load| 4~25mm²

Screw Torque

| COMM / Pulse / 2T| 0.2Nm
Load| 2.5Nm

ABOUT COMPANY

  • IMPORTER: Prima Group 2004 LTD,
  • Bulgaria, 1784 Sofia, Mladost 1, bl. 144,
  • Ground Floor; Phone: +359 2 988 45 72;

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

OptonicaLED User Manuals

Related Manuals