20- to 30-Ton Packaged Rooftop Performance Data (Gas or Electric Heat)

Size(Tons) 20 Ton 25 Ton 25 Ton 30 Ton 30 Ton
Efficiency High High High High High

Model Number

| LCH / LGH 242H4V| LCH / LGH 300H4V| LCH / LGH 300H4M| LCH / LGH 360H4V| LCH / LGH 360H4M
Blower Type| VAV| VAV| MSAV| VAV| MSAV
Net Cooling Capacity (Btuh)| 238,000| 300,000| 300,000| 350,000| 350,000
Cooling Stages| 4| 4| 4| 4| 4
Nominal Supply Air (cfm)| 6800| 8100| 8100| 8600| 8600
IEER| 15.5| 14.3| 14.4| 13.5| 14.0
EER| 12.3 (LGH)

12.5 (LCH)

| 11.6| 11.6| 10.6 (LGH)

10.8 (LCH)

| 10.6 (LGH)

10.8 (LCH)

Gas Heat Size, (kBtuh)( stages)| 260 (4)

360 (4)

480 (4)

| 260 (4)

360 (4)

480 (4)

| 260 (4)

360 (4)

480 (4)

| 260 (4)

360 (4)

480 (4)

| 260 (4)

360 (4)

480 (4)

Electric Heat Size (kW)| 30, 45, 60, 90, 120
Blower Motor Size (HP)| 5, 7.5, 10| 5, 7.5, 10| 5, 7.5, 10| 5, 7.5, 10| 5, 7.5, 10
Net. Weight (lbs.) G/E| 3,107| 3,107| 3,107| 3,107| 3,107
Net. Weight (lbs.) E/E| 2,997| 2,997| 2,997| 2,997| 2,997
Weight—Shipping (lbs.) G/E| 3,317| 3,317| 3,317| 3,317| 3,317
Weight—Shipping (lbs.) E/E| 3,207| 3,207| 3,207| 3,207| 3,207
Cabinet Size—H x W x L (in.)| 65 x 91 x 145
Filter (Quantity/Size )| (12) 20 x 20 x 2
Sound (dBA)| 95| 95| 95| 95| 95

Unit MCA & MOCP Electrical Data (Standard Indoor Fan Motor) 

LGH/LCH Voltage HP MCA MOCP

242H

| 208-230/3| 7.5| 99| 110
460/3| 7.5| 54| 60
575/3| 7.5| 38| 45

300H

| 208-230/3| 7.5| 135| 150
460/3| 7.5| 64| 70
575/3| 7.5| 49| 50
360H| 208-230/3| 7.5| 145| 150
460/3| 7.5| 71| 80
575/3| 7.5| 54| 60
Factory- and Field-Installed Options|
---|---
Option| Factory| Field|  | Option| Factory| Field|
Cooling|  | I ndoor air quality|
Drain Pan Overflow Switch| •| •|  | MERV 8 Filters| •| •|
PVC or Copper Condensate Drain Trap| •| •| MERV 13 Filters| •| •|
Stainless Steel Condensate Drain Pan| •| •| MERV 16 Filters|  | •|
Blower|  | Replacement Media Filter with Metal Mesh|  | •|
IAQ (CO2) Sensors|  | •|
Blower – Supply Air Motors| •|  |  |
Electrical|
Blower – Supply Air Drive Kits| •|  |
Heating|  | Electrical Voltage| •|  |
Disconnect Switch| •| •|
Combustion Air Intake Extensions|  | •|  |
GFI Service Outlets| •| •|
Gas Heat Input| •|  |
Weatherproof Cover for GFI|  | •|
Low Temperature Vestibule Heater|  | •|
Phase Monitor| •|  |
LPG/Propane Conversion Kits|  | •|
Electric Heat| •| •|
Stainless Steel Heat Exchanger| •|  |
SCR (Silicon Controlled Rectifier) Electric Heat Control4| •|  |
Vertical Vent Extension|  | •|
Cabinet|  | Economizer|
Combination Coil/Hail Guards|  | •|  | Economizer – Downflow or Horizontal with Barometric Relief| •| •|
Corrosion Protection (indoor coil/outdoor coil)| •|  |
Economizer Controls – Sensible| •|  |
Controls|  |
Economizer Controls – Single Enthalpy| •| •|
CS3000, CS7500, and CS8500

Commercial Thermostats

|  | •|  | Economizer Controls – Differential Enthalpy| •| •|
Economizer Controls – Global Control| •|  |
Blower Proving Switch| •| •|
Downflow or Horizontal Barometric Relief Dampers- Hood Furnished| •| •|
BACnet® Module| •| •|
LonTalk® Module| •| •| Outdoor air|
Novar® LSE| •|  |
Manual Outdoor Air Dampers|  | •|
L Connection® Building Automation System|  | •|
Motorized Outdoor Air Dampers| •| •|
Dirty Filter Switch| •| •|
Power exhaust|
Fresh Air Tempering| •| •|
High Static with VFD|  | •|
Smoke Detector Supply and/or Return| •| •|
Supply Static Limit Switch|  | •| High Static with VFD and Bypass|  | •|
Discharge Air Temperature Sensor| •|  | Standard Static| •| •|
 | Humiditrol condenser reheat|
Humiditrol® Dehumidification System| •|  |
Humiditrol Sensor Kit, Remote mounted|  | •|
Roof curbs/ceiling diffusers|
Roof Curbs|  | •|
Ceiling Diffusers|  | •|

Dimension

Model No. Length Return Air
L RL
242 to 360 115-1/8 79-1/2

Logos

Visit us at www.lennox.com For the latest technical information, www.lennoxcommercial.com Contact us at 1-800-4-LENNOX
©2023 Lennox Industries, Inc. (14G47) 3/23 PC92164

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals