POTTER PAD300-4DB 4 Inch 6 Detector Base Owner’s Manual

June 10, 2024
POTTER

PAD300-4DB/6DB
4”/6” Detector BasePOTTER PAD300-4DB 4 Inch 6 Detector
Base

Features

  • Terminals marked with polarity to assist with installation
  • Duplicate Terminals for In-and-out SLC Wiring
  • Terminals accept 22 to 12 AWG wire sizes
  •  Installs on Single Gang, Double Gang, Octagon or 4” Square Box
  • Locking tab prevents unauthorized detector removal
  • Product includes 5-year warranty
  •  6” mounting base comes with trim plate cover

Application

The Potter PAD300-6DB and PAD300-4DB detector bases are used to install PAD300 series detectors. The PAD300-6DB will mount on a single gang, double gang, octagon, 4” square, 50mm, 60mm, and 70mm electrical box.

Description

The PAD300-6DB and PAD300-4DB are low-profile, surface-mount bases used with Potter’s addressable detectors. The base uses screw clamp terminals that accept wire ranging from 22 to 12 AWG. When installed on recessed electrical boxes, the PAD300-6DB is wide enough to completely cover the back box and the immediate surrounding area. The base is equipped with a locking tab to deter unauthorized removal of the attached detector.

Technical Specifications

Installation Temp Range 32°F to 150°F (0°C to 66°C)
Operating Humidity Range 0% to 93% (Non-condensing)
Dimension PAD300-4DB: 3.93 in / 100 mm

PAD300-6DB: 6.3 in / 160 mm
Weight| PAD300-4DB: 1.34 oz / 38 g
PAD300-6DB: 3.03 oz / 86 g
Height| 0.76 in / 20 mm
Acceptable Wire Gauge| 22 to 12AWG
Mounting Options| • Single Gang
• Double Gang
• 3-1/2″ Octagon Box
• 4″ Octagon Box
• 4″ Square with Plaster Ring
• 50mm c/c Box
• 60mm c/c Box
• 70mm c/c Box

Locking Feature

The PAD300-6DB and PAD300-4DB include a locking feature that prevents removal of the detector without using a tool.

  1. To enable this feature, break off the locking tab (See Figure 1), and then install the detector.
  2. To remove the detector from the base when the locking feature has been enabled, insert a small screwdriver into the slot on the base to push the plastic tab while simultaneously turning the detector head counter-clockwise.

Ordering Information

Model Description Stock No.
PAD300-4DB 4” Detector Base 3992781
PAD300-6DB 6” Detector Base 3992782

Wiring Diagrams

Fig. 3

  1. Class B Wiring:
  2. Class A Wiring:
  3. Class X Wiring:

Potter Electric Signal Company, LLC
St. Louis, MO
Phone: 800-325-3936
www.pottersignal.com
PRINTED IN USA
8830203- REV A
10/22

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>