i-therm XTM-443 Digital Preset Timer User Manual

June 10, 2024
i-therm

USER’S OPERATING MANUAL FOR DIGITAL PRESET TIMER
(Models: XTM – 443 / 773 / 993)i-therm XTM-443 Digital Preset
Timer

SPECIFICATIONS :

Display| 3 Digit , 0.56″ Ht (XTM-7731993)
3 Digit , 0.39″ Ht (XTM-443)
---|---
Status Indication| a] Time unit ( Hrs. / Min. /Sec. )
b] Relay status (0P1/0P2)
c] EOC (RT) Time
Time settings| Through Pushwheel Switches
Control Inputs| a] Start
b] Reset
Reset time| < 100 ms
Timing Accuracy| 0.05% Full Scale
Repeat Accuracy| 0.01%
Outputs| 5 Amp © 230VAC Relay (1C/0) x 2
Reset| a] Front switch (Programmable)
b] Remote Reset (via rear terminals)
C] On power interruption (Programmable)
Supply| 90 to 270 VAC
Mounting| Panel
Housing| ABS Plastic
Operating temp| 0 ∼ 50° C
Humidity| 95% Rh (Non Condensing)

Configurable Parameters:

Count direction Up / Down
Timer Start a] Power on Start

b] Front Start
c) Remote Start (Edge Triggered)
d] Remote Start (Edge + Level Triggered)
Timer Function| Auto Reset / Latched output
Front Reset| Enable / Disable
Output 2 Function| a] Auxiliary Contact
b] End of Cycle
c] Off

DIP Switch Setting:-

  1. Timer Mode Setting:-
    DIP 1| Mode
    ---|---
    OFF| On Delay
    ON| Off Delay
  2. Timer Range Setting:-

| DIP 4| DIP 3| DIP 2| Range| Resolution
---|---|---|---|---|---
1| OFF| OFF| OFF| 9.99 Sec| 0.01 Sec
2| OFF| OFF| ON| 99.9 Sec| 0.1 Sec
3| OFF| ON| OFF| 999 Sec| 1 Sec
4| OFF| ON| ON| 99.9 Min| 0.1 Min
5| ON| OFF| OFF| 999 Min| 1 Min
6| ON| OFF| ON| 9Hr. 59Min| 1 Min
7| ON| ON| OFF| 99.9 Hrs| 0.1 Hrs
8| ON| ON| ON| 999 Hrs| 1 Hrs

INSTALLATION GUIDELINES

  1. Prepare the cut-out with proper dimension as shown in figure.
  2. Remove clamp from Timer.
  3. Push the Timer through panel cut-out and secure the Timer in its place by tightening the side clamp.

SAFETY INSTRUCTION MECHANICAL

  • Ambient temperature and relative humidity surrounding the Timer must not exceed the maximum specified limits..
  • The Timer in its installed state must be protected against excessive electrostatic or electromagnetic interferences.

ELECTRICAL

  • The Timer must be wired as per wiring diagram & it must comply with local electrical regulation.
  • The Electrical noise generated by switching inductive loads might create momentary Fluctuation in display, latch up,  data loss or permanent damage to the instrument. To reduce this use snubber circuit across the load.

TERMINAL CONNECTIONS :

i-therm XTM-443 Digital Preset Timer - TERMINAL
CONNECTIONS

OVER ALL DIMENSIONS & PANEL CUT OUT (IN MM)

Programming:-
User List:-

  1. To access the user list press & hold ‘START’ key for 3 Sec.
  2. Press ‘RST’ Key to change he value.
  3. Press ‘START’ Key to Store data & move on to next parameter.
  4. All parameters as shown in the shaded will be displayed for 1 Sec. followed by its value.
PARAMETER DISPLAY DESCRIPTION DEFAULT

End of
Cycle
Time| | End of Cycle Time:- It will appears only if End of Cycle as Output 2 is selected.| 5
The End of Cycle time is set with the help of Push Wheel input.

Configuration List:-

  1. To Enter in this mode press & hold ‘START’ key for 5 sec. at Power On. ‘CNG’ & ‘1.1.2′ Message will be toggle for 5 sec. Now unit will allow the user to configure different parameters with options as described below.
  2. Press ‘START’ Key to move on to next parameter.
  3.  Press ‘RST’ Key to scroll between parameter options.
  4. All following parameters as shown in the shaded will be displayed for 1 Sec. followed by its options or values.
PARAMETER DISPLAY DESCRIPTION DEFAULT

Timer
Direction| | Timer Counting Direction:-| Down
Count

Up Counting:- If Selected. timer starts counting from 0 to set time in ascending
order. ( Up direction )
Down Counting:- If Selected. timer starts counting from Set time to 0 in
descending order. ( Down direction )
Timter Marl| | Timer Start Mode:- This parameter defines the Start mode for the timer.| Power
() II
Start

Power On Start:- If Selected, timer starts counting from Power On.

Front Start :- If Selected. Timer starts only after user presses START key. If the
cycle is incomplete at the time of power fail . It will continue after power is restored without need for re-issuing the Start command from front key ( If MEM=On ).
Remote Edge Trigger Start :- If Selected. Timer starts counting only when it detects
high to low pulse at back terminal from external Input.
Remote Edge Trigger + Level Start :• If Selected. Timer starts counting only when it
detects high to low pulse at back terminal from external Input. The input signal must remain low during timing cycle otherwise timer will Reset.
Cale
Input| | Gate Ingot :- Prompted only if Timer is configured as Power On Start. When| No
Enabled (Set to yes) the External Input can work as a Gate input.
Yes:- The External Input can be used as a Gate input.

his);‘• The External Input can not be used as a Gate input.
Tinter Mode| | Timer Mode:- This parameter will be prompted if other than power on start| Latch
Output
selected.
Latched Mode:• In this mode once the timing cycle is over, User must issue a Reset
signal from front key or Ext. Reset input to Re-Start the timer.
Auto Reset Mnde-• In this mode once the timing cycle is over. Next start input
through External Input signal will Re-Start the timer. No need to issue Reset Signal.
Front
Reset| | Front Reset :- This parameter allows the user to Enable or Disable front Reset| Yes
function. This feature prevents un-authorized attempt to Reset the Timer during Run mode.
Yes:- The Timer can be reset through front panel.

No:• The Timer can not be reset through front panel.

Output 2
Function| | Output 2 Function:-| Auxiliary
Auxiliary Contact:- The OP2 will operate simultaneously with OP1. This function is required when user needs 2 changeover Relay contacts.
End of Cycle Output:- The OP2 is energized for RT period programmed by user via push wheel switches in Sec.
Off:- The OP2 is not used & can be kept reserve for future use.

Mfgd by: Innovative Instruments & Controls LLP
338, New Sonal Link Service Industrial Premises Co-op Society Ltd,
Building No.2, Link Road, Malad (W), Mumbai – 400064.
Tel: 022-66939916/17/18;


https://www.youtube.com/channel/UCzWGtv0HuHUgZR4KKRyKG1w/videos

OIM XTM – XX3 V1.2 Page 3 of 3
E-mail : [email protected] 
Website :www.itherm.co.in

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

i-therm User Manuals

Related Manuals