Jandy AquaLink RS Control Systems Instruction Manual
- June 10, 2024
- Jandy
Table of Contents
Hardware Installation Manual
AquaLink RS Control Systems
AquaLink® RS Control Systems
For use with Pool/Spa Combination, Pool Only/Spa Only, and Dual Equipment
AquaLink RS Systems with Rev Y Firmware
WARNING
FOR YOUR SAFETY – This product must be installed and serviced by a contractor
who is licensed and qualified in pool equipment by the jurisdiction in which
the product will be installed where such state or local requirements exist.
The maintainer must be a professional with sufficient experience in pool
equipment installation and maintenance so that all of the instructions in this
manual can be followed exactly. Before installing this product, read and
follow all warning notices and instructions that accompany this product.
Failure to follow warning notices and instructions may result in property
damage, personal injury, or death. Improper installation and/or operation may
void the warranty. DO NOT MODIFY THIS EQUIPMENT.
Improper installation and/or operation can create unwanted electrical hazard
which may cause serious injury, property damage, or death.
ATTENTION INSTALLER – This manual contains important information about
the installation, operation and safe use of this product. This information
should be given to the owner/operator of this equipment.
EQUIPMENT INFORMATION RECORD
DATE OF INSTALLATION __
INSTALLER INFORMATION ____
INITIAL PRESSURE GAUGE READING (WITH CLEAR FILTER) __
PUMP MODEL ____
HORSEPOWER __
NOTES ____
Section 1. Important Safety Instructions
READ AND FOLLOW ALL INSTRUCTIONS
1.1 Safety Instructions
All electrical work must be performed by a licensed electrician and conform to
all national, state, and local codes. When installing and using this
electrical equipment, basic safety precautions should always be followed,
including the following:
WARNING
To reduce the risk of severe injury or death, do not remove the suction
fittings of your spa or hot tub. Never operate a spa or hot tub if the suction
fittings are broken or missing. Never replace a suction fitting with one rated
less than the flow rate marked on the equipment assembly.
WARNING
Prolonged immersion in hot water may induce hyperthermia. Hyperthermia occurs
when the internal temperature of the body reaches a level several degrees
above the normal body temperature of 98.6°F (37°C). The symptoms of
hyperthermia include dizziness, fainting, drowsiness, lethargy, and an
increase in the internal temperature of the body.
The effects of hyperthermia include:
- unawareness of impending danger;
- failure to perceive heat;
- failure to recognize the need to exit spa;
- physical inability to exit spa;
- fetal damage in pregnant women;
- unconsciousness resulting in a danger of drowning;
- The use of alcohol, drugs, or medication can greatly increase the risk of fatal hyperthermia in hot tubs and spas. less than the flow rate marked on the equipment assembly.
WARNING
To Reduce the Risk of Injury –
The water in a spa should never exceed 104°F (40°C). Water temperatures
between 100°F (38°C) and 104°F (40°C) are considered safe for a healthy adult.
Lower water temperatures are recommended for young children and when spa use
exceeds 10 minutes.
- Since excessive water temperatures have a high potential for causing fetal damage during the early months of pregnancy, pregnant or possibly pregnant women should limit spa water temperatures to 100°F (38°C).
- Before entering a spa or hot tub, the user should measure the water temperature with an accurate thermometer since the tolerance of water temperature-regulating devices varies.
- The use of alcohol, drugs, or medication before or during spa or hot tub use may lead to unconsciousness with the possibility of drowning.
- Obese persons and persons with a history of heart disease, low or high blood pressure, circulatory system problems, or diabetes should consult a physician before using a spa.
- Persons using medication should consult a physician before using a spa or hot tub since some medication may induce drowsiness while other medication may affect heart rate, blood pressure, and circulation.
WARNING
Risk of electric shock, which could result in severe injury or death – Install
the power center at least five (5) feet (1.52m) from the inside wall of the
pool and/or hot tub using non-metallic plumbing. Canadian, Australian, and
European installations must be at least three (3) meters from the water.
Children should not use spas or hot tubs without adult supervision.
Do not use spas or hot tubs unless all suction guards are installed to prevent
body and hair entrapment.
People using medications and/or having an adverse medical history should
consult a physician before using a spa or hot tub.
WARNING
People with infectious diseases should not use a spa or hot tub.
To avoid injury, exercise care when entering or exiting the spa or hot tub.
Do not use drugs or alcohol before or during the use of a spa or hot tub to
avoid unconsciousness and possible drowning.
Do not use a spa or hot tub immediately following strenuous exercise.
Prolonged immersion in a spa or hot tub may be injurious to your health.
Do not permit any electric appliance (such as a light, telephone, radio, or
television) within 5 feet (1.52m) of a spa or hot tub.
The use of alcohol, drugs or medication can greatly increase the risk of fatal
hyperthermia in hot tubs and spas.
WARNING
To avoid injury ensure that you use this control system to control only
packaged pool/spa heaters which have built-in operating and high limit
controls to limit water temperature for pool/spa applications. This device
should not be relied upon as a safety limit control. Water temperature in
excess of 100°F (38°C) may be hazardous to your health.
WARNING
A terminal bar marked “GROUND” is provided within the power center. To reduce
the risk of electrical shock, connect this terminal bar to the grounding
terminal of your electric service or supply panel with a continuous copper
conductor having green insulation and one that is equivalent in size to the
circuit conductors supplying this equipment, but no smaller than no. 12 AWG
(3.3mm2). In addition, a second wire connector should be bonded with a no. 8
AWG (8.4mm2) copper wire to any metal ladders, water pipes, or other metal
within five (5) feet (1.52m) of the pool/spa. In Canada, the bonding wire must
be minimum 6 AWG (13,3mm2).
WARNING
A ground-fault circuit-interrupter must be provided if this device is used to
control underwater lighting fixtures. The conductors on the load side of the
ground-fault circuit-interrupter shall not occupy conduit, boxes, or
enclosures containing other conductors unless the additional conductors are
also protected by a ground-fault circuit-interrupter. Refer to local codes for
complete details.
Attention installer: Install to provide drainage of compartment for
electrical components.
FCC Regulatory Compliance Statement
This device complies with Part 15 of the FCC Rules. Operation is subject to
the following two conditions:
- This device may not cause harmful interference, and
- This device must accept any interference received, including interference that may cause undesired operation.
CAUTION: Changes or modifications not expressly approved by the party
responsible for compliance could void the user’s authority to operate the
equipment.
NOTE: This equipment has been tested and found to comply with the limits
for a Class B digital device, pursuant to Part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful
interference in a residential installation. This equipment generates, uses and
can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by
turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
SAVE THESE INSTRUCTIONS
Section 2. System Overview
2.1 System Component Specifications and Dimensions
Specifications (USA and Canada)
Power Supply
120 VAC; 60 Hz; 3 A
Contact Rating
High voltage – 25 A; 3HP @ 240 VAC
1½ HP @120 VAC
1500 Watts Incandescent
Low Voltage – Class 2, 1 A @ 24 VAC
Service Switch
All Circuits (located at Power Center in Service Mode)
Dimensions
Suitable Listed Breakers (Available Locally)
Manufacturer| CIRCUIT BREAKER| Filler Plate
Cutler-Hammer® 1
Murray® 2
Siemens ® 3
Square DC® 4
Thomas & Betts®5| Single Double Twin Quad GFCB
BR
MP-T
QP
HOM
TB| BR
MP-T
QP
HOM
TB| BR
MH-T
QT
HOMT
TBBD| BQC
MH-T
QT
HOMT
TBBQ| GFCB
MP-GT
QPF
HOM
GFB| BRFP
LX100FP
QF3
HOMFP
FP-1 C-TB
- Cutler-Hammer is a registered trademark of Cutler-Hammer, Inc.
- Murray is a registered trademark of Briggs & Statton Corp.
- Siemens is a registered trademark of Siemens Energy and Automation, Inc.
- Square D is a registered trademark of Square D Company.
- Thomas & Betts is a registered trademark of Thomas & Betts Corp.
2.2 Basic Plumbing
2.2.1 Plumbing for Pool and Spa Combination
The intake and return JVA’s turn si mul ta neous lyso when the spa button is
pressed on the AquaLink RS control panel, water circulation switches between
pool and spa (consult the Jandy Valve Actuator Installation and Operation
Manual to ensure that the JVA’s are synchronized and rotate properly). Please
consult the Jandy Valve® Plumb ing Manual for further examples of pool/spa
plumbing. For pool only/spa only or dual equipment plumbing, please refer to
the Jandy Valve Plumbing Manual for further examples.
NOTE When the fi lter system is shared (a pool/spa combo), the spa water
must be able to overfl ow back to the pool.
2.2.2 Booster Pump Pool Cleaner Plumbing
2.2.3 Non-Booster Pump Pool Cleaner Plumbing
Section 3. Installation
3.1 Power Center Mounting
-
The power center should be located at or near the equipment pad. Locate the power center at least five (5) feet or more away from pool/spa and five (5) feet off the ground. All national, state, and local codes are applicable.
NOTE For Canadian installations, the power center must be at least three (3) meters (9.8 feet) away from the pool/spa and 1.5 meters (5 feet) above the ground. -
Use the mounting brackets and instructions provided with the standard power center and/or sub-panel power center.
-
Sub-panel power centers have special code requirements. Be sure to follow all applicable local and state codes to insure safe installation.
NOTE The power center is not to be considered as suitable for use as service equipment. Therefore, it is required to have the appropriate means of disconnection, circuit isolation, and/or branch circuit protection installed upstream of the power center.
3.2 High Voltage Wiring
3.2.1 System Power
**WARNING**
Potentially high voltages in the AquaLink Power Center can create dangerous
electrical hazards, possibly causing death, serious injury or property damage.
Turn off power at the main circuit of the AquaLink Power Center to disconnect
the Power Center from the system. To properly and safely wire the system, be
sure to carefully follow the applicable requirements of the National
Electrical Code® (NEC®), NFPA70 or the Canadian Electrical Code (CEC®), CSA
C22.1. All applicable local installation codes must also be adhered to.
Depending on the amount of equipment being controlled, run ½” or ¾” conduit
from the power supply panel to the bottom of the power center.
If you are using the sub-panel power center, wire power to the appropriate
breakers. Pull in appropriate wire for equipment. Each piece of equipment
requires its own high voltage relay.
Connect 120 volts for US/CAN to the power center terminals. Connect equipment
ground(s). See Figures 3 and 4.
![Jandy AquaLink RS Control Systems
- Power Center](https://manuals.plus/wp-content/uploads/2023/04/Jandy- AquaLink-RS-Control-Systems-Power-Center.png)
3.2.2 3HP (Standard) Relays
For each piece of 240 volt equipment to be controlled, connect line power to
the two (2) line terminals and connect equipment power to the two (2) load
terminals on the same relay.
For each piece of 120 volt equipment, connect power to a line terminal and
connect equipment to a load terminal on the same relay.
NOTE The following are the contact ratings for 3HP (Standard) Relay. DO
NOT exceed any ratings.
3 HP @ 240 VAC; 1½ HP @ 120 VAC; 25 Amps; 1500 Watts.
3.2.3 Bonding the Power Center
Install a bonding lug to the power center enclosure.
Connect the bond lug, using a #8 solid copper core wire, to an approved earth
ground (an approved ground stake, grid, or conducting metal water pipe buried
to a sufficient depth). See Figure 5.
The National Electrical Code® (NEC® in the United States) or the Canadian
Electrical Code (CEC in Canada) requires pool equipment to be bonded to each
other. Check your local codes to determine if the NEC or CEC and/or other
local installation codes are enforced by the Authority Having Jurisdiction
(AHJ in the United States) or the local competent authorities in Canada. A
solid, copper 8.37 mm2 (8 AWG) wire is required per the NEC, and 13.3 mm²
(6AWG) per the CEC, for bonding the equipment to a permanent bonding
connection that is acceptable to the local AHJ or the local competent
authorities in Canada.
Refer to your locally enforced codes for the acceptable bonding wire gauge. Do
not use the power center as the common bonding point. Each piece of non-
related pool equipment requiring a ground should also be bonded to the common
approved bonding point.
National Electrical Code® (NEC® ) requires bonding of the Pool Water. Where
none of the bonded pool equipment, structures, or parts are in direct
connection with the pool water; the pool water shall be in direct contact with
an approved corrosionresistant conductive surface that exposes not less than
5800 mm² (9 in²) of the surface
area to the pool water at all times. The conductive surface shall be located
where it is not exposed to physical damage or dislodgement during usual pool
activities, and it shall be bonded in accordance with the bonding requirements
of NEC Article 680. Refer to locally enforced codes for any additional pool
and spa bonding requirements
3.2.4 High Voltage Underwater Lighting GFCI Wiring
CAUTION
A Ground Fault Circuit Interrupter (GFCI) must be provided in high voltage
pool/spa lights. The conductors on the load side of the GFCI device shall not
occupy conduit, boxes, or enclosures containing other conductors unless the
other conductors are also on the load side of a GFCI, or unless the other
conductors are segregated, separated by barrier(s) or routed and secured to
provide permanent spacing from the conductors on the load side of the GFCI.
Refer to local codes for complete details.
CAUTION
The AquaLink RS system is for fixed installations only and to be used in
conjunction with swimming pool equipment. Also refer to the installation
instructions relating to the swimming pool equipment for which the system will
be an integral part. The system is to be supplied through a residual current
device (RCD) with a rated residual operating current of 30mA. If the supply
cord is damaged it must be replaced by the manufacturer or its service agent
or similarly qualified person in order to avoid hazard.
-
For a standard power center, install a GFCI receptacle or RCD next to the breaker panel.
For a sub-panel power center install a GFCI receptacle in the power center (use the knockout provided on the right side of the subpanel power center). See Figure 6. -
Connect neutral and hot wire (from circuit breaker) to the LINE side of the GFCI.
-
Connect neutral (white wire) and the hot (black wire) from the light to the LOAD side of the GFCI.
-
Connect ground from the light to the grounding bar inside the power center.
3.2.5 Jandy Pool and Spa Lights Wiring
The Jandy Pool and Spa Lights can be wired into the Jandy AquaLink RS control
system to ensure simplified operation of the lights, as well as a means to
synchronize the color change function. Connect the lights to one of the
auxiliary relays in the power center.
NOTE It is recommended to connect one (1) light per relay so each light
can be controlled separately.
However, up to four lights can be connected on a single relay. If there are
more than four (4) lights installed on one AquaLink RS system, ensure there is
more than one (1) auxiliary relay available in the Power Center.
Refer to Figures 7 and 8 to connect the Jandy pool and spa lights to the power
center.
NOTE The Jandy pool and spa lights are available in 120-volt and 12-volt
versions. If installing a 12-volt light, a 120-volt/12-volt step-down (AC)
transformer must be used. For more information about 12-volt installations,
refer to the Jandy Digital,Color Changing,Underwater Pool and Spa Lights
Installation and Operation Manual.
|
---|---
3.2.6 Infinite Watercolors Nicheless LED Light
WARNING
RISK OF ELECTRICAL SHOCK OR ELECTROCUTION, which could result in serious
injury or death. A Ground Fault Circuit Interrupter (GFCI) for 120 Volt
transformers should be used if required by the transformer manufacturer or if
required by the local applicable code and/or Authority Having Jurisdiction
(AHJ). When a GFCI is used, the conductors on the load side of the GFCI
circuit shall not occupy conduit, boxes, or enclosures containing other
conductors unless the additional conductors are also protected by a GFCI.
Refer to local codes for complete details.
WARNING
RISK OF ELECTRICAL SHOCK OR ELECTROCUTION, which could result in serious
injury or death. The Jandy Infinite WaterColors Nicheless LED Lights are only
available for 14 Volt AC power. For supply connection, use only an isolating
low voltage power supply with ungrounded output, evaluated and listed by a
NRTL for swimming pool use.
The Jandy Infinite WaterColors Nicheless LED Lights must be controlled by the
Infinite WaterColors LED Light Controller and AquaLink automation system.
Refer to Figure 9 to connect the Jandy Infinite WaterColors Nicheless LED
Lights and to the Infinite WaterColors LED Light Controller manual for
connecting the Infinite WaterColors LED Light Controller to the AquaLink
automation system.
- Knock out an opening in the right compartment.
- Run low voltage light through a cord grip and secure to the enclosure
- Connect the low voltage wires black to orange and white to orange. See Figure 9.
3.2.7 Wire Gauge and Length
CAUTION
Jandy® Nicheless Underwater LED Lights are low voltage fixtures. Improper wire
gauge and wire length can effect the performance of these products. Follow the
guidelines below to determine the proper operation and optimum performance of
the lights.
The output voltage of the Infinite WaterColors LED Light Controller is 14 VAC
to accommodate the voltage drop across cords up to 200 ft. Installations
should not exceed 200 ft.
NOTE Each color mode has a slightly different power draw
3.2.8 Fourteen (14) Volt Installation
The Infinite WaterColors LED Light Controller IS required to power Infinite
WaterColors Lights.
NOTE For optimum performance do not exceed the load factor specified by
the instructions included with the transformer.
3.2.9 RS-485 Connection
See low voltage wiring, Section 3.3.
To ensure maximum safety, use only the Jandy Infinite WaterColors LED Light
Controller listed for swimming pool and spa use.
CAUTION
To prevent risk of fire which could result in property damage, and to ensure
optimum performance, do not exceed the load factor specified in the
instructions provided by the transformer manufacturer.
3.2.10 Variable Speed Pump Wiring (High Voltage)
With the AquaLink it is possible to control up to sixteen (16) variable speed
pumps. This section describes how to supply AC power to the pumps. For
instructions on how to
connect the low voltage communications wiring (RS485) see Section 3.3.3.
3.2.11 Jandy Variable Speed Pump
For pump high voltage wiring specifications and instructions, please refer to
the installation/operation manual of the corresponding pump.
WARNING
Potentially high voltages in the AquaLink Power Center can create dangerous
electrical hazards, possibly causing death, serious injury or property damage.
Turn off power at the main circuit of the AquaLink Power Center to disconnect
the Power Center from the system. To properly and safely wire the system, be
sure to carefully follow the applicable requirements of the National
Electrical Code® (NEC® ), NFPA 70 or the Canadian Electrical Code (CEC® ), CSA
C22.1. All applicable local installation codes must also be adhered to.
To connect a Jandy variable speed pump to a dedicated circuit breaker.
- Make sure all electrical breakers and switches are turned off before wiring the motor.
- Make sure the wiring voltage is appropriate for the pump model being used. Refer to the pump installation manual for specifications.
- Use #12 AWG for wire runs up to 100 feet and #10 AWG for lengths longer than 100 feet. When in doubt use a heavier gauge (larger diameter) wire. Heavier gauge will allow the motor to run cooler and more efficient.
- Make sure all electrical connections are clean and tight.
- Strip the wires to the appropriate length so they do not overlap or touch when connected.
- Permanently ground the motor using the green ground wire, as shown in Figure 10. Use the correct wire size and type specified by National Electrical Code (NEC) and the Canadian Electrical Code (CEC). Make sure the ground wire is connected to an electrical service ground.
- Bond the motor to the pool structure in accordance with the National Electrical Code (NEC) and the Canadian Electrical Code (CEC). Use a solid No. 8 AWG or larger copper conductor (US). Run a wire from the external bonding lug to the pool bonding structure, as shown in Figure 10.
- Connect the red and black wires of the pump to the two line side connections on the filter pump relay as shown in Figure 10.
- Refer to low voltage Section 3.3.4 to connect the RS-485 communication wiring.
3.2.12 Pentair® Variable Speed/Flow Pumps
WARNING
Potentially high voltages in the AquaLink Power Center can create dangerous
electrical hazards, possibly causing death, serious injury or property damage.
Turn off power at the main circuit of the AquaLink Power Center to disconnect
the Power Center from the system. To properly and safely wire the system, be
sure to carefully follow the applicable requirements of the National
Electrical Code® (NEC®), NFPA 70 or the Canadian Electrical Code (CEC® ), CSA
C22.1. All applicable local installation codes must also be adhered to.
To connect a Pentair variable speed/flow pump to the AC power.
- Make sure all electrical breakers and switches are turned off before wiring the motor.
- Make sure that the wiring voltage is 230 VAC.
- Use #12 AWG for wire runs up to 100 feet and #10 AWG for lengths longer than 100 feet. When in doubt use a heavier gauge (larger diameter) wire. Heavier gauge will allow the motor to run cooler and more efficient.
- Make sure all electrical connections are clean and tight.
- Cut the wires to the appropriate length so they do not overlap or touch when connected.
- Permanently ground the motor using the green ground wire, as shown in Figure 11. Use the correct wire size and type specified by National Electrical Code® (NEC®) and the Canadian Electrical Code (CEC®). Make sure the ground wire is connected to an electrical service ground.
- Bond the motor to the pool structure in accordance with the National Electrical Code (NEC) and the Canadian Electrical Code (CEC). Use a solid No. 8 AWG or larger copper conductor (US). Run a wire from the external bonding lug to the pool bonding structure, as shown in Figure 11.
- Connect the two red hot wires of the pump to the two line side connections on the filter pump relay as shown in Figure 11.
- Refer to low voltage Section 3.3.4 to connect the RS-485 communication wiring.
3.3 Low Voltage Wiring
Minimum wire size should be 22 AWG. If wire run is more than 300 feet, larger
wire should be used. Two (2) RS485 4 pin red terminals are provided on the RS
power center board. For additional connections utilize a multiplex PCB, part
6584.
3.3.1 Bezel Connection
Plug the 24 VAC power plug from the transformer into its 3-pin terminal on the
back of the power center PCB as shown in Figure 12. Mount the bezel to the
power center using the screws provided.
3.3.2 Control Panel Cable to Power Center PCB
Make provision for the four conductor, 22 AWG or larger cable to be run
between the indoor control panel and the power center. Never run high voltage
and low voltage in the same conduit. Pull cable through the knockout with the
Heyco®1 fitting and into the low voltage compartment. Strip back jacket 6”.
Strip each wire a ¼” and connect to the red, 4-pin connector on the power
center PCB. A multiplex kit may be required if there are more than two cables
running to a red, 4-pin connector. See Figure 13.
3.3.3 Variable Speed Pump to Power Center PCB Cable
The low voltage wiring for the variable speed pumps consists of the RS485
communications four conductor, 22 AWG or larger cable. Make provision for the
cable to be run between the pump and the power center. Never run high voltage
and low voltage in the same conduit. Pull cable through the knockout with the
Heyco fitting and into the low voltage compartment. Strip back jacket 6”.
Strip each wire a 1/4” and connect to the red, 4-pin connector on the power
center PCB. A multiplex kit may be required if there are more than two cables
running to each of the red, 4-pin connectors on the power center PCB. See
Figure 14.
3.3.4 Wiring the Jandy Variable Speed Pump
Connection from the AquaLink power center PCB to the Jandy ePump is via an
RS485 cable. The cable pin out is shown below.
RS485 Wire Connections for Jandy ePump
This side connects to J1 or J4 of power center PCB or to the multiplexer PCB.|
This side of the cable connects to the Jandy ePump.
Pin 1 (no connection, not used)| Pin 1 no connection, not used)
Pin 2 (SD+)| Pin 2 (SD+)
Pin 3 (SD-)| Pin 3 (SD-)
Pin 4 (no connection, not used)| Pin 4 (no connection, not used)
3.3.5 Jandy Variable Speed Pump DIP switch settings
Dipswitch Settings with Local Controller
Please refer to the following table for required settings for Dip switches 3-4
when the pump is connected to a local controller.
Local Controller DIP Switch Settings
Controller| Switch 3| Switch 4
JEP-R| OFF| OFF
iQPUMP01| OFF| OFF
SpeedSet| Dip Switch 3-4 settings are only import- ant when connected to a
Jandy automa- tion system using SpeedSet automation pass-through wiring
connection on the bottom of the controller.
If applicable, please see following sec- tions.
Dip Switch Settings with Automation
Dip Switch 3-4 setting rules are not common across all Jandy automation
systems. Please reference the following sections to understand the required
settings.
For Jandy Aqualink RS Automation System users, a 2022 mid-year update changes
the method in which pumps in this manual interact with Jandy Aqualink RS
systems. Refer to the RS manual for more information.
Pre-2022 Aqualink RS Firmware Rev_V and Earlier
Aqualink RS systems using firmware Rev V and earlier, manufactured prior to
mid-year 2022, support up to 4 variable-speed pumps. Each pump is assigned an
address of 1 through 4 using Dip Switches 3-4 on the pump. Use the table below
for pump address assignment settings.
These settings are used when connected to the RS485 connection on the pump or
when connected to the pump using a SpeedSet controller’s automation pass-
through wiring connection on the bottom of the controller.
Local Controller DIP Switch Settings
Address| Switch 3| Switch 4
Pump 1| OFF| OFF
Pump 2| ON| OFF
Pump 3| OFF| ON
Pump 4| ON| ON
2022 Aqualink RS Firmware Rev W and Later
Aqualink RS systems using Rev W and later, manufactured after mid-year 2022,
support up to 16 variable-speed pumps that utilize a preassigned PUMP ADDRESS.
Dip Switches 3-4 are not utilized. Pumps in this manual are all assigned a
unique PUMP ADDRESS at the factory. The PUMP ADDRESS label can be found on the
pump motor in the location shown below.
When setting up pumps using this method, the pump address of each pump will
initially appear in the unassigned pump address section of the iAqualink App
or other automation setup device.
Utilize the App or other device to complete pump setup.
3.3.6 Wiring the Pentair® Pump
The Pentair IntelliFlo® VF LCD control panel is disabled when communicating
with the AquaLink system and “DISPLAY NOT ACTIVE” will be displayed. Note that
AquaLink RS will not start communicating with the Pentair IntelliFlo VF until
it has been configured accordingly. See the AquaLink Owner’s Manual (P/N
6593L) for more information.
Connection from the AquaLink power center PCB to the Pentair variable
speed/flow pumps is via the twowire cable (Pentair P/N 350122). The cable pin
out is shown in Figure 16.
In order to operate up to four (4) Pentair variable speed pumps the motor must
be addressed. Refer to the Pentair manual for instructions.
Jandy RS485 (RED) Connector | Pentair RS485 Cable Assembly |
---|---|
Pin 1 (no connection) | |
Pin 2 | Yellow Wire |
Pin 3 | Green Wire |
Pin 4 (no connection) |
3.4 Heater Connection
The heater connection section applies to all heaters or heat pumps with
thermostatic circuitry of 24 VAC or less.
NOTE If you are connecting a heater with thermostatic circuitry of 120
VAC or greater, do not connect to the green, 10-pin terminal bar. Instead
connect the heater to a high voltage relay in the power center and plug the
spare relay into the electric heater relay socket on the power center PCB.
3.4.1 Jandy Heater Connections
- Connect two #14 gauge wires, designed for use in hot environments, to the #1 and #2 terminals on the green, 10-pin terminal bar.
- Connect the other ends of the #14 gauge wires from step 1 to the fireman’s switch terminal bar in place of the factory installed wire loop.
- Do not disconnect high limit or pressure switches.
- Turn the heater thermostat(s) to maximum setting.
- Turn the heater switch to the ON position. For dual thermostat heaters turn switch to Spa position.
3.4.2 Guidelines for Sophisticated Diagnostic Communication to Jandy JXi™ Heaters
- Confirm the JXi heater software and AquaLink RS software revisions are compatible (see tables below).
- Run a 4-conductor cable from the JXi heater or the Air Energy heat pump power interface red, 4-pin connector to the power center red, 4-pin connector (see Figure 18).
JXi Power Interface Software Revision | AquaLink RS Software Revision |
---|---|
Any | N or Later |
NOTE If connecting more than two (2) items to the power center red, 4-pin connector, a multiplex PCB (P/N 6584) is required.
3.4.3 Other Brands Heater and Pump Connections
To set up heater connections on heaters and heat pumps made by other
manufactures, please refer to the Installation Manual provided with these
heaters and heat pumps.
3.4.4 Guidelines for a Gas Heater and a Heat Pump/Chiller Installation
NOTE The following steps provide the procedure for installing a Jandy JRT
Series Heat Pump and controlling it with the solar pump relay. If your Jandy
JRT Series Heat Pump is equipped with an RS485 Interface then you do not need
to use the solar pump relay to control it. You can control the heat pump via
the RS485 interface of the AquaLink RS.
- Set DIP switch S2 bit 1 to the ON position. The AquaLink will auto-relabel solar as heat pump.
- To run the wires from the heat pump control panel, remove the five (5) screws that attach the service/wiring cover panel to the heat pump. See Figure 19.
- Run the wires from the heat pump control panel through the wiring conduit located on the outer right hand side of the heat pump.
- Connect the heat pump to a standard relay, then connect the relay to the solar pump output on the AquaLink PCB.
- The solar button will activate the heat pump/ chiller and the pool and/or spa heater buttons will activate the gas heater. In this manner the pool or spa can be heated or chilled by the heat pump, the gas heater or both.
NOTE To program the heat pump control panel, refer to the Heat Pump
Manual.
3.5 Temperature Sensors
-
Drill 3/8” hole in pipe between filter pump and filter and install the water temperature sensor per instructions (make certain the o-ring is in place).
-
Install air temperature sensor outside the power center can, not in direct sunlight and away from motors and other heat sources.
-
Install solar temperature sensor (optional) adjacent to solar panels.
NOTE If a solar sensor is not installed, the solar button can be labeled and used as an extra auxiliary. -
Run the wire to the power center, through the low voltage raceway. Cut off excess wire. Strip the wire jacket back 6”, then strip each wire ¼”. Connect sensor wires to the green, 10-pin terminal bar (see Figure 20).
3.6 Jandy Valve® Actuators
NOTE Mount the JVA’s according to the Jandy Valve Actuator Installation
and Operation Manual. JVA cable is type SJW-A marked water resistant class 3
cable and does not require conduit.
Knockouts and Heyco® fittings are provided in the low voltage raceway.
-
Route the JVA wire to the power center.
-
Run the wire through the low voltage raceway and plug the JVA connectors into their proper sockets (see Section 6. Power Center Wiring Diagram). Verify that the JVA on the suction plumbing is connected to the Intake JVA Socket, and the discharge plumbing is connected to the Return JVA Socket.
NOTE Do not coil the JVA wires inside power center. To shorten the wire, remove the JVA cover and disconnect the wire. Shorten, strip, and reconnect. -
For alternate plumbing configurations the JVA cam settings can be adjusted as needed. See the Jandy Valve Actuator Installation and Operation Manual, Cam Setting Chart for proper settings.
3.7 Jandy TruSense Water Chemistry Analyzer
NOTE: Always install TruSense after the filter and before the heating
system and water care devices (saltwater chlorinator cell, chlorinator, acid
injection…).
- Run the RS485 cable from the TruSense Water Chemistry analyzer to the AquaLink RS power center.
- Route the four conductor RS485 cable through the low voltage raceway and connect the red connector to the automation system. See Figure 21b.
3.8 Auxiliary Power Centers
AquaLink RS All button models support one (1) auxiliary power center.
AquaLink RS models support a maximum of three (3) auxiliary power centers.
- The auxiliary power centers may be wired “in series”, starting from the primary power center (solid line) or wired “in parallel” from the primary power center (dashed line). See Figure 22.
- Run four conductor, 22 AWG or larger cable between the red, 4-pin ter mi nal bars in each power center.
NOTE
- All temperature sensors, heater connections and the main fi lter pump must be wired to the primary power center.
- Never put more than two (2) wires into each of the pins of the red, 4-pin terminal bar (use a Jandy® multiplex board).
- If more than one auxiliary power center is installed, set the jumpers as shown in Figure 23.
NOTE In the 2nd, 3rd, or 4th power centers, light dimming relay must be connected to auxiliary B5-B8, C5-C8, or D5-D8.
3.9 OneTouch Control Panel Indoor Installation
3.9.1 Surface Mount OneTouch Indoor Installation
-
With the aid of the homeowner, find the best location for the control panel.
-
Place surface mount box in the location chosen for the control panel. Mark the holes for drilling.
Drill 3/16” holes for the sheet rock anchors and a 1¼” hole for the 4-conductor cable. -
Run the 4-conductor cable from the power center to the location of the control panel (see Figure 24).
-
Pull the 4-conductor cable through the hole in the wall and the hole in the surface mount box. Mount the box to the wall using the screws pro vided.
-
Wire the 4-conductor cable to the red, 4-pin terminal bar (see Figure 25). Push the 4-pin terminal bar onto the back of the OneTouch PCB. Place the PCB with LCD and buttons back into the box. Insert the screws and hand tighten.
Do not overtighten. Snap the faceplate into place.
3.9.2 Flush Mount OneTouch Indoor Installation
-
With the aid of the homeowner, find the best location for the control panel.
-
Place the flush mount box in the location chosen for the control panel. Level the box and trace around the outside of the box with a pencil. Cut the hole being careful not to oversize.
-
Route the 4-conductor cable from the power center to the indoor control panel.
-
Pull the 4-conductor cable through the hole in the wall and the hole in the flush mount box.
Push the flush mount box into the hole in the wall with the correct orientation (see Figure 26). -
Depending on what size sheet rock (5/8” or 1/2”), determine which side of the cleat is to be facing you (see Figure 27).
-
Insert a screw through the screw boss (see Figure 26). Put a cleat into the top “U” shaped hole. Hand tighten the screw and repeat the process for the bottom cleat.
-
Wire the 4-conductor cable to the red, 4-pin terminal bar. Push the 4-pin terminal bar onto the back of the OneTouch PCB. Place the OneTouch PCB back into the Flush Mount Housing. Insert the screws with rubber washers and hand tighten. Do not overtighten. Snap the faceplate into place.
![Jandy AquaLink RS Control Systems
- Cleat Orientation](https://manuals.plus/wp-content/uploads/2023/04/Jandy- AquaLink-RS-Control-Systems-Cleat-Orientation.png)
3.9.3 Multiple AquaLink RS OneTouch Control Panel Indoor Installation
The AquaLink RS allows each system to support a maximum of 4 indoor control
panels (see Figure 28). The control panels may be wired “in series” starting
from the first control panel (solid lines), or wired “in parallel” from the
AquaLink RS power center (dotted lines), or any combination of the two. In
other words, any number of indoor control panels and/or power centers can be
connected by means of the red, 4-pin terminal bar in any combination of
“series” or “parallel” wiring.
NOTE Minimum wire size should be 22 AWG. If more than one control panel
is installed, or the length of run is more than 300 feet, larger wire should
be used.
3.9.4 AquaLink RS OneTouch Control Panel Jumper Settings
Move these jumpers only when installing more than one control panel on a
system (see Figure29). The jumpers are used to give each control panel a
unique system address. When replacing an existing control panel, change the
jumper settings to match those on the one being replaced.
3.10 iAquaLink Web-Connected Device Installation
The iAquaLink device can be installed outdoors, on the equipment pad, or
inside your home with a choice of wired or wireless connection.
The wireless iAquaLink device will transmit through walls and around corners.
The transceivers do not require line of sight to communicate. Steel framing,
aluminum siding, wrought iron, cyclone fences, leaded glass, and other 2.4 GHz
frequency items may inhibit/prevent communication between the iAquaLink J-Box
and the WiFi Access Point.
3.10.1 Outdoor Installation
WARNING
Potentially high voltages in the power center can create dangerous electrical
hazards, possibly causing death, serious injury or property damage. Turn off
power at the main circuit feeding the power center to disconnect the power
center from the system.
Never run high voltage and low voltage in the same conduit.
-
Turn off all power to the power center.
-
Mount the outdoor iAquaLink J-box at least six (6) feet (1,8 m) above the ground, at least ten (10) feet (3 m) from any motor or air blowers that may be in the vicinity, and at least five (5) feet (1.5 m) away from other transceiver J-boxes.
See Figure 31.
NOTE To improve performance of the transceiver, mount the iAquaLink device more than six (6) feet (1.8 m) above the ground. -
Open the door to the power center and remove the dead panel.
-
Pull cable through a knockout and into the low voltage area.
-
Strip back the insulation jacket of the cable approximately 6” (15 cm).
-
Strip each wire ¼” (6 mm) and connect to the red, wire connector on the power center PCB. A multiplex kit (P/N 6584) may be required if there are more than two (2) cables running to a red, wire connector on the PCB.
3.10.2 Indoor Installation
WARNING
Potentially high voltages in the power center can create dangerous electrical
hazards, possibly causing death, serious injury or property damage. Turn off
power at the main circuit feeding the power center to disconnect the power
center from the system.
NOTE When installing the iAquaLink device indoors, if another AquaLink
wired interface (ie. OneTouch™, All-button, etc.) is mounted indoors, the two
devices may share an RS-485 (4-wire) cable to communicate from inside the home
to the AquaLink control panel. In this scenario, the RS485 cable from the
iAquaLink device should be connected to the red 4-wire connector in the back
of the wired interface. The red 4-wire connector will then have two cables
running to it: the cable from the iAquaLink device, and the cable that runs to
the AquaLink system on the equipment pad.
Never run high voltage and low voltage in the same conduit.
-
Turn off all power to the power center.
-
Find a suitable place inside your home to mount the iAquaLink device.
-
Install the iAquaLink device at least six (6) feet (1.8 m) above the ground and at least five (5) feet (1.5 m) away from other transceiver J-boxes.
NOTE To improve performance of the iAquaLink device, you may wait to permanently mount it after it has been powered up. The signal strength indicator shown during the WiFi Hotspot method is a convenient way to determine & optimize signal strength between the iAquaLink device and the router. -
Open the door to the power center and remove the dead panel.
-
Pull cable through the knockout and into the low voltage area. See Figure 31.
-
Strip back the insulation jacket of the cable approximately 6” (15 cm).
-
Strip each wire ¼” (6 mm) and connect to the red, wire connector on the power center PCB. A multiplex kit (P/N 6584) may be required if there are more than two (2) cables running to a red, wire connector on the power center PCB.
3.10.3 Set Up the iAquaLink
Device for Wireless Connection
There are 2 ways to do this, the Hotspot Method and the WPS Method.
For wired connection skip to Section 4.5
Connect iAquaLink to the Home Network -WiFi Hotspot Method
-
Remove the two (2) screws from the cover of the iAquaLink J-box. Remove the gasket and cover.
See Figure 32. -
Inside the iAquaLink, toggle the WiFi – Wired switch to clear the Wi-Fi settings and put the iAquaLink in desired setup mode.
-
After clearing the WiFi settings and with the Wired/WiFi switch set to WiFi, use a smartphone or WiFi enabled device and go to WiFi settings.
Connect to the network labeled iAquaLink, followed by the last three digits of the iAquaLink device number. For example, iAquaLink ABC, if the last 3 digits of the device were ABC. -
Locate the device number on the side product label or the door hanger that came with the device
-
Some devices will automatically re-direct you to the Log In Screen. If not, open a browser and go to any web page, such as zodiacpoolsystems.com
-
iAquaLink will display the networks it detects, as well as signal strength. Select the network iAquaLink should use.
NOTE If prompted for a password, enter the password for the home network (caps sensitive). iAquaLink will disconnect from the smartphone at this point. -
Within 2 minutes, the yellow LED should turn solid yellow, indicating it is communicating with the router. When the green LED illuminates, the iAquaLink is connected.
Connect iAquaLink to the Home Network WPS (WiFi Protected Setup) Method
-
Remove the two (2) screws from the cover of the iAquaLink J-box. Remove the gasket and cover.
See Figure 32. -
Push the WPS Button on the pool owner’s router. To find it, look for the symbol or see the following notes.
NOTE Some brands use other names (like Quick Setup) or other icons (such as padlock or similar) for WPS. Some routers may have WPS disabled, which may require using the hotspot method.
The hotspot method is recommended for Apple routers -
Inside the iAquaLink, toggle the WiFi – Wired switch to clear the Wi-Fi settings and put the iAquaLink in desired setup mode.
-
After clearing the WiFi settings and with the Wired/WiFi switch set to WiFi, press and release the WPS button on the iAquaLink and wait for the small yellow LED, next to the WPS button to start blinking slowly.
-
Within 2 minutes, the yellow LED should stop blinking, and the green LED will illuminate. The iAquaLink is now connected.
For additional assistance, contact our Technical Support Department at 1-800-822-7933.
3.10.4 Set Up the iAquaLink Device for Wired Connection
NOTE To prevent potential Ethernet signal interference, order and install
part# R0616800. (Does not apply to wi-fi installations).
-
Remove the two (2) screws that secure the cover and gasket on the iAquaLink device.
Remove the gasket and cover. See Figure 33. -
Slide the Wired/WiFi switch to the WIRED position.
-
To allow the cable to exit the device, use needle nose pliers to remove the break-away piece.
Wrap the cable inside the J-box and route it through the break-away hole. -
Using an Ethernet (RJ45) cable connect the iAquaLink device to the homeowner’s router.
-
Reinstall the cover and gasket on the iAquaLink J-box with the two (2) screws previously removed.
3.11 Powered Hardware Connection Test:
- When installation is complete and safe, turn power On at the breakers to restore power for the RS system and any attached peripheral equipment.
- Verify that all LEDs in the Power Center are on.
- Verify that all connected peripheral equipment are connected and on.
- Verify that the OneTouch Control Panel and/ or the iAquaLink Web-connected Device are connected and on. All LEDs should show Green.
- Refer to the RS Control System Owner’s Manual, as well as the specific equipment Owner’s manual, for further details on programming all connected peripheral equipment.
3.12 Further Reference Information
For RS programming and operation, please refer to the AquaLink RS Control
System Owner’s Manual (P/N H0812100 Rev A) located at
www.jandy.com under the Residential Automation RS
Section.
Section 4. Troubleshooting
4.1 OneTouch Quick Troubleshooting Guide
Symptom | Problem | Possible Solution |
---|
Power center override switches operate when in service or time out mode, but
the control panel is completely dead (no lights on, no display).| Power supply
problem.| Check connection of the outside two wires (red & green) of the four
conductor cable. If wired correctly, check the voltage between these two
wires. Voltage for an All button system should be 7+ VDC and for a OneTouch
system, 8+ VDC (use the higher voltage for a mixed system).
All LEDs are on at the control panel and the part # and revi- sion letter of
the control panel software are displayed. The override switches at the power
center operate as they should.| Control panel is not commu- nicating with the
power center PCB.| Check the two center wires (black & yellow) of the four
conductor cable. Also check the installation of the CPU Board on the power
center PCB. If the PPD is not seated correctly the system will not commu-
nicate.
All LEDs are on at the con- trol panel and the part # and revision letter are
displayed, but override switches at the power center do not operate at all.|
1. Damaged or improperly installed CPU Board.
2. Damaged power center PCB.| 1. Check alignment of the CPU Board.
2. If CPU Board is installed correctly, replace the power center PCB.
Some buttons do not operate from the control panel, nor from the power center
override switches.| Wrong CPU Board chip installed at the power center PCB.|
Check part number and revision letter by pressing the reset button at the
control panel. The second part number and revision letter displayed is for the
CPU Board indicating which model.
System locked up.| Microprocessor locked.| Turn off power to the system and
turn back on.
Programs do not run at the correct time.| AquaLink does not display correct
time and date.| At the control panel set correct time and date.
One button on the Four Func- tion Remote or SpaLink® RS does not operate.|
Check programming first. If the Four Function Remote or SpaLink RS is
programmed correctly, the button may be shorted.| Replace the Four Function
Remote or SpaLink RS. Use MENU, REVIEW, SPA SWITCH (or SPA LINK) to check
programming.
Pool cleaner booster pump turns on without the filter pump being on, and can
run with the spa on.| System is not recognizing DIP switch S1-1 is on. Note:
before turning on any DIP switches, first turn off all equipment.| Turn off
all equipment buttons, then turn off power to the system, finally turn off,
then on, DIP switch S1-1. Turn on power and test system.
Model is one of the AquaLink RS Dual Equipment, message scrolls “ADJUSTABLE
FREEZE SENSOR NOT INSTALLED”.
System comes on at times that are not programmed.| Normal operation when a
Dual Equipment AquaLink RS is controlling a solar system and an adjustable
freeze sensor is not installed.| Either install the adjustable freeze sensor,
or wait 24 hours and this message will go away.
---|---|---
System comes on at times that are not programmed.| Phantom programs.| At the
control panel press MENU, then scroll to RE- VIEW. Make note of all programs
(the Four Function Remote setting, labels, and temperature settings) then turn
off all DIP switches and go to the control panel. CLEAR MEMORY, reprogram and
try system again.
Heater will not fire. Heater LED will not light in “Service Mode”.| Water
temperature sensor not installed or defective.| Check water temperature
sensor.
4.2 iAquaLink Troubleshooting Guide
Use the troubleshooting information in the following table for suggestions.
Symptom | Problem | Possible Solution |
---|
The iAquaLink is on and the startup screen is displayed. The override switches
at the power center operate as they should.| The iAquaLink is not
communicating with the power center PCB.| Check the cabling to the iAquaLink
Web-Connect device (all conductors).
The iAquaLink is on and the “Waiting for connection…” screen is displayed, but
override switches at the power center do not operate at all.| 1. Damaged or
improperly installed CPU board.
2. Wrong CPU board.
3. Damaged power center PCB.| 1. Check alignment of the CPU board.
2. Make sure that the CPU board is revision R or later for an AquaLink RS
system. Make sure that the CPU board is revision 6.0 or later for PDA control
system.
3. If CPU board is installed correctly, replace the power center PCB.
Some buttons do not operate from the iAquaLink, nor from the power center
override switches.| Wrong CPU board installed at the power center PCB.| Make
sure that the CPU board is revision R or later for an AquaLink RS system. Make
sure that the CPU board is revision 6.0 or later for PDA control system.
Programs do not run at the correct time.| The iAquaLink does not display
correct time and date.| At the iAquaLink screen, set correct time and date.
Communication is lost.| Signal Interference.| The wireless iAquaLink J-box
will stop communicating anytime interference (such as a 2.4 GHz device)
prevents a valid signal transmission. When communication is lost the iAquaLink
screen will lock on the “waiting for connection…” screen until a good link is
again achieved, usually within a few seconds.
4.3 LED Status Indicator Lights
Normal Operating Mode
Function | LED Indication |
---|---|
Power (Red) | ON = Power |
OFF = No power
Network Connection* (Yellow)| ON = Connected to Network Fast Flashing =
Communication
Slow Flashing/OFF = Not connected
Online Status** (Green)| ON = On-Line (connected to internet)
OFF = Off-Line
- Network Connection: the connection between the iAquaLink device and the Wi-Fi access point (ie. wireles router)
** Online Status: the connection to the internet. Only possible when Yellow LED indicates the iAquaLink is already connected or communicating to the router.
Section 5. Power Center Wiring Diagram for Combos and Onlys
Section 6. Power Center PCBDIP Switch Settings
6.1 DIP Switch Functions
S1 DIP #1 ON- AUX 1 Controls Pool Cleaner If you installed a booster pump for
a pool cleaner, the relay coil for the booster pump must be plugged into the
AUX 1 relay socket. If a non-booster pump cleaner is installed, plug the JVA
into the cleaner JVA socket. Turn ON DIP Switch #1.
- Main filter pump turns on whenever cleaner turns on.
- Cleaner will not turn on until filter pump has been on for three (3) minutes (to ensure priming of system).
- Cleaner turns off when water circulation is to spa.
- Cleaner turns off when spa spillover feature is activated.
- Cleaner turns off for three (3) minutes when solar is activated (to ensure air is purged from the system).
- AquaLink RS control panel display reads “CLEANER” rather than “AUX 1”.
S1 DIP #2 ON- AUX 2 Controls Low Speed of Filter Pump
Turn this switch ON if you want to control both speeds of a two-speed filter
pump. With this switch on, the filter pump button on the AquaLink RS control
panel will control high speed and the AUX 2 button will control low speed.
IMPORTANT You must also install a Jandy twospeed relay.
S1 DIP #3 ON- AUX 3 Controls Spa Spillover (Operates with Pool/Spa
Combination)
Turn this switch ON, and when the AUX 3 button on the AquaLink RS control
panel (or spa side switch) is pressed, the return valve actuator will rotate
to spa circulation. Because the intake valve actuator does not rotate, the spa
will fill with water and overflow into the pool.
NOTE Leave AUX 3 relay socket empty.
S1 DIP #4 ON- Heater Cool Down Disabled Turn this switch ON to disable the
heater cool down safety feature on the AquaLink RS.
WARNING
Turn this DIP Switch ON only if you are using an electric heater or a heat
pump that does not retain residual heat. If you are turning this switch ON for
service purposes, be sure to turn it back off to ensure that equipment
operates as specified.
S1 DIP #5 ON- Factory Use Only
This switch is used for calibration by Jandy® certified technicians only.
Please leave this switch in the OFF position.
S1 DIP #6 ON
Change spare AUX to activate when filter pump is on and system is in spa mode
(pool/spa combination units only). Spare AUX socket is on the front side of
the power center PCB.
S1 DIP #7 ON- Not Used
This switch only applies to DUAL EQUIPMENT systems. When OFF a separate heater
is used for the pool and spa. When ON the pool and spa share the same heater.
S1 DIP #8 ON- Heat Pump Instead of Gas Heater
Turn this switch ON if you have installed a heat pump instead of a gas heater.
After thermostat setting has been reached, heater will remain OFF for 5
minutes.
S2 DIP #1 ON- Heat Pump Priority
This switch is used for configuring solar priority or heat pump priority. Set
this switch to ON if heat pump priority will be used. Set this switch to OFF
if solar priority is to be used.
6.2 DIP Switch Settings for Pool and Spa Combination
S1 DIP Switch # | OFF | ON |
---|---|---|
1 | AUX1= any equipment | AUX1= Pool Cleaner |
2 | AUX2= any equipment | AUX2= Low Speed for a two-speed filter pump. |
Filter pump circuit becomes High Speed.
3| AUX3= any equipment| AUX3= Spa Spillover effect- Combination controls only.
4| Heater cool down operates.| Heater cool down disabled.
5| Normal operation| Factory adjustment- when this switch is on, tempera- ture
delays are eliminated and solar temperature is displayed.
Do not leave this switch in the ON position.
6| Spare Aux activates with Filter Pump when Spa OFF.| No change on Revision
“HH” or older PPD. With revi- sion “I” or newer, Spare AUX operation is
reversed.
7| Spare| No change on Combination or Only Controls.
8| After thermostat setting has been reached, heater will remain OFF for three
(3) minutes.| Heat Pump installed; after thermostat setting has been reached,
heater will remain OFF for five (5) minutes.
S2 DIP Switch #| OFF| ON
---|---|---
1| The AquaLink RS will be able to control a Solar Heating system (If a solar
sensor is connected to the solar sensor input).| The AquaLink RS will be able
to control a Heat Pump. (The AquaLink RS will not be able to control a Solar
Heating system.)
2| NOT USED
3| NOT USED
4| NOT USED
6.3 DIP Switch Settings for Pool or Spa Only
S1 DIP Switch # | OFF | ON |
---|---|---|
1 | AUX1= any equipment | AUX1= Pool Cleaner |
2 | AUX2= any equipment | AUX2= Low Speed for a two-speed filter pump. |
Filter pump circuit becomes High Speed.
3| AUX3= any equipment| No change
4| Heater cool down operates.| Heater cool down disabled.
5| Normal operation| Factory adjustment- when this switch is on, tempera- ture
delays are eliminated and solar temperature is displayed.
Do not leave this switch in the ON position.
6| Spare| No change
7| Spare| No change
8| After thermostat setting has been reached, heater will remain OFF for 3
minutes.| Heat Pump installed; after thermostat setting has been reached,
heater will remain OFF for 5 minutes.
S2 DIP Switch #| OFF| ON
---|---|---
1| The AquaLink RS will be able to control a Solar Heating system (If a solar
sensor is connected to the solar sensor input).| The AquaLink RS will be able
to control a Heat Pump. (The AquaLink RS will not be able to control a Solar
Heating system.)
2| NOT USED
3| NOT USED
4| NOT USED
6.4 DIP Switch Settings for Heat Pump Installation
This table shows how to configure the system for SOLAR PRIORITY or HEAT PUMP
PRIORITY.
DIP S2-1| GREEN 10-PIN TERMINAL BAR| RS485 HEAT PUMP|
DESCRIPTION
---|---|---|---
OFF| No sensor installed| Not connected| In this configuration there is no
Solar Heating and no Heat Pump. Extra AUX is available.
OFF| Sensor installed| Not connected| In this configuration there is Solar
Heating and there is Solar Priority. There is no Heat Pump.
OFF| Sensor installed| Connected| In this configuration there is Solar Heating
and there is Solar Priority. There is Heat Pump. There is Heat Pump Priority.
ON| No sensor installed| Not connected| In this configuration there is no
Solar Heating. There is a mechanically connected Heat Pump. There is Heat Pump
Priority (a limited implementation).
ON| Sensor installed| Not connected| In this configuration there is no Solar
Heating. There is a mechanically connected Heat Pump. There is Heat Pump
Priority (full implementation).
ON| Sensor installed| Connected| In this configuration there is no Solar
Heating. There is an RS485 controlled Heat Pump. There is Heat Pump Priority.
NOTES__
Zodiac Pool Systems LLC
2882 Whiptail Loop # 100
Carlsbad, CA 92010, USA
Jandy.com | 1.800.822.7933
Zodiac Pool Systems Canada, Inc.
2-3365 Mainway
Burlington, ON L7M 1A6, Canada
Jandy.ca | 1.800.822.7933
A Fluidra Brand
©2022 Zodiac Pool Systems LLC. All rights reserved. ZODIAC® is a registered
trademark of Zodiac International,
S.A.S.U., used under license. All other trademarks are the property of their
respective owners.
6594_REVT