TESUCO CO2 R744 Liquid Charging Kit Instruction Manual
- June 10, 2024
- TESUCO
Table of Contents
- CO2 R744 Liquid Charging Kit
- Product Information: CO2 R744 Liquid Charging Kit
- Product Usage Instructions
- INSTRUCTION SHEET
- PRE–CHARGING THE EQUIPMENT
- CONNECTING THE EQUIPMENT
- PURGING THE EQUIPMENT
- CHARGING THE UNIT WITH LIQUID CO2
- FINISHING AND DE-PRESSURISING THE SYSTEM
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
CO2 R744 Liquid Charging Kit
Product Information: CO2 R744 Liquid Charging Kit
The Tesuco R744 liquid CO2 charging kit is designed for high-speed charging on low-pressure cascade systems. It comes complete with a needle valve, safety relief valve, purge valve, pressure gauges, and a 5M hose assembly. This equipment can only be used on CO2 cylinders with a dip tube that allows for liquid CO2 to be withdrawn. These cylinders have black stripe lengthways on the outside of the cylinder.
The maximum design pressure of the kit is 40 BAR, and it is not suitable for use on transcritical systems or cascade systems with a design pressure above 40 BAR. The equipment should only be used by qualified persons who are wearing appropriate personal protective equipment. Liquid CO2 can cause cold burns, and the area where the equipment is being used should be well-ventilated as CO2 is an asphyxiant.
Product Usage Instructions
-
Step 1: Unpack the charging assembly and hose from the case.
-
Step 2: Connect the T30 inlet connection to the cylinder and tighten using a spanner.
-
Step 3: Connect the other end of the hose to the rack or unit to be charged at the correct inlet port.
-
Step 4: Ensure that at this stage the needle control valve and the purge valve are closed, and no pressure is reading o the gauges.
-
Step 5: Start by purging the air between the cylinder and the needle valve. Slowly open the CO2 cylinder valve, and the pressure gauge will go up indicating the cylinder pressure. Then open the purge valve. After doing that, open the needle valve slowly allowing a small amount of CO2 to vent through the purge valve. You will know it is venting as a white vapour will be released. Close the needle valve and then the purge valve and then close the cylinder valve. The area between the cylinder valve and the needle valve is now charged with liquid CO2. Now purge the air from the hose.
-
Step 6: The delivery gauge should be reading zero. At the unit or rack side, open the ball valve with a shifter. This will charge the hose with the system pressure, which can be confirmed by the delivery (left side) pressure gauge showing system pressure. Open the purge valve and allow the gas to vent for a few seconds. Close the purge valve. The hose will now be purged of any air and filled with gaseous CO2. The left gauge should be reading system pressure and the cylinder gauge reading cylinder pressure.
-
Step 7: To charge the rack system with liquid CO2, open the CO2 cylinder valve. Open the needle valve very slowly.
Caution:
Opening the valve too quickly may cause the Safety Relief Valve to vent. The
refrigeration unit is now charging. Cylinder scales can be used to measure the
weight of the CO2 being transferred.
Please note: This instruction is to be used as a guide only and does not override any normal standard operating procedures. Each system is different, please consult the operating manual before using this equipment.
INSTRUCTION SHEET
Part Number: TECK01
The Tesuco R744 liquid CO2 charging kit comes complete with a needle valve,
safety relief valve, purge valve, pressure gauges and 5M hose assembly. It is
packaged in a plastic case with a foam insert for protection of the equipment
when not in use.
This equipment can only be used on CO2 cylinders with a dip tube that allows
for liquid CO2 to be withdrawn. These cylinders have a black stripe length
ways on the outside of the cylinder.
DO NOT USE ON CO2 CYLINDERS WITHOUT A DIP TUBE
Only use this equipment for high-speed charging on LOW-PRESSURE Cascade
systems.
NOTE: This instruction is to be used as a guide only and does not override any normal standard operating procedures. Each system is different, please consult the operating manual before using this equipment.
PRE–CHARGING THE EQUIPMENT
Before charging the system with liquid using this equipment, the unit must be
charged with gaseous CO2 to 550 kPa using a standard CO2 regulator and hose c
onnected to a gaseous draw-off CO2 cylinder. RC1SCD10 CO2 Regulator 0 – 1,000
kPa G WSWIG3F 3M Inert gas hose 5/8-18 to !/4 SAE Flare
CONNECTING THE EQUIPMENT
Unpack the charging assembly and the hose from the case.
Connect the T30 inlet connection to the cylinder and tighten using a spanner.
Connect the hose to the ¼ SAE flare fitting on the outlet of the charging assembly.
Connect the other end of the hose to the rack or unit to be charged at the
correct inlet port.
Ensure that at this stage the needle control valve and the purge valve are
closed and no pressure is reading on the gauges.
PURGING THE EQUIPMENT
Start by purging the air between the cylinder and the needle valve. Do this by slowly opening the CO2 cylinder valve, the pressure gauge will go up indicating the cylinder pressure.
Then, open the purge valve. After doing that open the needle valve slowly allowing a small amount of CO2 to vent through the purge valve. You will know it is venting as a white vapour will be released.
Close the needle valve and then the purge valve and then close the cylinder
valve. The area between the cylinder valve and the needle valve is now charged
with liquid CO2.
Now purge the air from the hose.
The delivery gauge should be reading zero.
At the unit or rack side open the ball valve with a shifter.
This will charge the hose with the system pressure, which can be confirmed by the delivery (left side) pressure gauge showing system pressure.
Open the purge valve and allow the gas to vent for a few seconds.
Close the purge valve. The hose will now be purged of any air and filled with
gaseous CO2.
The left gauge should be reading system pressure and the cylinder gauge
reading cylinder pressure.
CHARGING THE UNIT WITH LIQUID CO2
To charge the rack system with liquid CO2 follow the following steps. Open the CO2 cylinder valve. Open the needle valve very slowly
Caution: Opening the valve too quickly may cause the Safety Relief Valve
to vent The refrigeration unit is now charging.
Cylinder scales can be used to measure the weight of the CO2 being transferred.
CO2 being transferred. Consult the manual to determine the amount to charge the unit with.
FINISHING AND DE-PRESSURISING THE SYSTEM
- Close the cylinder valve.
- Wait around 30 seconds, this allows any liquid to be drawn into the rack.
- Then close the ball valve on the rack.
- There will still be pressure reading on the gauges, to release this pressure and purge the equipment of liquid and gaseous CO2 open the purge valve until both the pressure gauges drop to zero.
- Close the purge valve, close the needle valve.
- Remove the hose from the rack and the charging unit and then remove the charging unit from the cylinder. Re-Pack the charging unit and hose back into the case.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>