DESCRIPTION

Part No: TECK01TESUCO TECK01 Liquid Charging Kit

The Tesuco® R744 liquid CO2 charging kit comes complete with needle valve, safety relief valve, purge valve, pressure gauges and 5M hose assembly. It is packaged in a plastic case with foam insert for protection of the equipment when not in use.
This equipment can only be used on CO2 cylinders with a dip tube that allows for liquid CO2 to be withdrawn.
These cylinders have a black stripe length ways on the outside of the cylinder.
DO NOT USE ON CO2 CYLINDERS WITHOUT A DIP TUBE
Only use this equipment for high speed charging of CO2 systems.

SAFETY

This instruction is to be used as a guide only and does not override any normal standard operating procedures. Each system is different, please consult the operating manual before using this equipment.TESUCO TECK01 Liquid
Charging Kit - Valve

WARNING
MAXIMUM DESIGN PRESSURE 175 BAR
HIGH SPEED LIQUID CHARGING SUITABLE FOR USE ON TRANSCRITICAL AND SUBCRITICAL SYSTEMS QUALIFIED PERSONS ONLY USING APPROPRIATE PPE

LIQUID CO2 CAN CAUSE COLD BURNS
ENSURE AREA IS WELL VENTILATED
CO2 IS AN ASPHYXIATE

PRE-CHARGING THE EQUIPMENT

TESUCO TECK01 Liquid Charging Kit - PRE-CHARGING THE
EQUIPMENTBefore charging the system with liquid using this equipment, the unit must be charged with gaseous CO2 to 550 kPa using a standard CO2 regulator and hose connected to a gaseous draw off CO2 cylinder.
RC1SCD10 CO2 Regulator 0 – 1,000 kPa
GWSWIG3F 3M Inert gas hose 5/8-18 to 1/4 SAE Flare

CONNECTING THE EQUIPMENT

Unpack the charging assembly and the hose from the case.

Connect the T30 inlet connection to the cylinder and tighten using the hand wheel.TESUCO TECK01 Liquid Charging Kit - hand wheel

Connect the hose to the 1/4 SAE flare fitting on the outlet of the charging assembly.
Connect the other end of the hose to the rack or unit to be charged at the correct inlet port.
Ensure that at this stage the needle control valve and the purge valve are closed and no pressure is reading on the gauges.TESUCO TECK01 Liquid
Charging Kit - charging assembly

Start by purging the air between the cylinder and the needle valve.
Do this by slowly opening the CO2 cylinder valve anti-clockwise with the needle valve closed.TESUCO TECK01 Liquid Charging Kit - air between the
cylinder

CONNECTING THE EQUIPMENT

TESUCO TECK01 Liquid Charging Kit - white vapour Then, open the purge valve. After doing that open the needle valve slowly allowing a small amount of CO2 to vent through the purge valve. You will know it is venting as a white vapour will be released. TESUCO TECK01 Liquid
Charging Kit - cylinder valveClose the needle valve and then the purge valve and then close the cylinder valve. The area between the cylinder valve and the needle valve is now charged with liquid CO2.TESUCO TECK01 Liquid Charging Kit - purge the airNow purge the air from the hose.
The delivery gauge should be reading zero.![TESUCO TECK01 Liquid Charging Kit

  • unit or rack](https://manuals.plus/wp-content/uploads/2023/10/TESUCO-TECK01 -Liquid-Charging-Kit-unit-or-rack.jpg)At the unit or rack side open the ball valve with a shifter.
    This will charge the hose with the system pressure, which can be confirmed by the delivery (lower) pressure gauge showing system pressure.TESUCO TECK01
Liquid Charging Kit - purge valveOpen the purge valve and allow the gas to vent for a few seconds.
    Close the purge valve. The hose will now be purged of any air and filled with gaseous CO2.
    The left gauge should be reading system pressure and the cylinder gauge reading cylinder pressure.

CHARGING WITH LIQUID CO2

TESUCO TECK01 Liquid Charging Kit - WITH LIQUID

The rack system can be charged with liquid CO2 follow these steps.
Open the CO2 cylinder valve.
Open the needle valve very slowly
Caution: Opening the valve too quickly may cause the safety relief valve to vent
The refrigeration unit is now charging.
Cylinder scales can be used to measure the weight of the CO2 being transferred.
CO2 being transferred. Consult the manual to determine the amount to charge the unit with.

FINISHING & DE-PRESSURISING THE SYSTEM

Close the cylinder valve.
Wait around 30 seconds, this allows any liquid to be drawn into the rack.
Then close the ball valve on the rack.
There will still be pressure reading on the gauges, to release this pressure and purge the equipment of liquid and gaseous CO2 open the purge valve until both the pressure gauges drop to zero.
Close the purge valve, close the needle valve.
Remove the hose from the rack and the charging unit and then remove the charging unit from the cylinder.
Re-Pack the charging unit and hose back into the case.

NOTES ——–
© Tesuco

HOSPITALITY, GAS SAFETY, INDUSTRIAL, SCIENTIFIC, MEDICAL

The information contained herein is provided to assist the operator in the safe use of the CO2 R744 Liquid Charging Kit. However, the ultimate responsibility for the safe use of this lies solely with the operator, including any requirements of associated Australian Standards.

Quality
ISO 9001
R744 Liquid Charging Kit
OI_TECK01_V01