Altronix T3SSK75F28 and T3SSK75F28D Trove S2 kits are pre-assembled and consist of Trove enclosures/backplanes with factory installed Altronix power supply/chargers and sub-assemblies. Both kits accommodate Lenel-S2 (S2 Security Platform) S2-INST Installation Kit for S2 Network Node for up to twenty-eight (28) (T2SSK7F8) doors in a single enclosure.
Configuration Chart
Altronix Model Number| 120VAC 60Hz Input Current A| Power Supply Board Input Fuse Rating| Power Supply Board Battery Fuse Rating| Nominal DC Output Voltage| ****
Maximum Supply Current for
Main and Aux. Outputs on Power Supply board and ACM8(CB)
Access Power Controllers outputs
| Fail-Safe/Fail-Secure Outputs| Additional Fused Outputs| ACM8
CB Board Input Fuse Rating
| ACM8 Board Output Fuse Rating| ACM8CB Board Output PTC Rating| ACM4
CB Board Input Fuse Rating
| ACM4 Board Output Fuse Rating| ACM4CB Board Output PTC Rating| PD16W Board
Output Fuse Rating| PD16WCB Board Output PTC Rating
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
Power Supply 1| Power Supply 2
DC| Aux| DC| Aux
Output Range VDC| Output Range VDC| Output Range VDC| Output Range VDC
T3SSK75F28
| ****
7.5
| eFlow104NB
6.3A/ 250V
eFlow102NB 5A/ 250V
| ****
15A/
32V
| ****
20.17-
26.4
| ****
20.28-
26.4
| ****
9.7-
13.2
| ****
10.03-
13.2
| 24VDC
9.4A
12VDC
10A
| ****
28
| ****
16
| ****
10A/
250V
| 3.5A/
250V
| | ****
10A/
32V
| 3A/
32V
| | 3.5A/
250V
|
T3SSK75F28D
| | ****
2.5A
| | ****
2.5A
| | ****
2.5A
Installation Instructions
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction. Product is intended for indoor use only.
- Remove backplane from enclosure.
- Do not discard hardware.
- Mark and predrill holes in the wall to line up with the top two/three keyholes in the enclosure.
- Install two/three upper fasteners and screws in the wall with the screw heads protruding.
- Place the enclosure’s upper keyholes over the two/three upper screws level and secure. Mark the position of the lower three holes.
- Remove the enclosure.
- Drill the lower holes and install the three fasteners.
- Place the enclosure’s upper keyholes over the two/three upper screws.
- Install the three lower screws and make sure to tighten all screws.
- Mount included UL Listed tamper switches Altronix Model TS112 or equivalent) in desired locations, opposite hinge. ;
- Slide the tamper switch bracket onto the edge of the enclosure approximately 2 from the right side.
- Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device.
- To activate alarm signal open the door of the enclosure.
- Mount S2-INST Installation Kit to backplane ACM8(CB) and PD16W(CB) for further installation instructions.
T3SSK75F28(D)
Access Controller Position Chart for the S2-INST Installation Kit
- Align S2-INST mounting holes with pems on TSS3.
- Attach S2-INST to backplane with lock nuts provided.
- Mount backplane to enclosure with hardware.
- Fasten TSS3 backplane to Trove3 enclosure utilizing hardware provided.
Trove3 Enclosure Dimensions H x W x D approximate
36.12x 30.125 x 7.06 917.5mm x 768.1mm x 179.3mm