Majestic ECHEL36IN-C 72 Inch Echelon II Contemporary Direct Vent Gas Fireplace Instruction Manual
- June 10, 2024
- Majestic
Table of Contents
ECHEL36IN-C 72 Inch Echelon II Contemporary Direct Vent Gas Fireplace
Product Information
The ECHELON-C SERIES is a gas fireplace available in six
different models: ECHEL36IN-C, ECHEL36STIN-C, ECHEL48IN-C,
ECHEL48STIN-C, ECHEL60IN-C, and ECHEL72IN-C. The appliance must be
installed in accordance with the manufacturer’s instructions and
the applicable safety standards.
Important Safety Instructions
-
Do not store the instruction manual inside the fireplace cavity
to avoid the risk of fire. -
Leave the manual with the appliance and retain a copy for
future reference. Do not store inside the appliance. -
The appliance should only be used with the type(s) of gas
indicated on the rating plate. It cannot be converted for use with
other gases unless a certified kit is used. -
A barrier designed to reduce the risk of burns from the hot
viewing glass is provided with this appliance and must be installed
for the protection of children and other at-risk individuals. -
Children should never be allowed to touch the glass, and the
glass should not be touched until it has cooled down.
Product Usage Instructions
Before using the ECHELON-C SERIES gas fireplace, please read the
installation manual carefully and follow the safety instructions.
Here are some usage instructions:
-
Make sure that the appliance is installed correctly and that
all components are in good condition. -
If you smell gas in your building, do not try to light the
appliance or touch any electrical switch. Leave the building
immediately and call your gas supplier from a neighbor’s phone. If
you cannot reach your supplier, call the fire department. -
Never leave children unattended near the fireplace, and make
sure that the barrier designed to reduce the risk of burns from the
hot viewing glass is installed properly. -
Do not modify the appliance or its components in any way. Any
modification could result in serious injury, death, or property
damage. -
Turn off the appliance and let it cool down before cleaning it
or performing any maintenance.
Following these instructions will help ensure safe and efficient
use of the ECHELON-C SERIES gas fireplace.
Installation Manual
Installation and Appliance Setup
CAUTION! Risk of Fire! DO NOT store instruction manuals inside fireplace
cavity. High temperatures could cause a fire.
INSTALLER: Leave this manual with the appliance, not inside the appliance.
CONSUMER: Retain this manual for future reference. Do not store inside the
appliance.
NOTICE: DO NOT discard this manual!
ECHELON-C SERIES
Models:
ECHEL36IN-C ECHEL36STIN-C ECHEL48IN-C ECHEL48STIN-C ECHEL60IN-C ECHEL72IN-C
WARNING: FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly
could result in serious injury, death, or property damage.
· DO NOT store or use gasoline or other flammable vapors and liquids in the
vicinity of this or any other appliance.
· What to do if you smell gas
– DO NOT try to light any appliance.
– DO NOT touch any electrical switch. DO NOT use any phone in your building.
– Leave the building immediately.
– Immediately call your gas supplier from a neighbor’s phone. Follow the gas
supplier’s instructions.
– If you cannot reach your gas supplier, call the fire department.
· Installation and service must be performed by a qualified installer, service
agency, or the gas supplier.
This appliance may be installed as an OEM installation in manufactured home
(USA only) or mobile home and must be installed in accordance with the
manufacturer’s instructions and the Manufactured Home Construction and Safety
Standard, Title 24 CFR, Part 3280 in the United States, or the Standard for
Installation in Mobile Homes, CAN/CSA Z240 MH Series, in Canada.
This appliance is only for use with the type(s) of gas indicated on the rating
plate. This appliance is not convertible for use with other gases, unless a
certified kit is used.
DANGER HOT GLASS WILL CAUSE BURNS.
DO NOT TOUCH GLASS UNTIL COOLED.
NEVER ALLOW CHILDREN TO TOUCH GLASS.
A barrier designed to reduce the risk of burns from the hot viewing glass is
provided with this appliance and must be installed for the protection of
children and other at-risk individuals.
Decorative barrier front must be ordered separately at time of appliance
purchase. See Section 3.A.
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
1
Safety Alert Key:
· DANGER! Indicates a hazardous situation which, if not avoided will result in
death or serious injury. · WARNING! Indicates a hazardous situation which, if
not avoided could result in death or serious injury. · CAUTION! Indicates a
hazardous situation which, if not avoided, could result in minor or moderate
injury. · NOTICE: Used to address practices not related to personal injury.
Note: The term “recommend” or “recommended” does not indicate a requirement.
It is a best practice suggested by Hearth & Home Technologies®.
Table of Contents
Installation Standard Work Checklist. . . . . . . . . . . . . . . . . . . . 3
1 Product Specific and Important Safety Information A. Appliance Certification
. . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 B. Glass
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
C. BTU Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . 4 D. High Altitude Installations . . . . . . . . . . . . . . . . . . . .
. . . . . . 4 E. Non-Combustible Materials Specification. . . . . . . . . . .
. . . 5 F. Combustible Materials Specification . . . . . . . . . . . . . . . .
. 5 G. Electrical Codes . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . 5 H. California . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . 5 I. Requirements for the Commonwealth of
Massachusetts. . 6
2 Getting Started
A. Design and Installation Considerations . . . . . . . . . . . . . . . 7 B.
Good Faith Wall Surface . . . . . . . . . . . . . . . . . . . . . . . . . . 8
C. Tools and Supplies Needed . . . . . . . . . . . . . . . . . . . . . . . 10
D. Inspect Appliance and Components. . . . . . . . . . . . . . . . . 10
3 Framing and Clearances
A. Appliance/Decorative Barrier Front Dimension Diagrams 11 B. Appliance
Location and Clearances to Combustibles . . . 16
C. Constructing the Appliance Chase . . . . . . . . . . . . . . . . . . 26 D.
Floor Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. 27 E. Vinyl Flooring . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . 27
4 Termination Location and Vent Information
A. Approved Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . 28 B. Vent Termination Minimum Clearances . . . . . . . . . . . . . . 28
C. Vent Terminal Clearances . . . . . . . . . . . . . . . . . . . . . . . . 30
D. Use of Elbows . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . 31 E. Vent Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . 32
5 Vent Clearances and Vent Framing
A. Vent Clearances to Combustibles . . . . . . . . . . . . . . . . . . 40 B.
Wall Penetration Framing/Firestops . . . . . . . . . . . . . . . . . 41 C.
Ceiling Firestop/Floor Penetration Framing . . . . . . . . . . . 42 D. Install
Attic Insulation Shield. . . . . . . . . . . . . . . . . . . . . . . 42
6 Appliance Preparation
A. Top Standoff Preparation . . . . . . . . . . . . . . . . . . . . . . . . .
43 B. Prepare For Heat Management . . . . . . . . . . . . . . . . . . . . 44
C. Securing and Leveling the Appliance . . . . . . . . . . . . . . . . 45 D.
Installing Non-Combustible Facing Material . . . . . . . . . . 46
7 Venting A. Assemble Vent Sections (DVP Pipe Only) . . . . . . . . . . . 47
B. Assemble Slip Sections . . . . . . . . . . . . . . . . . . . . . . . . . .
49 C. Secure the Vent Sections . . . . . . . . . . . . . . . . . . . . . . . .
. 49 D. Disassemble Vent Sections . . . . . . . . . . . . . . . . . . . . . .
. 50 E. Vertical Termination Requirements. . . . . . . . . . . . . . . . . .
51 F. Horizontal Termination Requirements . . . . . . . . . . . . . . . 52
8 Electrical Information A. General Information . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . 54 B. Wiring Requirements . . . . . . . . . . . .
. . . . . . . . . . . . . . . . 56
9 Gas Information A. Fuel Conversion . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . 58 B. Gas Pressure . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . 58 C. Gas Service Access . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . 58 D. Gas Connection . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . 60 E. High Altitude Installations . .
. . . . . . . . . . . . . . . . . . . . . . . 60 F. Air Shutter Setting . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . 61
10 Finishing A. Facing Material. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . 62 B. Drywall Installation . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . 63 C. Decorative Barrier Fronts . . . . . . . . . .
. . . . . . . . . . . . . . . 66 D. Mantel and Wall Projections. . . . . . . .
. . . . . . . . . . . . . . . 71
11 Appliance Setup A. Fixed Glass Assembly Removal and Replacement . . . . .
74 B. Remove the Shipping Materials/Install Bottom
Glass Shield . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . 74 C. Clean the Appliance . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . 75 D. Install Glass Refractory (Optional) . . . . . . . . . . . . .
. . . . 75 E. Install Log Set or Stones (Optional) . . . . . . . . . . . . . .
. . 75 F. Install Media (Included) . . . . . . . . . . . . . . . . . . . . . .
. . . . 75 G. IntelliFire Touch® Control System Setup. . . . . . . . . . . . .
. 78 H. Install Decorative Barrier Front. . . . . . . . . . . . . . . . . . .
. . 78
12 Reference Materials A. Vent Components Diagrams . . . . . . . . . . . . . .
. . . . . . . . 79 B. Accessories . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . 87
= Contains updated information.
2
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
Installation Standard Work Checklist
ATTENTION INSTALLER:
Follow this Standard Work Checklist
This standard work checklist is to be used by the installer in conjunction with, not instead of, the instructions contained in this
installation manual. Customer:
Date Installed:
Lot/Address:
Location of Fireplace:
Installer:
Model (circle one): ECHEL36IN-C ECHEL36STIN-C ECHEL48IN-C
Dealer/Distributor Phone #
ECHEL48STIN-C ECHEL60IN-C ECHEL72IN-C
Serial #:
WARNING! Risk of Fire or Explosion! Failure to install appliance according to these instructions can lead to a fire or explosion. Install ONLY components and accessories approved by Hearth & Home Technologies. Unapproved components and accessories could cause fireplace to overheat.
Appliance Install Sections 3 and 6
Verified that the chase is insulated and sealed. (Pg. 26) Required factory
included non-combustible board is installed. (Pg 46) Standoffs bent up into
installation position and secured. (Pg. 43) Verified clearances to
combustibles. (Pg. 16-25) Fireplace is leveled and secured. (Pg. 45) Header no
wider than 3.5 in.(2×4) (Pg. 18-19) Heat management system(s) and/or power
vent properly installed.
YES
IF NO, WHY?
Venting/Chimney Sections 4,5 and 7
Venting configuration complies to vent diagrams. (Pg 32-39)
Venting installed, locked, and secured in place with proper clearance.
(May need to order separately.)
Firestops installed. (Section 5) Attic insulation shield installed. (Pg 42)
Exterior wall/Roof flashing installed and sealed. (Section 7) Terminations
installed and sealed. (Section 7)
Electrical Section 8 (Pg 54-57)
Unswitched power (110-120 VAC) provided to the appliance. Switch wires
properly installed.
Gas Section 9 (Pg 58-61)
Proper appliance for fuel type. Was a conversion performed?
Leak check performed and inlet pressure verified. Verified proper air shutter
setting for installation type.
Finishing Section 10 (Pg 62-73)
Combustible materials not installed in non-combustible areas.
Verified all clearances meet installation manual requirements. Finishing done
correctly using inside fit or overlap fit method. Bottom finishing template
and finishing guards removed.
Mantels and wall projections comply with installation manual requirements.
Appliance Setup Section 11 (Pg 74-78)
All packaging and protective materials removed (inside & outside of appliance).
Refractories and media installed correctly.
Glass assembly installed and secured.
Accessories installed properly.
Decorative barrier front properly installed. (May need to order separately.)
Manual bag and all of its contents are removed from inside/under the appliance
and given to party responsible for use and operation.
Started appliance and verified no gas leaks exist. Lights work in all switched
positions (if so equipped).
Component heat shield is installed. (Pg. 56)
Hearth & Home Technologies recommends the following: · Photographing the
installation and copying this checklist for your file. · That this checklist
remain visible at all times on the appliance until the installation is
complete. Comments: Further description of the issues, who is responsible
(Installer/ Builder/ Other Trades, etc) and corrective
action needed
Comments Communicated to party responsible ____ by __on ___
= Contains updated information.
(Builder / Gen. Contractor/) (Installer)
(Date)
2608-982 Rev. E 8/21
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
3
1 Product Specific and Important Safety Information
A. Appliance Certification
MODEL: ECHEL36IN-C ECHEL36STIN-C ECHEL48IN-C ECHEL48STIN-C ECHEL60IN-C
ECHEL72IN-C
LABORATORY: Underwriters Laboratories, Inc. (UL) TYPE: Direct Vent Heater
STANDARD: CSA / ANSI Z21.88-2019 · CSA 2.33-2019
This product is listed to ANSI standards for “Vented Gas Fireplace Heaters”
and applicable sections of “Gas Burning Heating Appliances for Manufactured
Homes and Recreational Vehicles”, and “Gas Fired Appliances for Use at High
Altitudes”. Also Certified for Installation in a Bedroom or a Bedsitting Room.
NOTICE: This installation must conform with local codes. In the absence of
local codes you must comply with the National Fuel Gas Code, ANSI
Z223.1-latest edition in the U.S.A. and the CAN/CGA B149 Installation Codes in
Canada.
NOT INTENDED FOR USE AS A PRIMARY HEAT SOURCE. This appliance is tested and
approved as either supplemental room heat or as a decorative appliance. It
should not be factored as primary heat in residential heating calculations.
C. BTU Specifications
Models
(U.S. or Canada)
ECHEL36IN-C (NG)
ECHEL36IN-C (Propane)
ECHEL36STIN-C (NG)
ECHEL36STIN-C (Propane)
ECHEL48IN-C (NG)
ECHEL48IN-C (Propane)
ECHEL48STIN-C (NG)
(0-2000 FT) (0-2000 FT) (0-2000 FT) (0-2000 FT) (0-2000 FT) (0-2000 FT) (0-2000 FT)
ECHEL48STIN-C (Propane)
(0-2000 FT)
Maximum Input BTU/h
30,000 27,000 30,000 27,000 40,000 34,000 40,000 34,000
Minimum Input BTU/h
17,500 15,000 17,500 15,000 21,000 20,000 21,000
20,000
Orifice Size (DMS)
36 #52
36 #52
.124 #50
.124
50
ECHEL60IN-C (NG)
(0-2000 FT) 50,000 28,000 #28
ECHEL60IN-C (Propane)
(0-2000 FT) 37,500 20,000 #49
ECHEL72IN-C (NG)
(0-2000 FT) 58,000 30,000 #23
ECHEL72IN-C (Propane)
(0-2000 FT) 45,000 25,000 #46
B. Glass Specifications
This appliance is equipped with 5 mm ceramic glass. Replace glass only with 5
mm ceramic glass. Please contact your dealer for replacement glass.
D. High Altitude Installations
NOTICE: If the heating value of the gas has been reduced, these rules do not
apply. Check with your local gas utility or authorities having jurisdiction.
When installing above 2000 feet elevation:
· In the USA: Reduce input rate 4% for each 1000 feet above 2000 feet.
· In CANADA: Input ratings are certified without a reduction of input rate for
elevations up to 4500 feet (1370 m) above sea level. Please consult provincial
and/or local authorities having jurisdiction for installations at elevations
above 4500 feet (1370 m).
Check with your local gas utility to determine proper orifice size.
4
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
E. Non-Combustible Materials Specification
Material which will not ignite and burn. Such materials are those consisting
entirely of steel, iron, brick, tile, concrete, slate, glass or plasters, or
any combination thereof.
Materials that are reported as passing ASTM E 136, Standard Test Method for
Behavior of Materials in a Vertical Tube Furnace at 750 ºC shall be considered
non-combustible materials.
F. Combustible Materials Specification
Materials made of or surfaced with wood, compressed paper, plant fibers,
plastics, or other material that can ignite and burn, whether flame proofed or
not, or plastered or unplastered shall be considered combustible materials.
G. Electrical Codes
NOTICE: This appliance must be electrically wired and grounded in accordance
with local codes or, in the absence of local codes, with National Electric
Code ANSI/NFPA 70-latest edition or the Canadian Electric Code CSA C22.1.
· A 110-120 VAC circuit for this product must be protected with ground-fault
circuit interrupter protection, in compliance with the applicable electrical
codes, when it is installed in locations such as in bathrooms or near sinks.
H. California
WARNING: This product and the fuels used to operate this product (liquid
propane or natural gas), and the products of combustion of such fuels, can
expose you to chemicals including benzene, which is known to the State of
California to cause cancer and reproductive harm. For more information go to:
www. P65Warnings.ca.gov.
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
5
Note: The following requirements reference various Massachusetts and national
codes not contained in this document.
I. Requirements for the Commonwealth of Massachusetts
For all side wall horizontally vented gas fueled equipment installed in every
dwelling, building or structure used in whole or in part for residential
purposes, including those owned or operated by the Commonwealth and where the
side wall exhaust vent termination is less than seven (7) feet above finished
grade in the area of the venting, including but not limited to decks and
porches, the following requirements shall be satisfied:
Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented gas fueled
equipment, the installing plumber or gas fitter shall observe that a hard
wired carbon monoxide detector with an alarm and battery back-up is installed
on the floor level where the gas equipment is to be installed. In addition,
the installing plumber or gas fitter shall observe that a battery operated or
hard wired carbon monoxide detector with an alarm is installed on each
additional level of the dwelling, building or structure served by the side
wall horizontal vented gas fueled equipment. It shall be the responsibility of
the property owner to secure the services of qualified licensed professionals
for the installation of hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled equipment is
installed in a crawl space or an attic, the hard wired carbon monoxide
detector with alarm and battery back-up may be installed on the next adjacent
floor level. In the event that the requirements of this subdivision can not be
met at the time of completion of installation, the owner shall have a period
of thirty (30) days to comply with the above requirements; provided, however,
that during said thirty (30) day period, a battery operated carbon monoxide
detector with an alarm shall be installed.
Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accordance with the above
provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS
certified.
Signage
A metal or plastic identification plate shall be permanently mounted to the
exterior of the building at a minimum height of eight (8) feet above grade
directly in line with the exhaust vent terminal for the horizontally vented
gas fueled heating appliance or equipment. The sign shall read, in print size
no less than one-half (1/2) in. in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR
OF ALL OBSTRUCTIONS”.
Inspection
The state or local gas inspector of the side wall horizontally vented gas
fueled equipment shall not approve the installation unless, upon inspection,
the inspector observes carbon monoxide detectors and signage installed in
accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
Exemptions
The following equipment is exempt from 248 CMR 5.08(2) (a)1 through 4:
· The equipment listed in Chapter 10 entitled “Equipment Not Required To Be
Vented” in the most current edition of NFPA 54 as adopted by the Board; and
· Product Approved side wall horizontally vented gas fueled equipment
installed in a room or structure separate from the dwelling, building or
structure used in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS
Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall horizontally vented gas
equipment provides a venting system design or venting system components with
the equipment, the instructions provided by the manufacturer for installation
of the equipment and the venting system shall include:
· Detailed instructions for the installation of the venting system design or
the venting system components; and
· A complete parts list for the venting system design or venting system.
Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall horizontally vented gas
fueled equipment does not provide the parts for venting the flue gases, but
identifies “special venting systems”, the following requirements shall be
satisfied by the manufacturer:
· The referenced “special venting system” instructions shall be included with
the appliance or equipment installation instructions; and
· The “special venting systems” shall be Product Approved by the Board, and
the instructions for that system shall include a parts list and detailed
installation instructions.
A copy of all installation instructions for all Product Approved side wall
horizontally vented gas fueled equipment, all venting instructions, all parts
lists for venting instructions, and/or all venting design instructions shall
remain with the appliance or equipment at the completion of the installation.
See Gas Connection section for additional Commonwealth of Massachusetts
requirements.
6
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
2 Getting Started
A. Design and Installation Considerations
WARNING! Risk of Fire or Explosion! Read all instructions before starting the
installation. Majestic direct vent gas appliances are designed to operate with
all combustion air siphoned from outside of the building and all exhaust gases
expelled to the outside. No additional outside air source is required.
Installation MUST comply with local, regional, state and national codes and
regulations. Consult insurance carrier, local building inspector, fire
officials or authorities having jurisdiction over restrictions, installation
inspection and permits. Before installing, determine the following: · Where
the appliance is to be installed. · The vent system configuration to be used.
If Passive
Heat will be installed, consider location of discharge opening in relation to
venting and other construction materials. · Gas supply piping requirements. ·
Provisions for optional heat management system(s). · Electrical wiring
requirements. · Framing and finishing details. · Whether optional
accessories–devices such as a fan, wall switch, or remote control–are desired.
Installation and service of this appliance should be performed by qualified
personnel. Hearth & Home Technologies recommends NFI certified professionals.
Improper installation, adjustment, alteration, service or maintenance can
cause injury or property damage. For assistance or additional information,
consult a qualified service technician, service agency or your dealer.
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
7
B. Good Faith Wall Surface
The ECHELON-C models may be installed with or without optional heat management
systems, including the Passive Heat kit. The installation of a heat management
system will affect certain aspects of the appliance installation including
framing dimensions and clearances to combustibles. Note that Figure 2.3 in
this section refers to the wall surface temperatures when the Passive Heat kit
is installed.
FIREPLACE OPENING
125°F 125°F
130°F
140°F
42 in.
145°F
36 in. 30 in.
155°F
24 in.
18 in. 170°F
12 in. 6 in.
MEASUREMENTS FROM TOP EDGE OF THE FIREPLACE OPENING APPLIANCE FRONT
FACTORY-SUPPLIED NON-COMBUSTIBLE BOARD SHOWN INSTALLED.
Figure 2.1 Good Faith Wall Surface Temperatures Above Appliance
(ECHEL36IN-C/ECHEL36STIN-C, ECHEL48IN-C, ECHEL48STIN-C)
FIREPLACE OPENING
125°F 125°F
135°F
140°F
42 in.
155°F
36 in. 30 in.
190°F
24 in.
18 in. 245°F
12 in. 6 in.
MEASUREMENTS FROM TOP EDGE OF THE OPENING
APPLIANCE FRONT
FACTORY-SUPPLIED NON-COMBUSTIBLE
Figure 2.2 Good Faith Wall Surface Temperatures Above Appliance (ECHEL60IN-C,
ECHEL72IN-C)
OPTIONAL PASSIVE HEAT KIT INSTALLED
FIREPLACE OPENING
95°F 95°F 95°F
95°F
48 in.
105°F
42 in.
115°F
36 in. 30 in.
120°F
24 in.
18 in. 144°F
12 in. 6 in.
MEASUREMENTS FROM TOP EDGE OF THE OPENING
APPLIANCE FRONT
FACTORY-SUPPLIED NON-COMBUSTIBLE BOARD SHOWN INSTALLED.
Figure 2.3 Good Faith Wall Surface Temperatures Above Appliance with Passive
Heat Kit Installed
NOTICE: Surface temperatures listed above are taken with a temperature measuring probe as prescribed by the test standard used for appliance certification. Temperatures on walls or mantels taken with an infrared thermometer may yield increased temperatures of up to 30 °F (17 °C) or more depending on the thermometer settings and material characteristics being measured. Use appropriate finishing materials that are able to withstand these conditions. For additional finishing guidelines, see Section 10.
If installing a television (TV) above the appliance, see Figure 2.4. For installations with the Passive Heat kit, refer to Section 10, Figure 10.19.
8
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
Good Faith Guidelines for TV Installations Above Appliance
TV Wall Bracket
TV on the wall
TV recessed into the wall
TV Item
Minimum Dimensions
A 2.5 inches
B 2 inches minimum to 3 inches maximum
COMBUSTIBLE: 23 inches:ECHEL36IN/STIN-C & 48IN/STIN-C
C COMBUSTIBLE: 27 inches: ECHEL60IN-C & 72IN-C NON-COMBUSTIBLE 18 inches: ALL
SIZES
D Wall Brkt + TV Thickness + 2.5 inches
COMBUSTIBLE: 46 inches ECHEL36/48/60IN-C & 36/48STIN-C
E
58 inches ECHEL72IN-C
A
B
Mantel
D C
B A E
Appliance
Appliance
Notes:
1. These are good faith recommended clearances only and not a guarantee of
compliance with all TV manufacturers’ maximim allowable operating
temperatures.
2. Since every home has unique air flow characteristics and maximum allowable
operating temperatures can vary from manufacturer to manufacturer and from
model to model, actual TV temperatures should be validated at the time of each
installation. TVs should not be used in situations where the actual TV
temperature exceeds the manufacturers’ maximum allowable operating
temperatures identified in the TV’s technical specifications. Contact the TV’s
manufacturer directly if you cannot locate this information or have questions
regarding the information.
3. Mantel height and depth must conform to mantel requirements specified in
the fireplace installation manual.
4. “C” and “E” dimensions taken from the top of the hood or fireplace
opening.
5. Suggestions on how to further reduce TV temperatures: a. Increase “A”
dimension. b. Increase “C” and “E” dimension, however, increasing “B”
dimension beyond maximum recommended typically results in higher temperatures.
Figure 2.4 Good Faith TV Guidelines
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
9
C. Tools and Supplies Needed
Before beginning the installation be sure that the following tools and building supplies are available.
Hand Tools
Tape measure
Level
Framing material
Manometer
Framing square
Voltmeter
Electric drill and bits (1/4 in.)
Plumb line
Safety glasses/Gloves
Wrenches
Reciprocating saw
1/4 in. nut driver
Non-corrosive leak check solution
1/2 – 3/4 in. length, #6 or #8 Self-drilling screws
Caulking material (300 ºF minimum continuous exposure rating)
D. Inspect Appliance and Components
WARNING! Risk of Fire or Explosion! Damaged parts could impair safe operation.
DO NOT install damaged, incomplete or substitute components. Keep appliance
dry.
WARNING! Risk of Fire, Explosion or Electric Shock! DO NOT use this appliance
if any part has been under water. Call a qualified service technician to
inspect the appliance and to replace any part of the control system and/or gas
control which has been under water.
· Carefully remove the appliance and components from the packaging.
· The vent system components and decorative barrier fronts may be shipped in
separate packages.
· If packaged separately, the media, refractory, and/or optional log kits must
be installed.
· Report to your dealer any parts damaged in shipment, particularly the
condition of the glass.
· This product is factory-equipped with an IntelliFire Touch® remote control,
which was paired to the appliance at the factory. This specific remote control
needs to remain with the contents of the manual bag. Do not install batteries
in the remote control until performing the final appliance setup and
checklist.
Hearth & Home Technologies disclaims any responsibility for, and the warranty
will be voided by, the following actions:
· Installation and use of any damaged appliance or vent system component.
· Modification of the appliance or vent system.
· Installation other than as instructed by Hearth & Home Technologies.
· Improper positioning of the logs/media (as applicable) or the glass
assembly.
· Installation and/or use of any component part not approved by Hearth & Home
Technologies.
10
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
3 Framing and Clearances
A. Appliance/Decorative Barrier Front Dimension Diagrams
Dimensions are actual appliance dimensions. Use for reference only. For
framing dimensions and clearances refer to Section 5.
HEAT MANAGEMENT SYSTEMS KNOCKOUTS
IMPORTANT: Must use appropriate
knockout(s) for the selected Heat
Management System. See Section 6.
J
I
M
K
H oL CENTERED ON APPLIANCE
V
U T
N Q
O SR
P
GAS ACCESS
A B
D
G
C
E
F
ELECTRICAL ACCESS
Location
A B C D E F G H I J K
ECHEL36IN-C
Inches Millimeters
49-1/2
1257
39-1/4
997
15-5/8
397
42-1/2
1080
4
102
8-9/16
218
63
1600
8-9/16
218
1
25
46-3/16
1173
17-1/8
435
ECHEL48IN-C
Inches Millimeters
61-1/2
1562
51-1/8
1299
15-5/8
397
42-1/2
1080
4
102
8-9/16
218
63
1600
8-9/16
218
1
25
58
1473
17-1/8
435
Location
L M N O P Q R S T U V
ECHEL36IN-C
Inches Millimeters
8
203
18-5/8
473
41-3/4
1061
2-3/8
60
8-9/16
218
24-1/2
622
7-1/4
184
8-7/8
225
2-3/4
70
23-3/4
603
36-5/8
930
ECHEL48IN-C
Inches Millimeters
8
203
18-5/8
473
41-3/4
1061
2-3/8
60
8-9/16
218
24-1/2
622
7-1/4
184
8-7/8
225
2-3/4
70
23-3/4
603
36-5/8
930
Figure 3.1 Appliance Dimensions – ECHEL36IN-C, ECHEL48IN-C
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
11
HEAT MANAGEMENT SYSTEMS KNOCKOUTS IMPORTANT: Must use appropriate knockout(s)
for the selected Heat Management System. See Section 6.
MK
V
U T
N
Q
O
SR
P
GAS ACCESS
I J
H oL CENTERED ON APPLIANCE
A B
G
D C
E
F
ELECTRICAL ACCESS
Location
A B C D E F G H I J K
ECHEL60IN-C
Inches Millimeters
74
1880
63-1/8 15-5/8
1603 397
48-1/2 4
1232 102
8-9/16
218
63 8-9/16
1600 218
1
25
70
1778
17-1/8
435
ECHEL72IN-C
Inches Millimeters
86
2184
75-1/8 15-5/8
1908 397
48-1/2 4
1232 102
8-9/16
218
75
1905
8-9/16
218
1
25
82 17-1/8
2083 435
Location
L M N O P Q R S T U V
ECHEL60IN-C
Inches Millimeters
8
203
18-5/8
473
47-3/4
1213
2-3/8
60
8-9/16
218
24-1/2
622
7-1/4
184
8-7/8
225
2-3/4
70
23-3/4
603
36-1/2
927
ECHEL72IN-C
Inches Millimeters
8
203
18-5/8
473
47-3/4
1213
2-3/8
60
8-9/16
218
24-1/2
622
N/A
N/A
8-7/8
225
2-3/4
70
23-3/4
603
36-1/2
927
Figure 3.2 Appliance Dimensions – ECHEL60IN-C, ECHEL72IN-C
12
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
HEAT MANAGEMENT SYSTEMS KNOCKOUTS IMPORTANT: Must use appropriate knockout(s)
for the selected Heat Management System. See Section 6.
MK
V
U T
N Q
O SR
P GAS ACCESS
J
I
H
oL CENTERED ON APPLIANCE
A B
D
G
C
E
F
ELECTRICAL ACCESS
Location
A B C D E F G H I J K
ECHEL36STIN-C
Inches Millimeters
50
1270
39-1/4
997
15-5/8
397
42-1/2
1080
4
102
8-9/16
218
63
1600
8-9/16
218
1/2
13
46-3/16
1173
17-1/8
435
ECHEL48STIN-C
Inches Millimeters
62
1575
51-1/8
1299
15-5/8
397
42-1/2
1080
4
102
8-9/16
218
63
1600
8-9/16
218
1/2
13
58
1473
17-1/8
435
Location
L M N O P Q R S T U V
ECHEL36STIN-C
Inches Millimeters
8
203
18-1/8
460
41-3/4
1061
2-3/8
60
8-9/16
218
24-1/2
622
7-1/4
184
8-7/8
225
2-3/4
70
23-3/4
603
36-1/2
927
ECHEL48STIN-C
Inches Millimeters
8
203
18-1/8
460
41-3/4
1061
2-3/8
60
8-9/16
218
24-1/2
622
7-1/4
184
8-7/8
225
2-3/4
70
23-3/4
603
36-1/2
927
Figure 3.3 Appliance Dimensions – ECHEL36STIN-C, ECHEL48STIN-C
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
13
PFF DECORATIVE FRONT
Note: See Section 10 for hearth, mantel and finishing requirements.
G
E D
Barrier Mesh: Integral to Decorative Barrier Front
A C
BF
Location
A B C D E F G
ECHEL36IN-C ECHEL36STIN-C
Inches Millimeters
37-1/4
946
13-1/8
333
47
1194
4-15/16
126
10-1/16
256
23-3/8
594
28-5/16
719
ECHEL48IN-C ECHEL48STIN-C
Inches Millimeters
49-1/4
1250
13-1/8
333
59
1498
4-15/16
126
10-1/16
256
23-3/8
594
28-5/16
719
ECHEL60IN-C
Inches 61-1/4 13-1/8
71 4-15/16 10-1/16 23-3/8 28-5/16
Millimeters 1556 333 1803 126 256 594 719
The PFF decorative front has an installed depth of 3/4 in. (19 mm), measured from the front of the non-combustible finishing material to the front of the decorative front.
Figure 3.4 Picture Frame Front Dimensions
14
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
CLEAN FACE TRIM DECORATIVE BARRIER FRONT Note: See Section 10 for
hearth, mantel and finishing requirements.
A
G
H F
Barrier Mesh: Integral to Decorative Barrier Front
C B
D E
Location
ECHEL36IN-C ECHEL36STIN-C
Inches Millimeters
A
39
991
B
16-3/4
425
C
13-1/8
333
D
37-3/16
945
E
40-5/16
1024
F
24
610
G
5/8
16
H
25
635
ECHEL48IN-C ECHEL48STIN-C
Inches Millimeters
51
1295
16-3/4 13-1/8 49-3/16 52-5/16
24 5/8 25
425 333 1249 1329 610 16 635
ECHEL60IN-C
Inches 63
16-3/4 13-1/8 61-3/16 64-5/16
24 5/8 25
Millimeters 1600
425 333 1554 1634 610 16 635
ECHEL72IN-C
Inches 75
16-3/4 13-1/8 73-3/16 76-5/16
24 5/8 25
Millimeters 1905
425 333 1859 1938 610 16 635
Figure 3.5 Clean Face Trim Front (Inside Fit) Decorative Barrier Front Dimensions
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
15
B. Appliance Location and Clearances to Combustibles
When selecting a location for the appliance it is important to consider the
required clearances to walls and allow sufficient clearance for heat
management systems venting. See Figure 3.6 and Figure 3.7.
WARNING! Risk of Fire or Burns! Provide adequate clearance around air openings
and for service access. Due to high temperatures, the appliance should be
located out of traffic and away from furniture and draperies.
NOTICE: Illustrations reflect typical installations and are FOR DESIGN PURPOSES ONLY. Illustrations/diagrams are not drawn to scale. Actual installation may vary due to individual design preference.
E G
B
AG
B
C
D
Refer to Section 10 for hearth, mantel and wall projection information.
If a Heat Management System will be
installed, refer to Section 6.B for information.
H
18 in. (457 mm) required when Passive Heat Side
B
Discharge Kit is installed. Refer to the Passive
Heat kit instructions for more information.
F
Model
A
B
C
D
E
F
G
Inches ECHEL36IN-C
Millimeters
62-1/2 1588
48-1/4 1226
88-1/8 2238
24-1/2
18-3/4
1
622
476
25
Inches ECHEL48IN-C
Millimeters
70-3/4 1797
60-1/4 1530
100-3/8 2550
See Section
28-1/2 724
18-3/4 476
1 25
ECHEL60IN-C
Inches
79-1/2
72-1/4
112-3/8
10, Figure 10.17 and
31-3/4
18-3/4
1
Millimeters 2019
1835
2854
10.18.
807
476
25
ECHEL72IN-C
Inches Millimeters
88 2235
84-1/4 2140
124-3/8 3159
35-1/4
18-3/4
1
895
476
25
Figure 3.6 Appliance Locations: ECHELON-C Single-Sided Models
H 50 1270 62 1575 74 1880 86 2184
16
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
NOTICE: This See-Through appliance is NOT designed or approved for an indoor/outdoor application.
DC
C
E
E
A
B
D
MODEL
A
B
C
D
E
Inches 48-1/4 17-1/8 48
1/2
1
ECHEL36STIN-C
Millimeters 1226 435 1219
13
25
Inches 60-1/4 17-1/8 48
1/2
1
ECHEL48STIN-C
Millimeters 1530 435 1219
13
25
Figure 3.7 Appliance Locations: ECHELON-C See-Through Models
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
17
A CEILING
F
E
HEADER DEPTH**
B
C D APPLIANCE MAY BE INSTALLED OFF OF FLOOR***
K
G****
NOTE: Header MUST be installed
H
on end as shown in diagram.
J
I
NOTE: E & K dimensions will change if Passive Heat option is installed. Reference the instructions included with the Passive Heat Kit for dimensions.
ECHEL36IN-C Inches
A
Rough Opening (Vent Pipe)
10
B
Rough Opening (Height)
42
MINIMUM FRAMING DIMENSIONS*
C
D
E
F
G****
Rough Opening (Depth)
Rough Opening (Width)
Clearance to Ceiling
Combustible Floor
Combustible Flooring
18-1/4 48-1/4
31
0
0
H
Behind Appliance
1
I
Sides of Appliance
1
J
K
Front of Clearance Appliance to Ceiling
48
55-1/2
Millimeters
254
1067
464
1226
787
0
0
25
25
1219
1410
ECHEL48IN-C Inches
A
Rough Opening (Vent Pipe)
10
Millimeters
254
B
Rough Opening (Height)
42
1067
MINIMUM FRAMING DIMENSIONS*
C
D
E
F
G****
H
I
J
K
Rough Opening (Depth)
Rough Opening (Width)
Clearance to Ceiling
Combustible Combustible Behind Sides of Front of Clearance
Floor
Flooring Appliance Appliance Appliance to Ceiling
18-1/4 60-1/4
31
0
0
1
1
48
55-1/2
464
1530
787
0
0
25
25
1219
1410
ECHEL60IN-C Inches
A
Rough Opening (Vent Pipe)
10
Millimeters
254
B
Rough Opening (Height)
48
1219
MINIMUM FRAMING DIMENSIONS*
C
D
E
F
G****
H
I
J
K
Rough Opening (Depth)
Rough Opening (Width)
Clearance to Ceiling
Combustible Combustible Behind Sides of Front of Clearance
Floor
Flooring Appliance Appliance Appliance to Ceiling
18-1/4 72-1/4
31
0
0
1
1
48
55-1/2
464
1835
787
0
0
25
25
1219
1410
ECHEL72IN-C Inches
A
Rough Opening (Vent Pipe)
10
B
Rough Opening (Height)
48
MINIMUM FRAMING DIMENSIONS*
C
D
E
F
G****
H
I
J
K
Rough Opening (Depth)
Rough Opening (Width)
Clearance to Ceiling
Combustible Combustible Behind Sides of Front of Clearance
Floor
Flooring Appliance Appliance Appliance to Ceiling
18-1/4 84-1/4
31
0
0
1
1
48
55-1/2
Millimeters
254
1219
464
2140
787
0
0
25
25
1219
1410
- = Adjust framing dimensions for interior sheathing (such as sheetrock) **= Header depth not to exceed 3-1/2 inches. *= If appliance is installed off of floor, maintain required clearances to combustibles.
Construct platform in accordance with local building codes. **= For installations with vinyl flooring, see Section 3.E.
Figure 3.8 Clearances to Combustibles-ECHEL36IN-C, ECHEL48IN-C, ECHEL60IN-C, ECHEL72IN-C
18
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
E=MEASUREMENT FROM TOP
OF FIREPLACE OPENING
A
TO CEILING
J=MEASUREMENT FROM
BOTTOM OF FIREPLACE
TO CEILING
HEADER
DEPTH**
HEADER
DEPTH** F
E
C B
D
J G****
I
H
NOTE: Header MUST be installed on end as shown in diagram.
APPLIANCE MAY BE INSTALLED OFF OF FLOOR***
NOTE: E & J dimensions will change if Passive Heat option is installed. Reference the instructions included with the Passive Heat Kit for dimensions.
A
Rough Opening (Vent Pipe)
in.
10
ECHEL36STIN-C
mm
254
in.
10
ECHEL48STIN-C
mm
254
MINIMUM FRAMING DIMENSIONS*
B
C
D
E
F
G****
H
Rough Opening (Height)
Rough Opening (Depth)
Rough Opening (Width)
Clearance Combustible
to Ceiling
Floor
Combustible Flooring
Sides of Appliance
42
17
48-1/4
31
0
0
1
1067
432
1226
787
0
0
25
42
17
60-1/4
31
0
0
1
1067
432
1530
787
0
0
25
I
Front or Rear of Appliance
48
1219
48
1219
J
Clearance to Ceiling
55-1/2 1410 55-1/2 1410
- = Adjust framing dimensions for interior sheathing (such as sheetrock) **= Header depth not to exceed 3-1/2 inches. *= If appliance is installed off of floor, maintain required clearances to combustibles.
Construct platform in accordance with local building codes. **= For installations with vinyl flooring, see Section 3.E.
Figure 3.9 Clearances to Combustibles-ECHEL36STIN-C, ECHEL48STIN-C
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
19
Framing Dimensions – Passive Heat Front Discharge (PH-FRT) Single-Sided or See-Through Front Discharge: Air conveyed into the room through one front discharge slot.
CHASE DETAIL
C
1-1/2 IN. (2 X 4 FRAMING) ROOM CEILING
2 IN. MIN.
CHASE CEILING (REQUIRED)
A
1/2 IN. X 1/2 IN. WIRE MESH**
WIRE MESH**
F
TV
= PASSIVE HEAT
DISCHARGE OPENING
E D
B
WARNING! Risk of Fire! Wire mesh required on bottom of discharge opening when discharge opening is greater than 3 inches. Secure mesh to top of framing.
APPLIANCE MAY BE INSTALLED OFF OF FLOOR
ECHEL36IN-C ECHEL36STIN-C
ECHEL48IN-C ECHEL48STIN-C
ECHEL60IN-C
ECHEL72IN-C
Inches millimeters
Inches millimeters
Inches millimeters
Inches millimeters
FRONT DISCHARGE MINIMUM FRAMING DIMENSIONS
A TRIM KIT* (PH-TRIM)
Height of Discharge Opening
NO TRIM KIT**
Minimum Height of Discharge Opening
B
C
D
E
F
Minimum Clearance
to
Framing
Width of Discharge Opening
Clearance to Top of Discharge Opening from Bottom of Appliance
Clearance from Bottom of Appliance to Bottom of Discharge
Opening
Minimum Clearance Appliance Opening to
Ceiling
3-1/2
2
48
36-1/2
74-1/2
72-1/2
51-1/2
89
51
1219
927
1892
1842
1308
3-1/2
2
48
48-1/2
74-1/2
72-1/2
51-1/2
89
51
1219
1232
1892
1842
1308
3-1/2
2
48
60-1/2
74-1/2
72-1/2
51-1/2
89
51
1219
1537
1892
1842
1308
3-1/2
2
67-1/2
72-1/2
94
92
51-1/2
89
51
1715
1842
2388
2337
1308
- Measurement for Trim Kit = 3-1/2 in. + additional finishing material thickness. Figure 3.11 shows vent cover dimensions. ** Measurement for without trim kit = 2 in. + additional finishing material thickness. If discharge opening is greater than 3
inches, wire mesh is required.
Figure 3.10 Passive Heat Front Discharge Framing Dimensions with Clean Face Finish or Trim Kit
20
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
Passive Heat Front Discharge (PH-FRT) Trim Kit
Vent Cover Dimensions
CA B D
PHTRIM-36C PHTRIM-48C PHTRIM-60C PHTRIM-72C
Inches millimeters
Inches millimeters
Inches millimeters
Inches millimeters
FRONT DISCHARGE FRAMING DIMENSIONS
A
B
C
Inside Height
Inside Width
Outside Height
2-9/16 65
2-9/16 65
2-9/16 65
2-9/16 65
36-1/2 927
48-1/2 1232 60-1/2 1537 72-1/2 1842
5-5/8 143 5-5/8 143 5-5/8 143 5-5/8 143
D
Outside Width
38-3/8 975
50-3/8 1280 62-3/8 1585 74-3/8 1889
Figure 3.11 Passive Heat Front Discharge – Vent Cover Dimensions
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
21
Framing Dimensions – Passive Heat Side Discharge (PH-SIDE) Single-Sided or See-Through
Side Discharge: Air conveyed into the room through two discharge registers, one on each side of appliance.
E = NON-COMBUSTIBLE ZONE (BOTH SIDES) B
1-1/2 IN. (2 X 4 FRAMING) CHASE CEILING ZONE ROOM CEILING
CHASE CEILING (REQUIRED)
DISCHARGE OPENING
E = PASSIVE HEAT DISCHARGE OPENING
A
F D C
WARNING! Risk of Fire! DO NOT place combustible objects or combustible materials in non-combustible zone. Appliance and combustible materials will overheat.
APPLIANCE MAY BE INSTALLED OFF OF FLOOR
SIDE DISCHARGE FRAMING DIMENSIONS
A
B
C
D
Height of Discharge
Opening
Width of discharge Opening
Minimum Clearance Bottom of Appliance to Bottom of Discharge Opening
Minimum Clearance Bottom of Appliance to Ceiling
ECHEL36IN-C ECHEL36STIN-C
ECHEL48IN-C ECHEL48STIN-C
ECHEL60IN-C
Inches millimeters
Inches millimeters
Inches millimeters
12-1/4 311
12-1/4 311
12-1/4 311
8-3/4 222 8-3/4 222 8-3/4 222
62-3/4 1594 62-3/4 1594 62-3/4 1594
76-1/2 1943 76-1/2 1943 76-1/2 1943
ECHEL72IN-C
Inches millimeters
12-1/4 311
8-3/4 222
81-1/4 2064
95 2413
Figure 3.12 Passive Heat Side Discharge Framing Dimensions
E
Minimum Clearance to Combustible
Materials
18 457 18 457 18 457 18 457
F
Minimum Clearance Appliance Opening to
Ceiling
52 1321
52 1321
52 1321 70-1/2 1791
22
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
Framing Dimensions – Passive Heat Open Top Discharge Single-Sided or See-
Through Open Top Discharge: Both sides and the top are open allowing air to be
conveyed into the room.
WARNING! Risk of Fire! Wire mesh required on bottom of discharge opening when
discharge opening is greater than 3 inches. Secure mesh to top of framing.
C A
D B
OPEN TOP DISCHARGE MINIMUM FRAMING DIMENSIONS
A*
B
C
Minimum Height of Clearance Discharge Opening to Framing
Width of Discharge Opening
Inches
2
ECHEL36IN-C/ECHEL36STIN-C
millimeters
51
Inches
2
ECHEL48IN-C/ECHEL48STIN-C
millimeters
51
Inches
2
ECHEL60IN-C
millimeters
51
48 1219
48 1219
48 1219
36-1/2 927
48-1/2 1232 60-1/2 1537
Inches
2
ECHEL72IN-C
millimeters
51
67-1/2 1715
72-1/2 1842
- Wire mesh required for front discharge or open top discharge passive heat installations with discharge
opening of 3 inches or greater.
D Minimum Clearance Appliance Opening to Ceiling
50
1270
50
1270
50
1270
69-1/2 1765
Figure 3.13 Passive Heat Minimum Framing Dimensions Open Top Discharge
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
23
Framing Dimensions – Ducted Passive Heat Front Discharge (PHFR-MCE) Single-
Sided or See-Through
Clearances to Combustibles Ducted Passive Heat Front Discharge Ducted Passive
Heat Kit (PHFR-MCE)
Single-Sided or See-Through
B
F
G F
A D
CE
MINIMUM FRAMING DIMENSIONS
FRONT DISCHARGE
MODEL
Ducted Passive Heat
Kit
A
Height of Discharge Opening
B
Width of Discharge Opening
C
Clearance Opening to
Framing
D
Clearance Opening to
Ceiling
E
Clearance Bottom of Appliance
to Ceiling
F Framing
G
2 X 4 Studs
ECHEL36IN-C ECHEL36STIN-C
PHFR-MCE-36
in. mm
6 152
38-3/4 984
50-1/2 1283
53-1/2 1359
78 1981
3-1/2 89
ECHEL48IN-C ECHEL48STIN-C
PHFR-MCE-48
in. mm
6 152
in.
6
ECHEL60IN-C PHFR-MCE-60
mm
152
50-7/8 1292 62-3/4 1594
50-1/2 1283 50-1/2 1283
53-1/2 1359 53-1/2 1359
78 1981
78 1981
16 inches (406 mm) on center
3-1/2 89
3-1/2 89
in.
6
ECHEL72IN-C PHFR-MCE-72
mm
152
74-3/4 1899
50-1/2 1283
72 1829
96-1/2 2451
3-1/2 89
Figure 3.14 Clearances to Combustibles – Ducted Passive Heat Front Discharge
24
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
Framing Dimensions – Ducted Passive Heat Side Discharge (PHSI-MCE) Single-
Sided or See-Through Clearances to Combustibles
Ducted Passive Heat Side Discharge (PHSI-MCE) Single-Sided or See-Through B
F
E A
C D
Note: Not for use with 60 inch and 72 inch models.
MODEL
Ducted Passive Heat
Kit
ECHEL36IN-C
in.
ECHEL36STIN-C
mm
PHSI-MCE
ECHEL48IN-C
in.
ECHEL48STIN-C
mm
MINIMUM FRAMING DIMENSIONS
SIDE DISCHARGE
A
B
C
D
E
Height of Discharge Opening
Width of Discharge Opening
Clearance Opening to
Framing
Clearance Opening to
Ceiling
Clearance Bottom of Appliance
to Ceiling
16
10-3/16
50
52
76-1/2
406
259
1270
16
10-3/16
50
406
259
1270
1321 52
1321
1943 76-1/2 1943
F
2 X 4 Studs
3-1/2 89
3-1/2 89
Figure 3.15 Clearances to Combustibles – Ducted Passive Heat Side Discharge
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
25
C. Constructing the Appliance Chase
NOTICE: Install appliance on hard metal or wood surfaces extending full width
and depth. DO NOT install directly on carpeting, vinyl, or any combustible
material other than wood. WARNING! Risk of Fire! Maintain specified air space
clearances to appliance and vent pipe: · Insulation and other materials must
be secured to prevent
accidental contact. · The chase must be properly blocked to prevent blown
insulation or other combustibles from entering and making contact with
fireplace or chimney. · Failure to maintain airspace may cause overheating and
a fire.
A chase is a vertical box-like structure built to enclose the gas appliance
and/or its vent system. In cooler climates the vent should be enclosed inside
the chase. NOTICE: Treatment of ceiling firestops and wall shield firestops
and construction of the chase may vary with the type of building. These
instructions are not substitutes for the requirements of local building codes.
Therefore, you MUST check local building codes to determine the requirements
to these steps.
NOTICE: Where required by code, install only sprinkler heads with a sprinkler
activation temperature classified as Extra High.
· Sprinklers inside of chase: Keep sprinkler head away from vent and chimney.
· Heat Management applications: Maintain 36 inches of clearance to openings
from which heat is discharged such as convection slots, passive heat
registers, heat zone registers, etc. Refer to Section 6.B for Heat Management
options allowed for this appliance.
Chases should be constructed and insulated in the same manner as the thermal
envelope of the home based on the code requirements for that climate zone to
prevent air leakage and draft problems. The chase is an extension of the
building thermal envelope.
To further prevent drafts and air leakage, the wall shield and ceiling
firestops should be sealed with caulk or foil tape with a minimum of 300 ºF
continuous exposure rating to seal gaps. Gas line holes and other openings
should be sealed with caulk with a minimum of 300 ºF continuous exposure
rating or stuffed with unfaced insulation. If the appliance is being installed
on a cement surface, a layer of plywood may be placed underneath to prevent
conducting cold up into the room.
Minimum height requirements for an exterior chase on a top-vented appliance
are shown in Figure 3.16. Reference Figure 4.5 for additional clearances.
Note: Figure 3.8 and Figure 3.9 show the fireplace installed on the floor. However, this fireplace can be elevated off the floor provided that the fireplace is properly supported by framing materials and the ceiling clearances are maintained.
ECHEL36 = 70 IN. ECHEL48 = 70 IN. ECHEL60 = 70 IN. ECHEL72 = 82 IN.
A
3 IN. MIN.
B*
REQUIRED MINIMUM OFF TOP ECHEL36 = 18 IN. ECHEL48 = 18 IN. ECHEL60 = 18 IN. ECHEL72 = 30 IN.
- NOTE: If overhang “A” is less than 2 inches, clearance from top of termination cap to bottom of overhang “B” MUST be a minimum of 4 inches. If A is two inches or greater, see Figure 4.4, “Minimum Clearances for Termination.”
Figure 3.16 Exterior Chase – Minimum Height Requirements
26
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
D. Floor Protection
NOTICE: Install appliance on hard metal or wood surfaces extending full width
and depth. DO NOT install directly on carpeting, vinyl, tile or any
combustible material other than wood. WARNING! Risk of Fire! Maintain
specified air space clearances to appliance and vent pipe: · Insulation and
other materials must be secured to prevent
accidental contact. · The chase must be properly blocked to prevent blown
insulation or other combustibles from entering and making contact with
fireplace or chimney. · Failure to maintain airspace could cause overheating
and fire.
Elevated Hearth Systems
Some hearth systems will elevate the appliance off the floor at a given
dimension. The elevation will also have to be added to the following: Wall
penetration referenced in Figure 5.2 (Wall penetration) and Rough Opening
Height (header height) referenced in Figure 3.8 and 3.9.
Note: Finished floor thickness should also be considered when determining
installation dimensions.
AVPINPYLLIA1N2CINE.WMIDINT.H
12 MIN.
IN.
MIN.
Figure 3.17 Vinyl Flooring Recommendations
E. Vinyl Flooring
Vinyl flooring is sensitive to heat. To avoid damage to the vinyl flooring, a
12 inch minimum x 12 inch minimum hearth is recommended when using vinyl
flooring up to the wall. See Figure 3.17. If no hearth is used, it is
recommended to provide a minimum of 30 inches of clearance in front of the
appliance to the vinyl flooring OR the bottom of the appliance should be
raised a minimum of 24 inches off of the floor to allow the vinyl flooring to
be installed up to the wall.
NOTICE: Clearances that do not meet the minimum guidelines could result in
damage or buckling to the vinyl flooring and is done at the installer’s risk.
Hearth and Home Technologies does not recommend adhesive based vinyl flooring
products due to thermal expansion during operation. Floating style flooring
can be used, but will reach temperatures up to to 110 °F (based on ambient
temperature of 70 °F). Consult the manufacturer’s flooring specifications to
ensure compatibility.
VINYL
24 IN. MIN.
Figure 3.18 Vinyl Flooring Recommendations
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
27
4 Termination Location and Vent Information
A. Approved Pipe
WARNING! Risk of Fire, Delayed Ignition or Asphyxiation. This appliance
requires a separate vent. DO NOT vent to a pipe serving any other appliance.
This appliance is only approved for use with Hearth & Home Technologies DVP
venting systems. Refer to Section 12.A for vent component information and
dimensions.
Only use listed decorative termination caps/shrouds with Hearth & Home
Technologies approved venting systems.
DO NOT mix pipe, fittings or joining methods from different manufacturers.
The pipe is tested to be run inside an enclosed wall. There is no requirement
for inspection openings at each joint within the wall.
B. Vent Termination Minimum Clearances
WARNING
Fire Risk. Maintain vent clearance to combustibles as specified. · DO NOT pack
air space with insulation or other
materials. Failure to keep insulation or other materials away from vent pipe
could cause overheating and fire.
HORIZONTAL OVERHANG
2 FT. MIN.
GAS DIRECT VENT TERMINATION CAP
20 INCHES MIN.
LOWEST DISCHARGE
OPENING
VERTICAL WALL
X 12
ROOF PITCH IS X/ 12
H (MIN.) – MINIMUM HEIGHT FROM ROOF TO LOWEST DISCHARGE OPENING
Roof Pitch
H (Min.) Ft
Flat to 6/12…………………………………………………..1.0*
Over 6/12 to 7/12………………………………………….1.25*
Over 7/12 to 8/12………………………………………….1.5*
Over 8/12 to 9/12………………………………………….2.0*
Over 9/12 to 10/12………………………………………..2.5*
Over 10/12 to 11/12 ………………………………………3.25
Over 11/12 to 12/12 ………………………………………4.0
Over 12/12 to 14/12………………………………………5.0
Over 14/12 to 16/12………………………………………6.0
Over 16/12 to 18/12………………………………………7.0
Over 18/12 to 20/12………………………………………7.5
Over 20/12 to 21/12………………………………………8.0
- H minimum may vary depending on regional snowfall. Refer to local codes.
Figure 4.1 Minimum Height From Roof to Lowest Discharge Opening
28
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
A 6 in. (minimum) up to 20 in.
152 mm/508 mm
20 in. and over
B 18 in. minimum
457 mm
0 in. minimum
Wood or Fuel Oil Termination Cap
B
C
A *
**Gas Termination
Cap
OVERHANG WALL
- If using decorative cap cover(s), this distance may need to be increased. Refer to the installation instructions supplied with the decorative cap cover.
** If two gas terminations are present, they may be level (B = 0 inches) provided A is a minimum of 6 inches.
Figure 4.2 Staggered Termination Caps
CAUTION! Risk of Burns! Termination caps are HOT, consider proximity to doors, traffic areas or where people may pass or gather (sidewalk, deck, patio, etc.). Listed cap shields available. Contact your dealer. · Local codes or regulations may require different
clearances. · Hearth & Home Technologies assumes no responsibility
for the improper performance of the appliance when the venting system does not meet these requirements. · Vinyl protection kits are suggested for use with vinyl siding. · Measure horizontal and vertical termination cap clearances as noted in Figure 4.3.
H=Measure Horizontal Distances from H
H
V=Measure Vertical Distances from V
H
V
V
C=L6EAINR. ANCE
E
C and E dimensions are defined in Figure 4.5.
Figure 4.4 Measure Horizontal and Vertical Termination Clearance to Trapezoid
Portion of Cap
Figure 4.3
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
29
C. Vent Terminal Clearances
C
V JB V
B DV
F
V
B
V A
G M
= AREA WHERE TERMINAL IS NOT PERMITTED
X = AIR SUPPLY INLET V = VENT TERMINAL
H or i
XV
E
H
V
VHV
V
A
V
L
V
K Electrical K
Service
V
C
V
U.S.A. Installations: In accordance with the current ANSI Z223.1/NFPA 54, National Fuel Gas Code. Canadian Installations: In accordance with the current CSA B149.1, Natural Gas and Propane Installation Code.
U.S.A.
A Clearance above grade,veranda, porch, deck, or balcony
12 in. (305 mm)
CANADA 12 in. (305 mm)
B
Clearance to window or door that may be opened, or to permanently closed window
U.S.A.: = 12 in. min. (305 mm min.)
CANADA: = 12 in. min. (305 mm min.)
Clearance below unventilated soffit C Clearance below ventilated soffit
Clearance below any vinyl soffits and electrical service D Clearance to
outside corner E Clearance to inside corner
18 in. (457 mm) 18 in. (457 mm) 30 in. (762 mm) 6 in. (152 mm) 6 in. (152 mm)
18 in. (457 mm) 18 in. (457 mm) 30 in. (762 mm) 6 in. (152 mm) 6 in. (152 mm)
F
Not to be installed above a gas meter/regulator assembly within 3 feet horizontally from the center-line of the regulator
3 ft (914 mm)
3 ft (914 mm)
G Clearance to gas service regulator vent outlet
3 ft (914 mm)
3 ft (914 mm)
H
Clearance to non-mechanical air supply inlet to building or the combustion air inlet to
9 in.
any other appliance termination (mechanical or non-mechanical)
(229 mm min.)
12 in. (305 mm min.)
Clearance to a mechanical (powered) air supply inlet
I
(All mechanical air intakes within 10 feet of a horizontal termination cap must be 3 ft (914 mm)
a minimum of 3 feet below termination.)
6 ft (1.8 m)
On public property: clearance above paved sidewalk or a paved driveway.
7 ft (2.1 m)
7 ft (2.1 m)**
J **(A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves both dwellings.)
Clearance from sides of electrical service
6 in. (152 mm)
K
Location of the vent termination must not interfere with access to the electrical service.
6 in. (152 mm)
Clearance above electrical service
12 in. (305 mm) 12 in. (305 mm)
L
Location of the vent termination must not interfere with access to the electrical service.
Clearance under veranda, porch, deck, balcony or overhang *(Permitted only if veranda, porch, deck, or balcony is fully open on a minimum of M two sides beneath the floor.)
18 in. (457 mm) 18 in. (457 mm)*
Vinyl or composite overhang
42 in. (1067 mm) 42 in. (1067 mm)
Figure 4.5 Minimum Clearances for Termination
30
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
D. Use of Elbows
Diagonal runs have both vertical and horizontal vent aspects when calculating
the effects. Use the rise for the vertical aspect and the run for the
horizontal aspect. See Figure 4.6.
Two 45º elbows may be used in place of one 90º elbow. On 45º runs, one foot of
diagonal is equal to 8-1/2 inch (216 mm) horizontal run and 8-1/2 inch (216
mm) vertical run. A length of straight pipe is allowed between two 45º elbows.
See Figure 4.6.
Figure 4.7 shows the vertical and horizontal offsets for DVP elbows.
RISE
VERTICAL
EFLFEENCGTITVHE RUN
Y
X
Vent Type DVP
Inches 6-5/8
X Millimeters
168
Inches 16-1/2
Y Millimeters
419
X
HORIZONTAL
DVP Pipe
DVP4 DVP6 DVP12 DVP24 DVP36 DVP48 DVP6A DVP12A
Effective Length
Inches Millimeters
4
102
6
152
12
305
24
610
36
914
48
1219
3 to 6 76 to 152
3 to 12 76 to 305
Rise/Run
Inches
Millimeters
2-3/4
70
4-1/4
108
8-1/2
216
17
432
25-1/2
648
34
864
2-1/8-4-1/4 54-108
2-1/8-8-1/2 54-216
Figure 4.6
X
Vent Type DVP
Inches 16-1/4
X Millimeters 413
Figure 4.7 Vertical and Horizontal Offset for DVP Elbows
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
31
E. Vent Diagrams
General Rules:
· SUBTRACT 3 ft from the total H measurement for each 90º elbow installed
horizontally.
· SUBTRACT 1-1/2 ft from the total H measurement for each 45º elbow installed
horizontally.
· A maximum of three 90º elbows (or six 45º elbows) may be used in any vent
configuration. Some elbows may be installed horizontally. See Figure 4.12 and
Figure 4.19.
· Elbows may be placed back to back anywhere in the system.
· Any 90º elbow may be replaced with two back to back
45º elbows.
· When penetrating a combustible wall, a wall shield firestop must be
installed.
· When penetrating a combustible ceiling, a ceiling firestop must be
installed.
· Horizontal runs of vent do not require vertical rise; horizontal runs may be
level.
· Horizontal termination cap should have a 1/4 inch downward slant to allow
any moisture in cap to be released. See Figure 4.8.
Measuring Standards:
Vertical and horizontal measurements listed in the vent diagrams and
clearances for termination were made using the following standards:
· Pipe measurements are shown using the effective length of pipe. See Section
12.A (Figure 12.1), for information on effective length of pipe components.
· Horizontal terminations are measured to the outside mounting surface (flange
of termination cap). See Figure 4.9.
· Vertical terminations are measured to top of last section of pipe. See
Figure 4.10.
· Horizontal pipe installed level with no rise.
MEASURE TO SHADED SURFACE (OUTSIDE MOUNTING SURFACE)
Figure 4.9 Measure to Outside Mounting Surface
1/4 in. max.
(6 mm)
W A L L
Figure 4.8
Figure 4.10 Measure to Top of Last Section of Pipe
32
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
WARNING
Fire Risk. Explosion Risk. Do NOT pack insulation or other combustibles
between ceiling firestops. · ALWAYS maintain specified clearances around
venting and firestop systems. · Install wall shield and ceiling firestops as
specified. Failure to keep insulation or other material away from vent pipe
could cause fire.
Top Vent – Horizontal Termination Venting with 1 elbow
WARNING! Risk of Fire!
DO NOT attach elbow directly to the appliance. · The
ECHEL36IN-C/ECHEL36STIN-C, ECHEL48IN-C/ECHEL48STIN-C and ECHEL60IN-C require a
minimum of 18 inches
of vertical venting before attaching any elbow to the appliance. · The
ECHEL72IN-C requires a minimum of 30 inches of vertical venting before
attaching any elbow to the appliance.
ECHEL36IN-C, ECHEL48IN-C, ECHEL60IN-C
V1 Minimum 1-1/2 ft. 457 mm
H1 Maximum 1-1/2 ft. 457 mm
Note: Use DVP Series components only.
2-1/2 ft. 762 mm
6 ft.
1.8 m
3-1/2 ft. 1.1 m
9 ft.
2.7 m
5 ft.
1.5 m
12 ft.
3.7 m
6 ft.
1.8 m
15 ft.
4.6 m
7 ft.
2.1 m
18 ft.
8 ft.
2.4 m
21 ft.
9 ft.
2.7 m
24 ft.
5.5 m 6.4 m 7.3 m
H1
V1
V1 + H1 = 63 ft. (19.2 m) Maximum H1 = 24 ft. (7.3 m) Maximum
ECHEL36STIN-C, ECHEL48STIN-C
V1 Minimum 1-1/2 ft. 457 mm
2-1/2 ft. 762 mm
3-1/2 ft. 1.1 m
5 ft.
1.5 m
6 ft.
1.8 m
7 ft.
2.1 m
8 ft.
2.4 m
9 ft.
2.7 m
3 ft. 6 ft. 9 ft. 12 ft. 15 ft. 18 ft. 21 ft. 24 ft.
H1 Maximum 914 mm 1.8 m 2.7 m 3.7 m 4.6 m 5.5 m 6.4 m 7.3 m
V1 + H1 = 63 ft. (19.2 m) Maximum H1 = 24 ft. (7.3 m) Maximum
ECHEL72IN-C
V1 Minimum 2-1/2 ft. 762 mm
H1 Maximum 1-1/2 ft. 457 mm
3-1/2 ft. 1.1 m
6 ft.
1.8 m
4-1/2 ft. 1.4 m
9 ft.
2.7 m
6 ft.
1.8 m
12 ft.
3.7 m
7 ft.
2.1 m
15 ft.
4.6 m
8 ft.
2.4 m
18 ft.
5.5 m
9 ft.
2.7 m
21 ft.
6.4 m
10 ft.
3.0 m
24 ft.
7.3 m
Figure 4.11
V1 + H1 = 63 ft. (19.2 m) Maximum H1 = 24 ft. (7.3 m) Maximum
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
33
Top Vent – Horizontal Termination Venting with 2 elbows
WARNING! Risk of Fire!
DO NOT attach elbow directly to the appliance. · The
ECHEL36IN-C/ECHEL36STIN-C, ECHEL48IN-C/ECHEL48STIN-C and ECHEL60IN-C require a
minimum of 18 inches
of vertical venting before attaching any elbow to the appliance. · The
ECHEL72IN-C requires a minimum of 30 inches of vertical venting before
attaching any elbow to the appliance.
ECHEL36IN-C, ECHEL48IN-C, ECHEL60IN-C
V1 Minimum
1-1/2 ft. 457 mm
2-1/2 ft. 762 mm
3-1/2 ft. 1.1 m
5 ft.
1.5 m
6 ft.
1.8 m
7 ft.
2.1 m
8 ft.
2.4 m
9 ft.
2.7 m
H1 + H2 Maximum
1-1/2 ft.
457 mm
6 ft.
1.8 m
9 ft.
2.7 m
12 ft.
3.7 m
15 ft.
4.6 m
18 ft.
5.5 m
21 ft.
6.4 m
24 ft.
7.3 m
V1 + H1 + H2 = 63 ft. (19.2 m) Maximum H1 + H2 = 24 ft. (7.3 m) Maximum
Note: Use DVP Series components only.
ECHEL72IN-C
V1 Minimum
2-1/2 ft. 762 mm
3-1/2 ft. 1.1 m
4-1/2 ft. 1.4 m
6 ft.
1.8 m
7 ft.
2.1 m
8 ft.
2.4 m
9 ft.
2.7 m
10 ft.
3.0 m
H1 + H2 Maximum
1-1/2 ft.
457 mm
6 ft.
1.8 m
9 ft.
2.7 m
12 ft.
3.7 m
15 ft.
4.6 m
18 ft.
5.5 m
21 ft.
6.4 m
24 ft.
7.3 m
V1 + H1 +H2 = 63 ft. (19.2 m) Maximum H1 + H2 = 24 ft. (7.3 m) Maximum
ECHEL36STIN-C, ECHEL48STIN-C
V1 Minimum
1-1/2 ft. 457 mm
2-1/2 ft. 762 mm
3-1/2 ft. 1.1 m
5 ft.
1.5 m
6 ft.
1.8 m
7 ft.
2.1 m
8 ft.
2.4 m
9 ft.
2.7 m
H1 + H2 Maximum
3 ft.
914 mm
6 ft.
1.8 m
9 ft.
2.7 m
12 ft.
3.7 m
15 ft.
4.6 m
18 ft.
5.5 m
21 ft.
6.4 m
24 ft.
7.3 m
V1 + H1 +H2 = 63 ft. (19.2 m) Maximum H1 + H2 = 24 ft. (7.3 m) Maximum
H2
H1
V1
INSTALLED HORIZONTALLY
Figure 4.12
34
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
Top Vent – Horizontal Termination Venting with 3 Elbows
WARNING! Risk of Fire!
DO NOT attach elbow directly to the appliance. · The
ECHEL36IN-C/ECHEL36STIN-C, ECHEL48IN-C/ECHEL48STIN-C and ECHEL60IN-C require a
minimum of 18 inches
of vertical venting before attaching any elbow to the appliance. · The
ECHEL72IN-C requires a minimum of 30 inches of vertical venting before
attaching any elbow to the appliance.
ECHEL36IN-C, ECHEL48IN-C, ECHEL60IN-C
V1 + V2 Minimum
1-1/2 ft. 457 mm
2-1/2 ft. 762 mm
3-1/2 ft. 1.1 m
5 ft.
1.5 m
6 ft.
1.8 m
7 ft.
2.1 m
8 ft.
2.4 m
9 ft.
2.7 m
H1 + H2 Maximum
1-1/2 ft.
457 mm
6 ft.
1.8 m
9 ft.
2.7 m
12 ft.
3.7 m
15 ft.
4.6 m
18 ft.
5.5 m
21 ft.
6.4 m
24 ft.
7.3 m
V1 + V2 + H1 + H2 = 63 ft. (19.2 m) Maximum H1 + H2 = 24 ft. (7.3 m) Maximum
Note: Use DVP Series components only.
H2 V2
H1
ECHEL36STIN-C, ECHEL48STIN-C
V1 + V2 Minimum
1-1/2 ft. 457 mm
2-1/2 ft. 762 mm
3-1/2 ft. 1.1 m
5 ft.
1.5 m
6 ft.
1.8 m
7 ft.
2.1 m
8 ft.
2.4 m
9 ft.
2.7 m
H1 + H2 Maximum
3 ft.
914 mm
6 ft.
1.8 m
9 ft.
2.7 m
12 ft.
3.7 m
15 ft.
4.6 m
18 ft.
5.5 m
21 ft.
6.4 m
24 ft.
7.3 m
V1 + V2 + H1 + H2 = 63 ft. (19.2 m) Maximum H1 + H2 = 24 ft. (7.3 m) Maximum
ECHEL72IN-C
V1 + V2 Minimum
2-1/2 ft. 762 mm
3-1/2 ft. 1.1 m
4-1/2 ft. 1.4 m
6 ft.
1.8 m
7 ft.
2.1 m
8 ft.
2.4 m
9 ft.
2.7 m
10 ft.
3.0 m
H1 + H2 Maximum
1-1/2 ft.
457 mm
6 ft.
1.8 m
9 ft.
2.7 m
12 ft.
3.7 m
15 ft.
4.6 m
18 ft.
5.5 m
21 ft.
6.4 m
24 ft.
7.3 m
V1 + V2 + H1 +H2 = 63 ft. (19.2 m) Maximum H1 + H2 = 24 ft. (7.3 m) Maximum
V1
Figure 4.13
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
35
Top Vent – Vertical Termination No Elbows V = 2-1/2 ft Min. (762 mm), 50 ft.
Max. (15.2 m)
Note: If installing a vertical vent/termination off the top of the appliance,
the optional exhaust restrictor may be needed.
Note: Use DVP Series components only.
V
Figure 4.14 Vertical Vent Maximum
36
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
Exhaust restrictor Instructions
Exhaust restrictors are recommended for these vertically terminated products
which have excessive draft. Exhaust restrictors will compensate for high
draft, and restore visual flame height. If the vent configuration has a total
vertical of 20-50 feet, the included exhaust restrictor may be needed.
Exhaust restrictor: ECHEL36IN-C, ECHEL48IN-C, ECHEL60IN-C, ECHEL72IN-C
1. Locate the two pilot holes in the inside firebox chamber as shown in
Figure 4.15.
2. Break the flue restrictor into two pieces. Do this by bending the part
back and forth until it breaks. See Figure 4.16.
3. The setting for ECHEL36IN-C, ECHEL48IN-C, ECHEL60IN-C and ECHEL72IN-C is a
2.5 inch setting, or 2-2. Align the holes marked “2” on the numbered exhaust
restrictor piece with the hole on the other exhaust restrictor piece. See
Figure 4.17. Align the exhaust restrictor pieces with the pilot holes in the
inner firebox chamber. Use two 1/2 inch self-piercing screws to secure vent
restrictor to firebox heat shield.
4. In some applications, such as those where the fireplace is elevated off
the floor, the exhaust restrictor may be painted, but painting is not
required.
PILOT HOLES EXHAUST RESTRICTOR
Figure 4.15 Exhaust Restrictor
NOTICE: Before painting, contact your dealer for information on the
appropriate high temperature paint.
Exhaust restrictor: ECHEL36STIN-C, ECHEL48STIN-C
1. Break the flue restrictor into two pieces. Do this by bending the part
back and forth until it breaks. See Figure 4.16.
Note: The ECHEL36STIN-C and ECHEL48STIN-C do not have pilot holes for the
exhaust restrictor in the firebox chamber.
2. The setting for ECHEL36STIN-C and the ECHEL48STIN-C is a 2.5 inch setting,
or 2-2. Align the holes marked “2” on the numbered exhaust restrictor piece
with the hole on the other exhaust restrictor piece. See Figure 4.17. Center
the exhaust restrictor on the vent and secure in place with two 1/2 inch self-
piercing screws.
3. In some applications, such as those where the fireplace is elevated off
the floor, the exhaust restrictor may be painted, but painting is not
required.
BREAK HERE
Figure 4.16 Break the Exhaust Restrictor
1 2 3 45
SETTING
NOTICE: Before painting, contact your dealer for information on the appropriate high temperature paint.
1 2 3 45
Figure 4.17 Set the Exhaust Restrictor
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
37
Top Vent – Vertical Termination Venting with 2 elbows
WARNING! Risk of Fire! DO NOT attach elbow directly to the appliance. · The
ECHEL36IN-C/ECHEL36STIN-C, ECHEL48IN-C/ECHEL48STIN-C and ECHEL60IN-C require a
minimum of 18 inches
of vertical venting before attaching any elbow to the appliance. · The
ECHEL72IN-C requires a minimum of 30 inches of vertical venting before
attaching any elbow to the appliance.
ECHEL36IN-C, ECHEL48IN-C, ECHEL60IN-C ECHEL36STIN-C, ECHEL48STIN-C
V1 + V2 Minimum 1-1/2 ft. 457 mm
2-1/2 ft. 762 mm
3-1/2 ft. 1.1 m
5 ft.
1.5 m
H Maximum
4 ft. 9 ft. 12 ft.
1.2 m 2.7 m 3.6 m
15 ft.
4.5 m
V1 + H1 + V2 = 63 ft. (19.2 m) Maximum HTotal = 23 ft. (7.1 m) Maximum
Note: Use DVP Series components only.
ECHEL72IN-C
V1 + V2 Minimum
2-1/2 ft. 762 mm
3-1/2 ft. 1.1 m
4-1/2 ft. 1.4 m
6 ft.
1.8 m
H Maximum
4 ft. 9 ft. 12 ft.
1.2 m 2.7 m 3.6 m
15 ft.
4.5 m
V1 + H1 + V2 = 63 ft. (19.2 m) Maximum HTotal = 23 ft. (7.1 m) Maximum
V2
H 1 V1
Figure 4.18
38
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
Top Vent – Vertical Termination Venting with 3 elbows
WARNING! Risk of Fire! DO NOT attach elbow directly to the appliance. · The
ECHEL36IN-C/ECHEL36STIN-C, ECHEL48IN-C/ECHEL48STIN-C and ECHEL60IN-C require a
minimum of 18 inches
of vertical venting before attaching any elbow to the appliance. · The
ECHEL72IN-C requires a minimum of 30 inches of vertical venting before
attaching any elbow to the appliance.
ECHEL36IN-C, ECHEL48IN-C, ECHEL60IN-C
ECHEL36STIN-C, ECHEL48STIN-C
V1 + V2 Minimum 1-1/2 ft. 457 mm
3 ft.
914 mm
4 ft.
1.2 m
5 ft.
1.5 m
H1 + H2 Maximum
4 ft.
1.2 m
9 ft.
2.7 m
12 ft.
3.7 m
15 ft.
4.6 m
V1 + V2 + H1 + H2 = 63 ft. (19.2 m) Maximum H1 + H2 = 23 ft. (7.1 m) Maximum
Note: Use DVP Series components only.
V2
ECHEL72IN-C
V1 + V2 Minimum 2-1/2 ft. 762 mm
H1 + H2 Maximum
4 ft.
1.2 m
4 ft.
1.2 m
9 ft.
2.7 m
5 ft.
1.5 m
12 ft.
3.7 m
6 ft.
1.8 m
15 ft.
4.6 m
V1 + V2 + H1 + H2 = 63 ft. (19.2 m) Maximum H1 + H2 = 23 ft. (7.1 m) Maximum
H1 H2
INSTALLED HORIZONTALLY
vV11
Figure 4.19
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
39
5 Vent Clearances and Vent Framing
A. Vent Clearances to Combustibles
WARNING! Risk of Fire! Maintain air space clearance to vent. DO NOT pack
insulation or other combustibles:
· Between ceiling firestops · Between wall shield firestops · Around vent
system Failure to keep insulation or other material away from vent pipe could
cause overheating and fire.
Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm). · DVP heat
shield – designed to be used on a wall 4 in. to 7-1/4 in.
(102 mm to 184 mm) thick. · If wall thickness is less than 4 in. the existing
heat shields must be
field trimmed. If wall thickness is greater than 7-1/4 in. a DVP-HSM-B will be
required.
(DVP Pipe Shown)
3 in. (76 mm) top clearance
1 in. (25 mm) clearance around vertical sections
Heat Shield
Wall Shield Firestop
3 in. (76 mm) top clearance *
Heat Shield
1 in. (25 mm) clearance bottom & sides
WALL
Figure 5.1 Horizontal Venting Clearances To Combustible Materials
40
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
B. Wall Penetration Framing/Firestops
Combustible Wall Penetration
Whenever a combustible wall is penetrated, you must frame a hole for the wall
shield firestop(s). The wall shield firestop maintains minimum clearances and
prevents cold air infiltration.
· The opening must be framed on all four sides using the same size framing
materials as those used in the wall construction.
· SLP pipe – A wall shield firestop must be placed on each side of an interior
wall. A minimum 1-1/2 in. (38 mm) overlap of attached heat shields must be
maintained.
· DVP pipe – A wall shield firestop is required on one side only on interior
walls. If your local inspector requires a wall shield firestop on both sides,
then both wall shield firestops must have a heat shield (refer to Section
12.A.) attached to them.
· See Section 7.F. for information for regarding the installation of a
horizontal termination cap.
Non-Combustible Wall Penetration
If the hole being penetrated is surrounded by non-combustible materials such
as concrete, a hole with diameter one inch greater than the pipe is
acceptable.
Whenever a non-combustible wall is penetrated, the wall shield firestop is
only required on one side and no heat shield is necessary.
DO NOT PACK VENT FRAMING HOLE WITH INSULATION OR OTHER MATERIAL.
10 in.
12 in.
B
A
MODEL ECHEL36IN-C ECHEL36STIN-C ECHEL48IN-C ECHEL48STIN-C ECHEL60IN-C
ECHEL72IN-C
A* 64 in. 1.63 m 76 in. 1.93 m
B 63 in. 1.60 m 75 in. 1.90 m
- Shows center of vent framing hole for top venting. The center of the hole is one (1) in. (25.4 mm) above the center of the horizontal vent pipe.
Note: Measurements for ECHEL36IN-C/ECHEL48IN-C and ECHEL60IN-C were taken with an 18 inch vertical section of pipe directly off the top of appliance. Measurements for ECHEL72-C were taken with an 30 inch vertical section of pipe directly off the top of appliance.
Note: Center of the horizontal vent pipe to the vertical measuring surface of a trap cap is 5 inches (127 mm).
Figure 5.2 Wall Penetration
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
41
C. Ceiling Firestop/Floor Penetration Framing
WARNING! Risk of Fire! DO NOT pack insulation around the vent. Maintain
clearances to vent to prevent overheating.
A ceiling firestop MUST be used between floors and attics.
· DVP pipe only – Frame an opening 10 in. by 10 in. (254 mm by 254 mm)
whenever the vent penetrates a ceiling/floor (see Figure 5.3).
· Frame the area with the same sized lumber as used in ceiling/floor joist.
· The ceiling firestop may be installed above or below the ceiling joists when
installed with an attic insulation shield. It must be under joists between
floors that are not insulated. Refer to Figure 5.4.
· Secure with two fasteners on each side.
ATTIC ABOVE A
A
PIPE DVP
A 10 in. (254 mm)
D. Install Attic Insulation Shield
WARNING! Fire Risk. The use of an attic shield is required to prevent loose
materials or insulation from contacting the vent causing overheating and a
fire.
The International Fuel Gas Code requires an attic shield constructed of 26
gauge minimum steel that extends at least 2 in. (51 mm) above insulation.
· Attic insulation shields must meet specified clearances to combustible
materials and be secured in place.
· An attic insulation shield kit is available from Hearth & Home Technologies.
Contact your dealer to order. Install attic insulation shield according to
instructions included with kit.
Figure 5.3 Installing Ceiling Firestop
INSTALL ATTIC INSULATION SHIELDS BEFORE OR AFTER INSTALLATION OF VENT SYSTEM
CEILING FIRESTOP INSTALLED BELOW CEILING
Figure 5.4 Installing the Attic Shield
CEILING FIRESTOP INSTALLED ABOVE CEILING
42
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
6 Appliance Preparation
CAUTION! Risk of Cuts, Abrasions or Flying Debris. Wear protective gloves and
safety glasses during installation. Sheet metal edges are sharp.
A. Top Standoff Preparation
1. Rotate the four (4) top standoffs up into vertical position.
60 and 72 only: Push the standoff support tab on each standoff toward the
center of the appliance and fasten it in place using the supplied screw and
pilot hole. See Figure 6.1.
TOP STANDOFFS STANDOFFS DOWN
STANDOFFS UP
LOCATION FOR INSTALLATION OF FIBERGLASS ROPE RING
Standoff Shipping Position
Standoff Installation Position
Figure 6.1 Standoffs Shown in Vertical Position (See-Through Appliance Shown)
2. Place a vent section on the starting collar.
WARNING! Risk of Fire! DO NOT attach elbow directly to the appliance. · The
ECHEL36IN-C/ECHEL36STIN-C, ECHEL48IN-C/
ECHEL48STIN-C and ECHEL60IN-C require a minimum of 18 inches of vertical
venting before attaching any elbow to the appliance. · The ECHEL72IN-C
requires a minimum of 30 inches of vertical venting before attaching any elbow
to the appliance.
4.Place the 1/8 inch thick, square fiberglass gasket over the initial vent
section.
5.Place the fiberglass rope ring over the gasket. Ensure both the gasket and
the rope ring are seated on the top of the appliance. See Figure 6.2 and
Figure 6.3.
Figure 6.2 Location of Fiberglass Rope Ring
GASKET
ROPE RING
Figure 6.3 Fiberglass Rope Ring Installed
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
43
B. Prepare For Heat Management
Introduction
An optional heat management system allows the heat from the appliance to be
redirected as desired.
An optional heat management system must be installed by a qualified service
technician at the time of the appliance installation. Follow the instructions
shipped with the kit for installation and operation.
NOTICE: Additional clearances are required for heat management systems
installations. Provisions must be made in advance to ensure fit within the
framing.
· Determine the heat management system(s) that will be installed.
· Remove the appropriate knockout(s).
· Remove insulation plug(s).
· Center the duct collar around the exposed hole and attach it to the
appliance. See Figure 6.4.
Note: Do this BEFORE final positioning of the appliance.
· Determine the location for the air register/fan housing assembly.
Reference the appropriate instructions included with the heat management
system kit for the remaining installation steps.
Optional Heat Management Systems are:
· HEAT-ZONE®-GAS: The heat is diverted into an adjacent room.
· HEAT-OUT-GAS: The heat is diverted outside the home/building.
· Passive Heat (PH-FRT, PH-SIDE): The heat is vented into the room in which
the appliance is installed through a discharge opening(s).
· Ducted Passive Heat (PHFR-MCE, PHSI-MCE) The heat is ducted into the room in
which the appliance is installed through a discharge opening(s) using an
insulated ducting system. PHSI-MCE side discharge available only for 36 and 48
inch sized appliances.
WARNING! Risk of Fire! DO NOT block passive heat registers! Overheating of
appliance and combustible materials will occur. WARNING! Risk of Fire! DO NOT
remove heat management seal plate unless a heat management System will be
connected at that location. Overheating of appliance and combustible materials
will occur.
PASSIVE HEAT, HEAT-OUT-GAS OR HEAT-ZONE-GAS
PASSIVE HEAT ONLY PASSIVE HEAT HEAT-OUT-GAS OR HEAT-ZONE-GAS
*Note: Remove only one of the outside knockouts if installing
the HEAT-OUT-GAS or HEAT-ZONE-GAS. The other knockout is removed only if
another heat management system is installed. Figure 6.4
Heat-Zone-Gas Adapter Kit (HZLIN-ADP) The HZLIN-ADP adapter kit is required
for use with the Heat-Zone-Gas Kit and is necessary when the optional Heat-
Zone-Gas Kit is installed on the ECHELON-C models. See Figure 6.5.
The ECHELON-C models may utilize two Heat Management Systems, but not all are
compatible.
Approved combinations are:
· HEAT-OUT-GAS: May be used with one HEAT-ZONEGAS or one of the Passive Heat
options (PH-FRT, PHSIDE, PHFR-MCE, PHSI-MCE).
· HEAT-ZONE-GAS: May be used with one HEATZONE-GAS, one of the Passive Heat
options (PH-FRT, PH-SIDE, PHFR-MCE, PHSI-MCE), or one additional HEAT-ZONE-
GAS.
· Passive Heat (PH-FRT, PH-SIDE, PHFR-MCE, PHSIMCE): May be used with HEAT-
ZONE-GAS or one HEAT-OUT-GAS. The dedicated knockouts must be used only as
indicated in Figure 6.4.
Figure 6.5 Heat-Zone-Gas Linear Adapter Collar
44
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
C. Securing and Leveling the Appliance
Setting the Fireplace into the Framing
The left and right nailing tabs were designed as a means to ensure the
fireplace is mounted flush with the framing materials. See Figures 6.6-6.8.
1. The shipping flanges protrude further out from the appliance than the side
standoffs. The shipping flange may be bent upward or broken off in order to
place the appliance into position in the framing.
2. Bend out all nailing tabs. The see-through model will have eight nailing
tabs. The single-sided model will have four nailing tabs.
3. Screw each nailing tab to the adjoining framing material. Ensure that the
one inch air space clearance is maintained on the sides and back of the
fireplace. See Figures 3.8-3.12 for framing and clearance details.
1 IN. STANDOFF
NAILING TAB
NAILING TAB
SHIPPING FLANGE
SHIPPING FLANGE
Figure 6.6 Nailing Tabs Shipping Position
Figure 6.7 Nailing Tabs Installation Position
Securing and Leveling the Appliance
WARNING
Risk of Fire!
Prevent contact with: · Sagging or loose insulation · Insulation backing or
plastic · Framing and other combustible materials
DO NOT remove standoffs or notch the framing around the appliance standoffs.
Failure to maintain air space clearance could cause overheating and fire.
Block openings into the chase to prevent entry of blown-in insulation. Make
sure insulation and other materials are secured.
The diagram shows how to properly position and secure the appliance. See
Figure 6.8. Nailing tabs are provided to secure the appliance to the framing
members. · Bend out nailing tabs on each side. · Place the appliance into
position. · Keep nailing tabs flush with the framing. · Level the appliance
from side to side and front to back. · Shim the appliance as necessary. It is
acceptable to use
wood shims underneath the appliance. · Secure the appliance to the framing by
using nails or
screws through the nailing tabs. Use a minimum of one fastener per nailing
tab. · Optional: Secure the appliance to the floor by inserting two screws
through the pilot holes at the bottom of the appliance. Some figures in manual
show the fireplace installed on the floor. However, this fireplace can be
elevated off the floor provided that the fireplace is properly supported by
framing materials and the ceiling clearances are maintained.
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
45
NAILING TABS BOTH SIDES
Figure 6.8 Proper Positioning and Securing of an Appliance
D. Installing Non-Combustible Facing Material
WARNING! Risk of Fire! · Follow these instructions exactly. · Facing materials
must be installed properly to prevent
fire. · No materials may be substituted without authorization
by Hearth & Home Technologies.
· Remove protective cardboard sleeve from noncombustible facing pieces, which
are included with the appliance.
· Install non-combustible facing material to the appliance using the 1-1/4
inch screws supplied in the manual bag assembly. There may be extra screws
included.
· Attach top board to the framing members with regular sheetrock screws or
nails. See Figure 6.9.
· Attach left and right side pieces to framing members with regular sheetrock
screws or nails.
· Use a wet or dry towel or soft brush to remove dust or dirt from facing
material.
· See Section 10 for finishing materials guidelines.
Figure 6.9 Install Factory-Included Non-Combustible Facing Material
46
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
7 Venting
A. Assemble Vent Sections (DVP Pipe Only)
WARNING! Risk of Fire or Explosion! Vent sections MUST be installed correctly.
Improperly installed vent sections could leak or cause appliance to overheat.
Attach Vent to the Firebox Assembly
Note: The end of the pipe sections with the lanced tabs will face toward the
appliance. Attach the first pipe section to the starting collar: · Lanced pipe
end of the starting collar. · Inner pipe over inner collar. · Push the pipe
section until all lanced tabs snap in place. · Lightly tug on pipe to confirm
it has locked.
Requirement for Commercial, Multi-family (Multi-level exceeding two stories),
or High-Rise Applications
WARNING! Risk of Fire or Explosion! DO NOT break silicone seals on slip
sections. Use care when removing termination cap from slip pipe. If slip
section seals are broken during removal of the termination cap, vent could
leak.
All outer pipe joints must be sealed using one of the methods below, including
the slip section that connects directly to the horizontal termination cap. ·
Apply a bead of silicone sealant (300 ºF minimum con-
tinuous exposure rating) inside the female outer pipe joint prior to joining
sections. See Figure 7.1 OR Apply a bead of silicone sealant (300 ºF minimum
continuous exposure rating) to the outside of connecting joint after joining
sections OR Apply aluminum foil tape (300 ºF minimum continuous exposure
rating) to the outside of connecting joint after joining sections. On
horizontal pipe runs, it is recommended that the tape seam is positioned on
the bottom side of the vent pipe. · Only outer pipes need to be sealed. All
unit collar, pipe, slip section, elbow and cap outer flues shall be sealed in
this manner, unless otherwise stated.
Assemble Pipe Sections
Per Figure 7.2:
· Start the inner pipe on the lanced end of section A into the flared end of
section B.
· Start the outer pipe of section A over the outer pipe of section B.
· Once both vents sections are started, push firmly until all lanced tabs lock
into place.
· Lightly tug on the pipe to confirm the tabs have locked.
It is acceptable to use screws no longer than 1/2 in. (13 mm) to hold outer
pipe sections together. If predrilling holes, DO NOT penetrate inner pipe.
For 90º and 45º elbows that are changing the vent direction from horizontal to
vertical, one screw minimum should be put in the outer flue at the horizontal
elbow joint to prevent the elbow from rotating. Use screws no longer than 1/2
in. (13 mm). If predrilling screw holes, DO NOT penetrate inner pipe.
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
47
Figure 7.1 High Temperature Silicone Sealant
A
Lances
NOTICE: When installing a vent system with an HRC termination cap, all pipe
system joints shall be sealed using a high temperature silicone sealant (300
ºF minimum continuous exposure rating). · Apply a bead of silicone sealant
(300 ºF minimum
continuous exposure rating) inside the female outer pipe joint prior to
joining sections. · Only outer pipes are sealed, sealing the inner flue is not
required. · All unit collar, pipe, slip section, elbow and cap outer flues
shall be sealed.
B
Figure 7.2
Figure 7.3
Note: Make sure that the seams are not aligned to prevent unintentional disconnection.
CORRECT
Figure 7.4 Seams
INCORRECT
48
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
B. Assemble Slip Sections
· Slide the inner flue of the slip section into the inner flue of the pipe
section and the outer flue of the slip section over the outer flue of the pipe
section. See Figure 7.5.
· Slide together to the desired length.
Pilot hole
Figure 7.5 Slip Section Pilot Holes
· Maintain a 1-1/2 in. (38 mm) overlap between the slip section and the pipe
section.
· Secure the pipe and slip section with two screws no longer than 1/2 in. (13
mm), using the pilot holes in the slip section. See Figure 7.6.
C. Secure the Vent Sections
WARNING! Risk of Fire, Explosion or Asphyxiation! Improper support could allow
vent to sag and separate. Use vent run supports and connect vent sections per
installation instructions. DO NOT allow vent to sag below connection point to
appliance. · Vertical runs originating off the top of the appliance, with
no offsets, must be supported every 8 feet (2.44 m) after the maximum allowed
25 feet (7.62 m) of unsupported rise. · Vertical runs originating off the rear
of the appliance, or after any elbow, must be supported every 8 feet (2.44 m).
· Horizontal runs must be supported every 5 feet (1.52 m). · Vent supports or
plumbers strap (spaced 120º apart) may be used to support vent sections. See
Figures 7.7 and 7.8. · Wall shield firestops may be used to provide horizontal
support to vent sections. · SLP ceiling firestops have tabs that may be used
to provide vertical support.
120º
Figure 7.6 Screws into Slip Section
· Continue adding pipe as necessary following instructions in “Assembling Pipe
Sections.”
NOTICE: If slip section is too long, the inner and outer flues of the slip
section can be cut to the desired length.
Figure 7.7 Securing Vertical Pipe Sections
120º
Figure 7.8 Securing Horizontal Pipe Sections
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
49
D. Disassemble Vent Sections
· Rotate either section (see Figure 7.9) so the seams on both pipe sections
are aligned as shown in Figure 7.10.
· Pull carefully to separate the pieces of pipe.
Figure 7.9 Rotate Seams for Disassembly
Figure 7.10 Align and Disassemble Vent Sections
50
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
E. Vertical Termination Requirements
Install and Seal Metal Roof Flashing
· See minimum vent heights for various pitched roofs (Section 4, Figure 4.1)
to determine the length of pipe to extend through the roof.
· Slide the roof flashing over the pipe sections extending through the roof as
shown in Figure 7.11.
· Use an elastomeric or silicone sealant with a minimum of 150 ºF temperature
rating to seal the metal roof flashing.
Assemble and Install Storm Collar
CAUTION! Risk of Cuts, Abrasions or Flying Debris. Wear protective gloves and
safety glasses during installation. Sheet metal edges are sharp.
· Slide the storm collar onto the exposed pipe section and align brackets.
· Insert a bolt (provided) through the brackets and install nut. Do not
completely tighten.
Note: When installing a silicone or EPDM pipe flashing boot on a metal roof, it is recommended to put a bead of 100% silicone sealant where the boot contacts the vent pipe to prevent the entry of water. Follow the manufacturer’s recommendations when installing the boot. Climate regions with frequent temperatures below – 50 °F (-45.6 °C) should use a silicone flashing boot.
NOTICE: Failure to properly seal the roof flashing and pipe seams could permit
entry of water. · Seal the gap between the roof flashing and the outside
diameter of the pipe.
· Seal the perimeter of the flashing where it contacts the roof surface. See
Figure 7.11.
· Seal the exposed pipe section seams that are located above the roof.
Figure 7.12 Insert Bolt into Brackets
· Slide the assembled storm collar down the pipe section until it rests on the
roof flashing. See Figure 7.12.
· Tighten nut and make sure the collar is tight against the pipe section.
· Seal around the top of the storm collar. See Figure 7.13.
SEAL
Figure 7.11
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
51
Install Vertical Termination Cap
· Attach the vertical termination cap by sliding the inner collar of the cap
into the inner flue of the pipe section while placing the outer collar of the
cap over the outer flue of the pipe section.
· Secure the cap by driving three self-tapping screws (supplied) through the
pilot holes in the outer collar of the cap into the outer flue of the pipe.
See Figure 7.13.
TERMINATION CAP
(1 OF 3) SCREWS
SEAL
Figure 7.13
STORM COLLAR
F. Horizontal Termination Requirements
Heat Shield Requirements for Horizontal Termination
WARNING! Risk of Fire! To prevent overheating and fire, heat shields must
extend through the entire wall thickness.
· DO NOT remove the heat shields attached to the wall shield firestop and the
horizontal termination cap (shown in Figure 7.14).
· Heat shields must overlap 1-1/2 in. (38 mm) minimum.
There are two sections of the heat shield. One section is factory-attached to
the wall shield firestop. The other section is factory-attached to the cap.
See Figure 7.14.
If the wall thickness does not allow the required 1-1/2 in. (38 mm) heat
shield overlap when installed, an extended heat shield must be used.
· If the wall thickness is less than 4 in./102 mm (DVP) or 4-3/8 in./ 111 mm
(SLP), the heat shields on the cap and wall shield firestop must be trimmed. A
minimum 1-1/2 in. (38 mm) overlap MUST be maintained.
· Use an extended heat shield if the finished wall thickness is greater than
7-1/4 in. (184 mm).
· The extended heat shield may need to be cut to length maintaining sufficient
length for a 1-1/2 in. (38 mm) overlap between heat shields.
· Attach the extended heat shield to either of the existing heat shields using
the screws supplied with the extended heat shield. Refer to vent components
diagrams in the back of this manual.
· Rest the small leg on the extended heat shield on top of the pipe section to
properly space it from the pipe section.
Important Notice: Heat shields may not be field constructed.
52
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
Install Horizontal Termination Cap (DVP and SLP Pipe)
WARNING! Risk of Fire! The telescoping flue section of the termination cap
MUST be used when connecting vent.
· 1-1/2 (38 mm) minimum overlap of flue telescoping section is required.
Failure to maintain overlap could cause overheating and fire.
· Vent termination must not be recessed in the wall. Siding may be brought to
the edge of the cap base.
· Flash and seal as appropriate for siding material at outside edges of cap.
· When installing a horizontal termination cap, follow the cap location
guidelines as prescribed by current ANSI Z223.1 and CAN/CGA-B149 installation
codes and refer to Section 4 of this manual.
CAUTION! Risk of Burns! Local codes may require installation of a cap shield
to prevent anything or anyone from touching the hot cap. NOTICE: For certain
exposures which require superior resistance to wind-driven rain penetration, a
flashing kit and HRC caps are available. When penetrating a brick wall, a
brick extension kit is available for framing the brick.
Note: When using termination caps with factory-supplied heat shield attached,
no additional wall shield firestop is required on the exterior side of a
combustible wall.
WALL SHIELD FIRESTOP
HEAT SHIELD OR EXTENDED
HEAT SHIELD
HEAT SHIELD 1-1/2 IN. (38 MM) MIN.
OVERLAP
SLIP SECTION CAN BE EXTENDED
INNER VENT OUTER VENT
INTERIOR
SHEATHING EXTERIOR
Figure 7.14 Venting Through the Wall
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
53
8 Electrical Information
A. General Information
WARNING! Risk of Shock! DO NOT wire 110-120 VAC to the ignition module or to
the appliance wall switch. (IPI)
Incorrect wiring will damage controls. NOTICE: This appliance must be
electrically wired and grounded in accordance with local codes or, in the
absence of local codes, with National Electric Code ANSI/NFPA 70-latest
edition or the Canadian Electric Code CSA C22.1.
· Wire the appliance circuit using a minimum 14-2 AWG with ground to
unswitched 110-120 VAC. This is required for proper operation of the appliance
(IntelliFire® ignition).
· A 110-120 VAC circuit for this product must be protected with ground-fault
circuit interrupter protection, in compliance with the applicable electrical
codes, when it is installed in locations such as in bathrooms or near sinks.
· Low voltage and 110-120 VAC voltage cannot be shared within the same wall
box.
· In some instances, the spark ignition of the fireplace may cause
intermittent, non-damaging, interference during the lighting sequence with a
TV plugged into the same circuit. It is recommended that the fireplace and TV
use different circuits to mitigate the interference potential. If interference
is occurring on the same circuit, the use of surge protectors may help
alleviate the interference.
54
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
Junction Box Installation
WARNING! Risk of Shock! Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous operation. Verify
proper operation after servicing.
1. Remove bottom panel by removing two screws. Screw locations are shown in
Figure 8.1. After removing two screws, gently lift the panel and pull forward,
avoiding contact with the non-combustible board if possible.
2. Remove insulation.
3. Remove screws on left and right sides of component heat shield and lift it
out of the control cavity. See Figure 8.3 for location of component heat
shield screws.
4. Remove the one screw that secures the junction box to the control tray
panel. See Figure 8.2.
5. Route the wire through the strain relief in the outer wrap and up through
the cutout located on the metal tray under the junction box.
6. Make the connection inside the junction box to the 110120V wire. Connect
green to the ground nut, black to black, and white to white.
7. To reattach the junction box, insert one end of the junction box in the
slot provided and securely screw the other end of the junction box to the
control tray panel.
8. Reinstall component heat shield and insulation.
CAUTION! Risk of Overheating! Component heat shield MUST be installed before
operating appliance. Electrical components will be damaged.
In the event that the junction box may need to be accessed or installed after
finish methods have been applied, access is possible by removing the bottom
glass shield.
BBOOTTTTOOMMGPLAANSESL SHIELD BOTTOM PANEL SCREW LOCATIONS
Figure 8.1 Bottom Panel Location
Figure 8.2 Junction Box Detail
COMPONENT INSULATION
(Behind Component Heat Shield)
RESET SWITCH – PROPANE ONLY
BATTERY TRAY
ECM
Accessories Requirements
· This appliance may be used with a wall switch, wall mounted thermostat
and/or a remote control. Use of a wall switch will limit the functionality of
the remote. A power vent can not be used with a wall switch.
Wiring for optional Hearth & Home Technologies approved accessories should be
done now to avoid reconstruction. Follow instructions that come with those
accessories.
Electrical Service and Repair
WARNING! Risk of Shock! Label all wires prior to disconnection when servicing
controls. Wiring errors could cause improper and dangerous operation. Verify
proper operation after servicing.
WARNING! Risk of Shock! Replace damaged wire with type 105º C rated wire. Wire
must have high temperature insulation.
COMPONENT HEAT SHIELD LED DIMMER
SCREW
SCREW
Figure 8.3 Valve Cavity (Lower Access Panel Removed)
ACM
LED POWER SUPPLY JUNCTION BOX
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
55
B. Wiring Requirements IntelliFire Touch® Ignition System Wiring
· Wire the appliance junction box to 110-120 VAC for proper operation of the
appliance.
WARNING! Risk of Shock or Explosion! DO NOT wire IPI controlled appliance
junction box to a switched circuit. Incorrect wiring will override IPI safety
lockout. · Refer to Figure 8.4 IntelliFire Touch (IPI) Wiring Diagram. · This
appliance is equipped with an IntelliFire control valve
which operates on a 6 volt system.
NOTICE: Batteries should only be used as a power source in the event of an
emergency power outage. Batteries should not be used as a primary long-term
power source. Batteries tend to corrode over time. When using batteries as a
power source, the 6 volt transformer must be unplugged from the receptacle.
Do not store batteries in the battery pack when the appliance is powered by
the 6 volt transformer connected to permanent electrical service.
Accessories Requirements
· This appliance ships standard with a remote control.
Wiring for optional Hearth & Home Technologies approved accessories should be
done now to avoid reconstruction. Follow instructions that come with those
accessories.
The junction box, control module, LED power supply and wall switch receiver
can be accessed by removing the bottom glass shield and component heat shield.
The decorative barrier front must be removed to access these components. See
Figure 8.4.
CAUTION! Risk of Overheating! Component heat shield MUST be installed before
operating appliance. Electrical components will be damaged. CAUTION! Risk of
Overheating! DO NOT remove component insulation from top of component heat
shield. Electrical components will be damaged.
56
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
NEUTRAL HOT
NEUTRAL HOT
6 VAC TRANSFORMER
FLAME SENSE
IGNITER
PROPANE ONLY
RESET SWITCH WIRE 2550-135
RESET SWITCH 2206-298
RF MODULE
JUNCTION BOX 110-120 VAC
IFT-RC400 REMOTE CONTROL
JUMPER WIRE SEE DETAIL A
TO JUNCTION BOX 110-120 VAC
DETAIL A JUMPER WIRE
ORANGE (PILOT)
BLUE WHITE BLACK
RED BLACK
LED DIMMER
BLK RED
LED POWER SUPPLY
BROWN
RED BLK
6V DC BATTERY PACK
TO JUNCTION BOX 110VAC
LED LIGHT TRAY (36 INCH MODELS)
LED LIGHT TRAY (48 INCH MODELS)
LED LIGHT TRAY (60 INCH MODELS)
LED LIGHT TRAY (72 INCH MODELS)
Figure 8.4 IntelliFire Touch Wiring Diagram
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
57
9 Gas Information
A. Fuel Conversion
· Make sure the appliance is compatible with available gas types.
· Conversions must be made by a qualified service technician using Hearth &
Home Technologies specified and approved parts.
B. Gas Pressure
WARNING
Fire Risk. Risk of Fire! Risk of Explosion! Incorrect pressure will damage
valve. · Isolate gas supply piping BEFORE pressure
testing gas line at test pressures above 1/2 psig. · Close the manual shutoff
valve BEFORE pressure testing gas line at test pressures equal to or less than
1/2 psig.
· Optimum appliance performance requires proper input pressures.
· Gas line sizing requirements will be determined in ANSI Z223.1 National Fuel
Gas Code in the USA and CAN/ CGA B149 in Canada.
· Pressure requirements when in operation are:
Note: Have the gas supply line installed in accordance with local codes, if
any. If not, follow ANSI Z223.1. Installation should be done by a qualified
installer approved and/or licensed as required by the locality. (In the
Commonwealth of Massachusetts installation must be performed by a licensed
plumber or gas fitter).
Note: A listed (and Commonwealth of Massachusetts approved) 1/2 in. (13 mm)
T-handle manual shut-off valve and flexible gas connector are connected to the
1/2 in. (13 mm) control valve inlet.
· If substituting for these components, please consult local codes for
compliance.
C. Gas Service Access
Note: This appliance does include a manual gas shutoff valve that is located
in the valve compartment. This manual gas shutoff valve is accessible for
service by removing the decorative barrier front and the bottom glass shield.
The valve is most accessible if it is located forward in the control cavity of
the appliance.
Depending upon local code, an additional manual gas shutoff, in a readily
accessible area may be required and located upstream from the appliance.
The bottom panel is removable if finishing material is not installed. See
Figure 9.2.
Gas Pressure Minimum inlet pressure Maximum inlet pressure Manifold pressure
Natural Gas 5.0 in. w.c. 10.0 in. w.c. 3.5 in. w.c.
Propane 11.0 in. w.c. 13.0 in. w.c. 10.0 in. w.c.
· Verify inlet pressures. Verify minimum pressures when other household gas
appliances are operating.
· Install regulator upstream of valve if line pressure is greater than 1/2
psig.
· Valve pressure taps are accessible by removing the decorative barrier front
and the bottom glass shield.
BBOOTTTTOOMMGPLAANSESL SHIELD BOTTOM PANEL SCREW LOCATIONS
Figure 9.2 Bottom Glass Shield and Bottom Panel Location
VALVE PRESSURE TAPS
Figure 9.1 Valve Pressure Taps
If the finishing materials have been installed around the appliance opening,
proceed as follows: 1. Remove bottom glass shield. 2. Remove screws on left
and right sides of component
heat shield and lift it out of the control cavity.
CAUTION! Risk of Overheating! Component heat shield MUST be installed before
operating appliance. Electrical components will be damaged.
58
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
3. Unplug the 6V transformer from the junction box. This will turn the power
off to the appliance.
4. Turn the gas shutoff handle to the “OFF” position to shut off the gas
supply.
If additional access is needed, proceed as follows:
5. Remove glass assembly from appliance by unlatching the top spring latches
from the glass frame and lifting glass frame assembly out of the bottom
bracket.
6. Remove interior media and refractory from the appliance if already
installed.
7. Remove the media tray. It is attached to the interior firebox bottom with
ten screws. See Figure 9.3.
8. Remove the two screws that attach the pilot to the burner.
9. Remove the four screws securing the burner to the firebox sides and
disengage burner from orifice. Remove burner. See Figure 9.3.
10. Remove the eight screws that secure the glass window. Remove the glass
window. Handle with care. See Figure 9.4.
11. Remove light tray from appliance by lifting up and out through the bottom
glass opening.
PILOT SHIELD MEDIA TRAY
Figure 9.4 Gas and Electrical Access – Remove Glass Window
BURNER 36 BURNER 48 BURNER 60 BURNER 72
GAS VALVE GAS ACCESS
Figure 9.5 Gas Fitting Access with Bottom Glass Shield Removed
Figure 9.3 Media Tray with Burner and Pilot Shield
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
59
D. Gas Connection
· Refer to Section 3 for location of gas line access in appliance.
· Gas line may be run through the left side of appliance.
· The gap between supply piping and gas access hole may be sealed with caulk
or aluminum foil tape with a minimum of 300 ºF continuous exposure rating or
stuffed with non-combustible, unfaced insulation to prevent cold air
infiltration.
· Ensure that gas line does not come in contact with outer wrap of the
appliance. Follow local codes.
· Pipe incoming gas line into valve compartment.
· Connect incoming gas line to the 1/2 in. (13 mm) NPT connection on manual
shutoff valve.
WARNING! Risk of Fire or Explosion! Support control when attaching pipe to
prevent bending gas line. WARNING! Risk of Fire or Explosion! Gas build-up
during line purge could ignite.
· A small amount of air will be in the gas supply lines. · Ensure adequate
ventilation. · Ensure there are no ignition sources such as sparks or
open flames.
Light the appliance. It will take a short time for air to purge from lines.
When purging is complete the appliance will light and operate normally.
WARNING! Risk of Fire, Explosion or Asphyxiation! Check all fittings and
connections with a non-corrosive commercially available leak-check solution.
DO NOT use open flame. Fittings and connections could have loosened during
shipping and handling.
E. High Altitude Installations
NOTICE: If the heating value of the gas has been reduced, these rules do not
apply. Check with your local gas utility or authorities having jurisdiction.
When installing above 2000 feet elevation:
· In the USA: Reduce input rate 4% for each 1000 feet above 2000 feet.
· In CANADA: Input ratings are certified without a reduction of input rate for
elevations up to 4500 feet (1370 m)above sea level. Please consult provincial
and/ or local authorities having jurisdiction for installations at elevations
above 4500 feet (1370 m).
Check with your local gas utility to determine proper orifice size.
60
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
F. Air Shutter Setting
WARNING! Risk of Explosion or Delayed Ignition! Improperly adjusted air
shutter could cause soot buildup. NOTICE: If sooting occurs, provide more air
by opening the air shutter. Air shutter settings may be adjusted by a
qualified installer at the time of installation. The air shutter is set at the
factory for minimum vertical vent run. Adjust air shutter for longer vertical
runs. See Figure 9.6. Air shutter settings should be adjusted by a qualified
service technician at the time of installation. The air shutter is set at the
factory for a typical horizontal termination through a 2 X 6 wall. See Figure
4.11 Top Vent – Horizontal Termination With One Elbow. · Refer to Gas Service
Access instructions in Section 9.C
to access the air shutter. · Loosen the 1/4 in. screw. · Twist shutter to
adjust. · Shutter may be open for longer horizontal vent runs. · Do not close
the air shutter more than 1/16 in. for NG or
1/4 in. for propane. · Tighten the screw.
Shutter Setting Verification / Flame Appearance · After 15 minutes, the flames
will be a yellow/blue mix.
The front flames may be blue at this time. · After 30 minutes, the flames
should be yellow with
some blue flames near the burner ports. · After 1 hour, the flame will be at
its maximum maturity.
NOTICE: Flames should not appear orange or stretch to the top of the firebox.
If flames are dark orange with dark, smoky tips, provide more primary air to
the burner by opening the air shutter accordingly.
Air Shutter Settings
ECHEL36IN-C ECHEL36STIN-C
ECHEL48IN-C ECHEL48STIN-C
GLASS REFRACTORY KIT
LOG KIT
NG
Standard Opening=
3/16 in. 1/4 in.
ECHEL60IN-C
GLASS REFRACTORY KIT
LOG KIT
NG
Standard Opening=
3/8 in.
3/8 in.
Propane
Standard Opening= Full Open Full Open
Propane Standard Opening= Full Open Full Open
ECHEL72IN-C
GLASS REFRACTORY KIT
LOG KIT
NG
Standard Opening=
1/2 in.
1/2 in.
Propane
Standard Opening= Full Open
Full Open
DETAIL
Figure 9.6 Air Shutter Location
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
61
10 Finishing
A. Facing Material
WARNING
Risk of Fire!
DO NOT apply combustible materials beyond the minimum clearances. Comply with
all minimum clearances to combustibles as specified in this manual. Materials
overlapping into non-combustible zones could ignite and will interfere with
air flow through decorative barrier fronts. · Metal front of appliance may be
covered with non-
combustible materials only. · Facing and/or finishing materials must not
interfere
with air flow through decorative barrier fronts, removal of decorative barrier
fronts or access for service. · Facing and/or finishing materials must never
overhang into the glass opening. · Observe all clearances when applying
combustible materials. · Seal gaps between the finished wall and appliance top
and sides using a 300 ºF minimum sealant. Refer to Figure 10.1.
NOTICE: Surface temperatures around the appliance will become warm while the
appliance is in operation. Ensure finishing materials used for all surfaces
(floor, walls, mantels, etc.) will withstand temperatures up to 190°F.
If using vinyl flooring, refer to Section 3.E.
WARNING! Risk of Fire! Comply with all minimum clearances to combustibles as
specified. Framing closer than the minimums listed must be constructed
entirely of noncombustible materials (i.e., steel studs, concrete board,
etc.).
Splatter Guard
The splatter guard is a piece of corrugated material used to protect the
appliance during the installation process before finishing work on the whole
hearth is complete. A splatter guard is factory-installed on ECHELON-C models.
Splatter guards must be removed before appliance is fired. WARNING! Risk of
Fire! Remove the splatter guard before lighting the appliance. Shut off gas to
the appliance when the splatter guard is in place to prevent accidental
operation.
Finishing Instructions
It is important to follow the framing and finishing instructions to ensure
proper placement of fireplace into the surrounding framing/finishing
materials. Wall sheathing materials 1/2 in. thick are specified in this
installation manual to properly align with the factoryincluded non-combustible
material. WARNING! Risk of Fire! Factory-included non-combustible board MUST
be installed. DO NOT remove or cover it with combustible material, such as:
· Drywall (gypsum board) · Plywood · Materials that do not meet the ASTM E 136
Non-com-
bustibility standard (below). Removal of installed, non-combustible board
and/or use of materials not meeting the ASTM E 136 standard could cause fire.
Non-Combustible Materials Specification Material which will not ignite and
burn. Such materials are those consisting entirely of steel, iron, brick,
tile, concrete, slate, glass or plasters, or any combination thereof.
Materials that are reported as passing ASTM E 136, Standard Test Method for
Behavior of Materials in a Vertical Tube Furnace at 750 ºC.
WARNING! Risk of Fire! Maintain specified air space clearances to
combustibles. Inadequate air space could cause overheating and fire.
Finishing Materials
NOTICE: The maximum finishing material not only includes the decorative finish
materials (marble, tile, slate, etc) but also the thin set, lath, and adhesive
used to attach the decorative finish material.
NOTICE: Hearth & Home Technologies recommends using multiple pieces of
decorative finish material around the opening of the appliance to reduce the
chances of the material cracking. A single piece of decorative finish material
(such as marble or granite) is more susceptible to cracking due to uneven
heating and cooling which causes temperature differentials within the material
itself. The use of multiple pieces will reduce the temperature differentials
in each piece and reduce the likelihood of cracks. In addition to using
multiple pieces of decorative finish material, the installation of the Passive
Heat optional heat management system will also reduce the chances of cracking.
62
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
B. Drywall Installation
Introduction
If the desired finished fireplace installation does not utilize non-
combustible finishing materials (such as tile, marble, stone, etc.), special
attention must be paid to the installation of drywall/gypsum wallboard to the
side joints of the non-combustible board to minimize potential development of
cracking and paint discoloration. Hearth and Home Technologies has tested the
following methods and materials and therefore recommends the following steps
for the best drywall performance.
Attaching Non-Combustible Board When finishing the wall around the fireplace,
it is critical that wall sheathing be fastened properly. Wall sheathing
fasteners, such as screws or nails, are not permitted in some locations. See
Figure 10.1.
It is acceptable to pre-drill holes and use self-tapped screws in the factory-
included non-combustible board which may be used to lathe (a backer for tile,
marble, etc.). Screws being installed through the installed noncombustible
board should be self-tapping type with a maximum length of 2 inches. See
Figure 10.1.
When installing finish material on the lower cover panel, DO NOT drill or
install screws longer than 3/4 of an inch. Screws longer than 3/4 of an inch
could penetrate the lower cover panel causing damage to components or
penetrate the gas line. See Figure 10.1.
WARNING! Risk of Fire! DO NOT use screws longer than two inches when attaching
finishing materials to installed non-combustible material. Screws longer than
two inches will compromise clearance and could cause overheating and fire.
WARNING! Risk of Fire, Explosion or Asphyxiation! DO NOT use screws more than
3/4 of an inch long on lower cover panel. Longer screws may penetrate gas line
or damage valve or electrical components.
MAXIMUM SCREW LENGTH = 2 INCHES (INSTALLED NON-COMBUSTIBLE BOARD)
NON-COMBUSTIBLE MATERIAL ONLY IN THIS AREA
2 IN.
MAXIMUM SCREW LENGTH = 3/4 INCH (LOWER COVER PANEL)
The appliance is designed to mate with 1/2 in. wall sheathing materials such
as drywall, plywood, wood composites, or non-combustible materials.
To ensure good adhesion of drywall compounds and tape, thoroughly clean the
non-combustible board and surrounding drywall to remove dust. The non-
combustible board may be primed with a high-quality PVA primer.
Filling and Finishing Seams
1. Step 1: Fill all gaps and joints between the noncombustible board pieces
and the drywall with a general purpose chemically setting joint compound such
as Durabond® 45 Joint Compound manufactured by USG (Sheetrock® brand),
recommended by Hearth & Home Technologies. Use a drywall knife to firmly press
the joint compound into all gaps. See Figure 10.1. Allow these joints to dry.
2. Step 2: All joints are to be taped with fiberglass mesh tape 1 7/8″
minimum width, and embedded with Setting-Type joint compound, such as with
Durabond® Joint Compound manufactured by USG (Sheetrock® brand), or
equivalent. Allow these joints to dry.
3. Step 3: Depending on the technique used in steps 1 and 2, two to three
finishing coats are required to provide a smooth and durable finish. Hearth
and Home Technologies recommends a lightweight or allpurpose compound. Allow
each coat to properly cure. Allow the finishing coat(s) to cure for 24 hours
before operating appliance.
WARNING! Risk of Fire! DO NOT apply combustible materials beyond the minimum
clearances. Comply with all minimum clearances to combustibles as specified in
this manual. Materials overlapping into non-combustible zones could ignite and
will interfere with air flow through decorative barrier fronts. WARNING! Risk
of Fire! DO NOT install drywall or other combustible materials directly onto
the installed noncombustible board. Overlapping materials could ignite.
Painting
If desired finishing includes a painted wall, a high-quality 100% acrylic
latex paint with a high-quality latex primer base coat are recommended around
the appliance to limit discoloration. Oil-based or standard acrylic paints may
be more prone to discoloration due to heat exposure.
= NO FASTENERS IN THIS AREA
Note: It is acceptable to use a high temperature silicone sealant to adhere drywall to lower cover panel.
Figure 10.1 Screw Length Requirements
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
63
Drywall Joint-Crack Prevention and Repair
Drywall joints around the fireplace will be affected by exposure to elevated
temperatures, along with other environmental, structural factors due to new
construction, and methods used to install and finish the drywall. If a crack
does emerge adjacent to the fireplace, it can be permanently repaired by
filling it with a paintable latex caulk, followed by repainting.
Some movement of the screws used to secure the noncombustible board to the
appliance/surround framing is expected. If a blemish begins to show over a
screw head, sand the surface to remove the blemish and repaint.
WARNING! Risk of Fire! Maintain specified air space clearances to
combustibles. Inadequate air space could cause overheating and fire. WARNING!
Risk of Fire! Maintain specified air space clearances to combustibles. Failure
to comply with these instructions may cause a fire or cause the appliance to
overheat. NOTICE: The location of the Passive Heat discharge opening could
allow for venting and other construction materials to be visible. It is
acceptable to paint the vent pipe and other construction materials using a
high temperature paint with a minimum of 300 °F continuous exposure rating.
Hearth & Home Technologies recommends using black touch up paint (part number
TUP-GBK-12) available from your Hearth & Home Technologies dealer.
Facing Material
· Facing and/or finishing materials must not interfere with air flow through
decorative barrier fronts.
· Facing and/or finishing materials must never overhang into the glass
opening.
· Observe all clearances when applying combustible materials.
Finishing – Hearth
See Inside Fit or Overlap Method sections to determine the necessary
requirements for installation of a noncombustible hearth for this model. Only
hearths made of non-combustible materials are allowed.
Decorative facing material thickness is measured from the face of the
installed non-combustible board. See Figure 10.2 and Figure 10.3. The fronts
for this appliance are compatible with noncombustible materials. See Figure
10.2 and Figure 10.3. Refer to Section 1.E and 1.F of this manual for
definitions and qualifications of non-combustible and combustible materials.
Specific requirements for each method of installation are described in this
section. Installation of finishing materials can be accomplished by either the
“overlap” or “inside-fit” method, depending on what type of decorative barrier
front is to be installed. See Figure 10.2 and 10.3. Overlap fit decorative
barrier fronts include the Quattro and Loft Forge. The Clean Face Trim Front
(CFT) can be either an inside fit or an overlap fit. See Table 1.
1/2 IN. THICK WALL SHEATHING
NON-COMBUSTIBLE FINISHING MATERIAL OVERLAP FIT = 0-1 IN. THICK INSIDE FIT =
1-4 IN. THICK
FINISHING GUARDS
BOTTOM FINISHING TEMPLATE
Figure 10.2 Finishing and Facing Materials – Single-Sided Models
Decorative Barrier Front Finishing Method
Clean Face Trim (CFT)
Picture Frame Front (PFF) Picture Frame Front (PFF)
Inside Fit
Overlap Fit Overlap Fit Inside Fit
Material Thickness
1-4 inches
0-1 inch 0-1 inch 1-4 inches
Trim Ring Included & Not Used (Option #1) Included & Used (Option #2) Included & Used Not included Not included
Table 1
64
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
1/2 IN. THICK WALL SHEATHING
NON-COMBUSTIBLE FINISHING MATERIAL OVERLAP FIT = 0-1 IN. THICK INSIDE FIT = 1-4 IN. THICK
1/2 IN. INSTALLED NON-COMBUSTIBLE
BOARD
NON-COMBUSTIBLE FINISHING MATERIAL OVERLAP FIT = 0-1 IN. THICK INSIDE FIT = 1-4 IN. THICK
FINISHING GUARDS
FINISHING GUARDS
BOTTOM FINISHING TEMPLATE (Control side only)
Figure 10.3 Finishing Materials – See-Through Models
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
65
C. Decorative Barrier Fronts
WARNING! Risk of Burns! A decorative barrier front is required for this model.
DO NOT operate this appliance without a decorative barrier front in place.
Only decorative barrier fronts certified for use with this appliance model may
be used. Contact your dealer for a list of decorative barrier fronts that may
be used.
Note: See appliance Owner’s Manual for TV mounting guidelines.
The decorative barrier fronts approved for use with this appliance have been
designed to be installed by two methods: Overlap Fit or Inside Fit. Before
beginning the installation, it is important to determine which method will be
used.
Clean Face Trim Front (CFT)
Overlap Fit (0-1 Inch Thick Finishing Method)
Non-Combustible Finish Materials
WARNING! Risk of Fire! DO NOT apply combustible materials beyond the minimum
clearances. Comply with all minimum clearances to combustibles as specified in
this manual. Overlapping materials could ignite.
Note: When a Clean Face Trim decorative barrier front is installed, the
rectangular holes in bottom access panel will be covered.
NOTICE: This one inch maximum not only includes the decorative finish
materials (marble, tile, slate, etc) but also the thin set, lath and adhesive
used to attach the decorative finish material.
1. Remove bottom finishing template from bottom access panel. Verify that
factory-installed finishing guards are installed to ensure finishing material
does not extend into the fireplace opening. See Figure 10.2 and 10.3.
2. The non-combustible finish material, 0-1 inch thick, should be installed
up to the fireplace opening on all four sides, including the bottom access
panel, covering the eight rectangular holes. Refer to Figure 10.4 for minimum
finished opening dimensions.
WARNING! Risk of Fire! DO NOT apply finishing material beyond the finishing
guard. Appliance will overheat if finishing material extends into appliance
opening. NOTICE: Decorative barrier front will not fit properly if finishing
material is applied beyond the finishing guard.
4. Follow Overlap Fit section of the instructions provided with decorative
barrier front.
Decorative Barrier Finishing Method Front
Clean Face Trim (CFT)
Overlap Fit
Material Thickness 0-1 inch
Trim Ring Included & Used
15-3/4 IN.
39-1/8 IN.ECHEL36IN-C/ECHEL36STIN-C 51-1/8 IN.ECHEL48IN-C/ECHEL48STIN-C 63-1/8
IN.ECHEL60IN-C 75-1/8 IN.ECHEL72IN-C
FIREPLACE VIEWING AREA
Figure 10.4 Minimum Finished Opening Dimensions – Clean Face Trim Front Method
66
Majestic · ECHEL36IN-C/STIN-C, ECHEL48IN-C/STIN-C, ECHEL60IN-C, ECHEL72IN-C Installation Manual · 2608-980 Rev. N · 11/21
Clean Face Trim Front (CFT) Inside Fit (1-4 Inches Thick Finishing Method)
Non-Combustible Finish Materials WARNING! Risk of Fire! DO NOT apply combustible materials beyond the minimum clearances. Comply with all minimum clearances to combustibles as specified in this manual. Overlapping materials could ignite.
Note: When a Clean Face Trim decorative barrier front is installed, the
rectangular holes in bottom access panel will be covered.
NOTICE: This four inch maximum not only includes the decorative finish
materials (marble, tile, slate, etc) but also the thin set, lath and adhesive
used to attach the decorative finish material.
There are two options for this method of finishing:
CFT Finishing Method Inside Fit
Trim Ring
Included & Not Used (Option #1)
Included & Used (Option #2)
Without Decorative Trim Ring: (Option #1)
Note: You will not use the trim ring, which is shipped with the CFT front, for
this application.
1. Remove bottom finishing template from bottom access panel. Verify that
factory-installed finishing guards are installed to ensure finishing material
does not extend into the fireplace opening. See Figures 10.2 and 10.3.
2. The non-combustible finish material, 1-4 inches thick, should be installed
up to the fireplace opening on all four sides, including the bottom ac
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>