Mounting humidity sensor (RH sensor)

Installation of a humidity sensor (RH sensor) is possible on all Brink heat recovery appliances, with the Renovent Excellent appliance only from software version S1.05

Mounting humidity

  1. Duct from dwelling

  2. Drilling hole; minimum ø18 mm – maximum ø25 mm
    Mounting humidity

  3. Isolated metal duct

  4. EPE duct

  5. Humidity sensor (RH sensor)

  6. Screw pozidrive 3,5 x 19

  7. PCB spacer

5A Renovent Excellent 300/400
Renovent Excellent

  1. Remove cover
  2. Remove breakout
    Renovent Excellent

5B Renovent Excellent 180
Renovent Excellent

  1. Renovent 180 Excellent appliance
  2. Control board
  3. Humidity sensor (RH sensor)
  4. Cable comes with humidity sensor. Cut out an opening in the available grommet for feeding through the sensor cable.
  5. Duct “Extract air”

C1 = Brown
C2 = White
C3 = Green
C4 = Yellow

5C Renovent Sky 150
Renovent Sky

  1. Sky 150 appliance
  2. Control board
  3. Humidity sensor (RH sensor)
  4. Cable comes with humidity sensor. Cut out an opening in the available grommet for feeding through the sensor cable.
  5. Duct “Extract air”

C1 = Brown C2 = White
C3 = Green
C4 = Yellow

5D Renovent Sky 300
Renovent Sky

  1. Sky 300 appliance
  2. Control board
  3. Humidity sensor (RH sensor)
  4. Cable comes with humidity sensor. Cut out an opening in the available grommet for feeding through the sensor cable.
  5. Duct “Extract air”

C1 = Brown
C2 = White
C3 = Green
C4 = Yellow

5E Flair HRV appliance
Flair HRV appliance 

  1. Flair HRV appliance (A Flair 325 is shown as an example)
  2. Control board
  3. Humidity sensor (RH sensor)
  4. Cable comes with humidity sensor. Cut out an opening in the available grommet for feeding through the sensor cable.
  5. Duct “Extract air”

C1 = Brown
C2 = White
C3 = Green
C4 = Yellow

Setting humidity sensor (RH sensor)

Renovent 180/ 300/400 Excellent
After installing the humidity sensor (RH sensor) it must be activated in the settings menu step number 30 to ON. Optionally, the sensitivity of the sensor can be altered by means of step number 31. Process for adjusting the value (s) in the settings menu of the Renovent Excellent, see § 6.3 of the installation instructions. 

Step no Description Factory setting Adjusting range
30 Humidity sensor (RH sensor) OFF OFF = Humidity sensor (RH sensor) not

active ON = Humidity sensor (RH sensor) active
31| Sensitivity| 0| +2 = most sensitive 0 = default setting -2 = least sensitive

Check the operation of humidity sensor (RH sensor)
Select step number 9 in readout menu (See §6.4 of the installation instructions)
Check the operation
Check the operation

Sky 150/300 Excellent
After installing the humidity sensor (RH sensor) it must be activated in the settings menu step appliance control unit number 29 to ON. Optionally, the sensitivity of the sensor can be altered by means of step number 30. Process for adjusting the value (s) in the settings menu of the Renovent Sky, see § 6.5.3 of the installation instructions.

Step no Description Factory setting Adjusting range
29 Humidity sensor (RH sensor) OFF OFF = Humidity sensor (RH sensor) not

active ON = Humidity sensor (RH sensor) active
30| Sensitivity| 0| +2 = most sensitive 0 = default setting -2 = least sensitive

Check the operation of humidity sensor (RH sensor)
See RH value Information menu installer (See § 6.5.4 of the installation instructions).

Flair HRV appliance
After installing the humidity sensor (RH sensor) it must be activated in the settings menu step number 7.1 to ON. Optionally, the sensitivity of the sensor can be altered by means of step number 7.2. Process for adjusting the value (s) in the settings menu of the HRV appliance, see the installation instructions.

Step no. Description Factory setting Adjusting range
7.1 Humidity sensor (RH sensor) OFF OFF = Humidity sensor (RH sensor) not

active ON = Humidity sensor (RH sensor) active
7.2| Sensitivity| 0| +2 = most sensitive 0 = default setting -2 = least sensitive

Check the operation of humidity sensor (RH sensor)
Select on touchscreen and go with and to readout value RH sensor
Check the operation

Support

Brink Climate Systems B.V. P.O. Box 11, NL-7950AA Staphorst
T : +31 (0) 522 46 99 44
E : info@brinkclimatesystems.nl
www.brinkclimatesystems.nl

BRINK Logo

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals