SIEMENS AD2-XHR Air Duct Monitoring Housings Instruction Manual

June 9, 2024
SIEMENS

SIEMENS AD2-XHR Air Duct Monitoring Housings

SIEMENS AD2-XHR Air Duct Monitoring Housings product

INTRODUCTION

Models AD2-P, AD2-PR and AD2-XHR (AD2 Series) from Siemens Building Technologies, Inc., are air duct monitoring housings containing sampling tubes. When used with a compatible smoke detector, smoke and combustion products are detected for shutdown of the duct system and/or operation of supplementary equipment as provided by the system control panel. See the following chart for usage.

Model Compatible Detectors Relay
AD2-P PE-11, FP-11, HFP-11, HFPO-11 No
AD2-PR PE-11 Yes
AD2-XHR FP-11, HFP-11, HFPO-11 Yes
  • For compatible control equipment, see charts on the page 14 of this manual.

TECHNICAL DATA

AIR DUCT CONDITIONS

Temperature Range:
32OF (0OC) – 100OF (38OC) per UL 268/268A

Altitude Range:
AD2-P, AD2-PR and AD2-XHR — No altitude limitations

Relative Humidity Range:
10-85% (non-condensing/non-freezing)

Air Duct Velocity Range:
100-4000 ft/min – AD2-P, AD2-PR and AD2-XHR

Sampling Tube Pressure Range of Differences:
Greater than 0.01 and less than 1.2 inches of water column
These air duct detectors are designed for detection and control of products of combustion in a duct system. They are not to be used for open area protection.
DO NOT USE air duct detectors with Alarm Verification.

APPLICATION

The AD2 Series duct smoke detectors provide early detection of smoke and products of combustion present in air moving through an HVAC duct supply, return, or both. These devices are designed to prevent the recirculation of smoke in areas by the air handling system’s fans and blowers. Complete systems may be shut down in the event of smoke detection.

  • For the correct installation of a duct smoke unit please refer to NFPA 72 (National Fire Alarm Code), NFPA 90A (Standard for Installation of Air Conditioning and Ventilation Systems), and NFPA 92A (Recommended Practice for Smoke Control Systems).

OPERATION

When the Models AD2-P, AD2-PR and AD2-XHR are operating, a sample of air is drawn from the duct and passed through the sampling chamber by means of the input sampling tube. The air sample passes through the smoke detector mounted in the duct housing and is exhausted back into the duct through the outlet tube.
This detector is equipped with cover removal switch (SW1) that instantly provides a trouble condition upon removal of the clear cover. For all testing and inspection with the cover removed, the cover removal switch (designated as SW1 on PCB) must be manually depressed to simulate normal operation.

LED Indicator
The AD2-P, AD2-PR and AD2-XHR contain an LED indicatorm(located on the smoke detector) capable of flashing either one of three distinct colors: green, yellow, or red. During each flash interval, the microprocessor based detector checks the following:

  •  for smoke in its sensing chamber
  •  that its critical smoke sensing electronics are operating.
COMPATIBLE CONTROL EQUIPMENT

AD2-P AND AD2-PR USING PE-11 DETECTOR

Module Equipment Compatibility Identifier| Module Installation/ Wiring Instructions
---|---
CDC-4 (Fire Finder-XLS)| P/N 315-034100-3
CP-35 (SYSTEM 3)| P/N 315-084902-22
*CZM-1B6 (MXL, MXL-IQ)| P/N 315-095355-6
CZM-4 (MXL, MXL-IQ)| P/N 315-090826-10
HZM (Fire Finder-XLS, FS-250)| P/N 315-034850-3
SXL-EX| P/N 315-095997-6
SZE-4X (SXL-EX)| P/N 315-096018-5
SZE-8AX (SXL-EX)| P/N 315-096022-5
ZU-35 (SYSTEM 3)| P/N 315-083222-15

AD2-P AND AD2-XHR USING FP-11 DETECTOR

Module Equipment Compatibility Identifier| Module Installation/ Wiring Instructions
---|---
ALD-2I (MXL, MXL-IQ)| P/N 315-091464-10
MMB-2 (MXL)| P/N 315-095097-8
MMB-3 (MXL)| P/N 315-048860-3
SMB-2 (MXL-IQ)| P/N 315-095931-7

AD2-P AND AD2-XHR USING HFP-11 OR HFPO-11 DETECTOR

Module Equipment Compatibility Identifier| Module Installation/ Wiring Instructions
---|---
DLC (Fire Finder-XLS)| P/N 315-033090-6
FS-DLC (FS-250)| P/N 315-049353-4

The detector model number is the compatibility identifier.

  • Control equipment does not support remote accessories; e.g., lamps or relays.

ELECTRICAL RATINGS FOR PE-11

Voltage 16-27 VDC
Ripple 3V peak-to-peak
Supervisory Current 110 uA max.
Start-up Time 50 seconds max.
PE-11 Detector PE-11 Detector + Remote Device
--- ---
Alarm Current 33 – 50mA

ELECTRICAL RATINGS FOR FP-11, HFP-11 AND HFPO-11
Electrical ratings are not provided here for these detectors. Guidance for detector loop loading, along with loop wire electrical specifications are provided in the applicable control unit instructions given in the above Compatible Control Equipment tables.
Based on the results of these checks, the LED indicator flashes as follows:

Flash Color Condition Flash Interval (Seconds)
PE-11 FP-11/HFP-11/ HFPO-11
Green Normal supervisory operation. 7
Yellow Detector requires service (cleaning or repair) or is operating beyond
its environmental specifications. 7-30 4
Red Alarm
No Flashes Detector is not powered, or requires repair.

SIEMENS AD2-XHR Air Duct Monitoring Housings 01Typical Mounting of Duct Housing

TYPE A: CLOSED SYSTEM – NO EXHAUST
SIEMENS AD2-XHR Air Duct Monitoring Housings 02TYPE B: PROVISION FOR EXHAUSTING SOME PERCENTAGE OF RETURN AIR
SIEMENS AD2-XHR Air Duct Monitoring Housings 03TYPE C: RETURN AIR UNDER POSITIVE PRESSURE FROM SEPARATE BLOWER
SIEMENS AD2-XHR Air Duct Monitoring Housings 04Recommended Locations in Duct Systems

MOUNTING THE AIR DUCT HOUSING

Location on Duct System
This guideline contains general information on duct smoke detector installation, but does not preclude the NFPA documents listed. Siemens Building Technologies, Inc. assumes no responsibility for improperly installed duct detectors. To determine the correct installation position for an AD2 Series duct smoke detector, the following factors must be considered.

  1.  A uniform non-turbulent (laminar) airflow between 100 ft/min. to 4,000 ft/min. must be present in the HVAC duct. To determine duct velocities, examine the engineering specifications that define the expected velocities or use an Alnor model 6000AP velocity meter (or equivalent).
  2.  To minimize the impact of air turbulence and stratification on performance, a duct smoke detector should be located as far as possible downstream from any obstruction (i.e. deflector plates, elbows, dampers, etc.). In all situations, confirmation of velocity and pressure differential within specifications is required. The pressure differential between the input sampling (high pressure) tube and outlet (low pressure) tube for the AD2 Series smoke duct detector should be greater than 0.01 inches of water and less than 1.2 inches of water.
  3.  Identify a code compliant location (supply or return side, or both) for the installation of the duct unit that will permit easy access for viewing and serviceability.
  4. When installing on the return side, install duct units prior to the air being exhausted from the building or diluted with outside “fresh” air.
  5. When installing duct smoke units downstream of filters, fires occurring in the filters will be detected, but if the filters become blocked, insufficient air flow through the duct unit will prevent the correct operation of the duct detector. Duct units installed in the supply air side may monitor upstream equipment and/or filters.
  6.  Where possible, install duct detectors upstream of air humidifiers and downstream of dehumidifiers.

MAINTENANCE

The performance of the air duct detector unit may be adversely affected by dirt or foreign matter on the sampling tubes or detector. If the air holes in the input sampling tube become restricted, the unit cannot receive a proper air sample, and performance is impaired. It is recommended that the sampling tubes be checked and cleaned periodically.
The detector maintenance program should consist of periodic cleaning of dust from the detector head by using a vacuum cleaner. For cleaning Models PE-11, FP-11, HFP-11 or HFPO-11, refer to the detector’s Installation Instructions (See Table A).
The cleaning and test program is recommended for 6 month intervals, or more frequently, if needed, depending on the individual detector environment. Consult your local code and AHJ requirements for required maintenance schedules.

  * Under no circumstances is the detector portion of the unit to be disassembled by anyone other than an authorized Siemens Building Technologies, Inc. Systems Technician. For service, contact your nearest authorized Siemens Building Technologies, Inc. Service Representative.
  * If the fire alarm system is connected to a central station or fire department, or operates external devices such as fans, extin-guishers, etc., connected, notify appropriate personnel and disconnect the external devices until all tests are completed. After testing, reset the system, reconnect the devices, and notify the personnel that the system is operating again.  

These tests ensure that the detector is within its listed and marked sensitivity range. For additional instructions on applying the Sensitivities mode, refer to the FireFinder-XLS Manual, P/N 315-033744, or the DPU Manual, P/N 315-033260.
Functional Test
Smoke Testing
Using TG-11 smoke test canister with testing nozzle model AD-TGN (purchased separately) available from Siemens Building Technologies, Inc., insert the test gas nozzle into the hole in the red plug in the unit cover. Press can against cover for about 1/2 second to release gas into the chamber.

  * DO NOT SPRAY GAS FOR MORE THAN ½ SECOND. OVER-USE OF TEST GAS MAY RESULT IN DETECTOR CONTAMI-NATION.  

After 15 to 20 seconds the detector will go into alarm, illuminating the detector LED and causing the duct unit functions to operate; alarm relays will change state, and the alarm related remote accessories, if attached, will function. If no test gas is available to conduct functional testing, remove cover and, while holding down the cover removal switch, blow smoke from a smoldering cotton wick or punk directly at the head to cause an alarm. The alarm indicator on the detector should illuminate within one minute.
Refer to the following Installation Instructions for additional information on testing each of these detectors:

**Detector**

| Installation Instruction
---|---
PE-11| 315-094198
FP-11| 315-095921
HFP-11| 315-033290
HFPO-11| 315-034800

The FP-11, HFP-11 and HFPO-11 detectors can also be tested individually using the DPU. Refer to the DPU Manual, P/N 315-033260.

  1. To prevent false alarms, the duct detector should not be mounted in areas of extreme high or low temperatures, in areas where high humidity exists, or in areas where the duct may contain gases or excessive dust.

Duct Preparation
The AD2 Series Housings come with an installation kit that contains the following items:

  • Short return (outlet) sampling tube
  •  Stopper
  • Two #12 x 3/4” sheet metal screws
  • Mounting template (packaged separately)

Remove mounting template from the installation kit. Remove paper backing from the mounting template and affix it to the duct at the desired location. Using the template as a guide, drill (2) mounting holes, 3/32″ (2.5mm) for the #12 X 3/4” sheet metal screws packaged in the installation kit. Drill or punch (2) 1¼” (32mm) holes for input sampling and outlet tubes, using the template as a guide. Clean all holes.

Sampling Tube Installation

The AD2 Series duct smoke detectors use a specially notched sampling tube, which may be ordered separately in one of four standard lengths.
ST-10    For duct widths of 6″ to 1.0’
ST-25    For duct widths of 1.0’ to 3.0’
ST-50    For duct widths of 3.0’ to 5.0’ (requires support)
ST-100*  For duct widths of 5.0’ to 10.0’ (requires support)

  • This model is supplied as two 5 ft. sections with a coupling.

Assembly is required for installation.

  • Each model is manufactured with a different number and size of sampling holes. Only the specific tube must be used for the specified duct width.

Standard sampling tubes are steel tubes with air intake holes drilled the entire length of the tube. These tubes can be cut to length and must span at least 80% the width of the duct. Sampling tubes over 3.0’ must be supported on the opposite side of the duct. To ensure the correct operation, the red stopper (stopper in installation kit) must be inserted in the end of the air input sampling tube. If the input tube protrudes through the opposite side of the duct, the opening around the tube must be sealed. For custom duct widths, always use the next longest standard size and cut down to the exact requirement.
Once the airflow direction has been determined
TUBE SUPPORT ONLY FOR DUCTS GREATER THAN 3 FEET WIDE
SIEMENS AD2-XHR Air Duct Monitoring Housings 05Sampling Tube Orientation
insert the input and outlet tubes into the duct housing.

  1.  Remove the cover from the housing.
  2.  Loosen the screw and rotate the tube retainer until the input tube is inserted and oriented properly. Ensure that the notched end of the tube is inside the housing and that the air input sampling tube is positioned so that the input holes are directly facing the airflow.
  3. Once the tube is installed, rotate the retainer back into place and tighten screw.
  4. Install the outlet tube in the remaining position. Once the tube is installed, rotate the retainer back into place and tighten screw.

Mounting
After securing the input and outlet tubes to the duct smoke unit, (or initially placing the tubes through the 1¼” holes drilled or punched in the HVAC duct to accept the input and outlet tubes and then attaching them to the duct unit), hold the duct unit assembly in position and use (2) # 12 X 3/4” sheet metal screws (packaged in the installation kit) to secure the duct smoke detector to the HVAC duct sheet metal.
When replacing a detector with a different model, be aware that existing detector accessories connected to the base or air duct housing that were compatible with the old detector may not be compatible with the new detector. Always read the Installation Instructions accompanying the detector to determine detector and accessory compatibility.

Installation Of Smoke Detectors

To Install:

  • Remove cover by loosening the four screws. Take off the cover and set it aside.
  •  Align detector with base and insert detector.
  •  Rotate detector clockwise while gently pressing on it until the detector drops fully into base.
  •  Then rotate the detector clockwise until it stops and snaps in place.
  • Replace cover and tighten the four screws.

To Remove:

  • Rotate the detector counterclockwise until stop is reached.
  • Pull detector out of base.

TESTING
Only qualified service personnel should test these units. To assure proper operation of the detector and control panel, both the Sensitivity and the Functional tests should be conducted. The minimum test schedule may be found in the current edition of NFPA 72 for installations in the U.S.

Sensitivity Test
The PE-11 detector monitors its smoke sensitivity automati-cally and requires no test equipment. A green flash of the detector LED about every seven seconds indicates that the smoke sensitivity is within its listed limits.

  • The following detector models are analog types that must be programmed for the air duct application using the control unit configuration tool; that is, CSG-M, Zeus or
    FS-CT2, as applicable.

To test the FP-11 detector refer to its installation instructions. See Table A on page 12.
To test the HFP-11/HFPO-11 detector refer to its installation instructions. See Table A on page 12.

NOTES:

  1.  The relay contacts are shown after a reset pulse, which represents the non-alarm condition.
  2.  Refer to the RL-HW / RL-HC Installation Instructions, P/N 315-033230.
  3. The green grounding screw in the wiring compartment of the air duct housing is not used.

If the relay contacts are being used to control 120 VAC operated equipment, ensure that the conduit is properly attached to the internal metal ground strap, using the proper conduit locking nuts. Failure to provide proper grounding may result in fatal electrical shock and violation of national and local codes.

Air Duct Sampling Tube Pressure Measurement
The Model PDM-3 Pressure Differential Measuring device should be used to ensure that the sampling tube pressure differential is within the specified limits. The differential pressure between the two tubes should be greater than 0.01 inches of water and less than 1.2 inches of water. Qualified personnel should take measurements in accordance with the PDM-3 instructions, P/N 315-085535.

WIRING
Conduit Knockouts To remove plastic knockout, first cut the plastic tab on the specific knockout. SIEMENS AD2-XHR Air Duct Monitoring Housings
07Removing the Knockouts
to locate the tab. Then, using a screw driver placed at the tab location, tap with a hammer until the knockout breaks out. Clean the hole before installing conduit.

Wiring
The AD2-P, AD2-PR and AD2-XHR should be connected as shown in Figures 5, 6 and 7.
SIEMENS AD2-XHR Air Duct Monitoring Housings 08
SIEMENS AD2-XHR Air Duct Monitoring Housings 09Typical Connections for the AD2-P / AD2-PR Using PE-11 Detectors SIEMENS AD2-XHR Air Duct Monitoring Housings
10Typical Connections for the AD2-P / AD2-XHR Using FP-11 DetectorsSIEMENS AD2-XHR Air Duct Monitoring Housings
06Typical Connections for the AD2-P / AD2-XHR Using H-Series Detectors Note any limitations on the number of detectors and restrictions on the use of remote devices permitted for each circuit.
The AD2-P is used with the HFP-11 detector in the Fire Finder-XLS or FS-250 System. The AD2-XHR must be used for the relay version. Also, all optional accessories in the same loop must be compatible with the detector series being used. These devices should be interconnected as shown in Figure 7 and wired to the DLC or FS-DLC. (Refer to the DLC Installation Instructions, P/N 315-033090, or the FS-250 Manual, P/N 315-049353, as applicable.) The HFP-11 and HFPO-11 are polarity insensitive detectors. Line 1 and Line 2 can be either line of the loop. Note any limitations on the number of detectors and restrictions on the use of remote devices permitted for each circuit.

NOTES:

  1.  Up to 30 air duct housings can be installed on one initiating circuit, except as noted in Note 2.
  2. When an AD2-PR is used to control a fire safety function, the AD2-PR must be the ONLY device on the initiating circuit.
  3. Do not use looped wire under base terminal.
  4. Break wire run to provide supervision of connection.
  5. The green grounding screw in the wiring compartment of the air duct housing is not used.

If the relay contacts are being used to control 120 VAC operated equipment, ensure that the conduit is properly attached to the internal metal ground strap, using the proper conduit locking nuts. Failure to provide proper grounding may result in fatal electrical shock and violation of national and local codes.
SIEMENS AD2-XHR Air Duct Monitoring Housings 11
SIEMENS AD2-XHR Air Duct Monitoring Housings 12 NOTES:

  1.  The relay contacts are shown after a reset pulse, which represents the non-alarm condition.
  2. The green grounding screw in the wiring compartment of the air duct housing is not used.

If the relay contacts are being used to control 120 VAC operated equipment, ensure that the conduit is properly attached to the internal metal ground strap, using the proper conduit locking nuts. Failure to provide proper grounding may result in fatal electrical shock and violation of national and local codes.