SIEMENS FT2018-U1 Tabular Annunciator Instruction Manual

June 9, 2024
SIEMENS

Tabular annunciator
FT2018-U1/FT2018-R1/FT2019-U1/FT2019-R1
Installation InstructionsSIEMENS FT2018 U1 Tabular
Annunciator

FT2018-U1 Tabular Annunciator

SIEMENS FT2018 U1 Tabular Annunciator - Tabular
annunciator

Intended use
The FT2018/FT2019 tabular annunciator enables the fire detection system to be displayed and operated in a simplified way. The FT2018 provides 2×16 LEDs to display alarm/trouble events. The FT2019 provides 2×32 LEDs to display alarm/trouble events. Both devices are operated on the UFP line.

Package contents

  • FT2018-U1/FT2018-R1 or FT2019-U1/FT2019-R1
  • Cable ties (2 pcs)
  • EOL jumper connecter (1 pcs)

Safety instructions

Risk of injury to people and damage to property
Please observe the following safety instructions:

  • The devices are only intended for stationary installation in dry rooms.
  • The devices can only be connected to UFP line.
  • If panel auxiliary power is not used, an UL listed/recognized for fire use, regulated, power limited 24 V c.c. power supply is required.
  • Take static discharge when using the FT2018/FT2019.

Legend

  1. Stub for mounting cover (2 pcs.)
  2. Shield terminal
  3. Earth ground terminal
  4. Mounting holes (8 pcs.)
  5. Cable tie point
  6. Cable entries (2 pcs.)
  7. Holes for hanging front panel over stub (2 pcs.)
  8. Dip-switch
  9. Screws (2 pcs.)
  10. EOL jumper
  11. Connection terminals for UFP line and power supply
  12. Front panel earth ground connection

Mounting instruction

  1. Break the required cable entries (6) on the backbox.
  2. Mark the drilling points for the 3 mounting holes (4), drill the holes and insert the anchors (not supplied); or use the pre-drilled mounting holes for installation on a 1 gang, 2 gang, or 4” square standard electrical box.
  3. Pull the cables for the UFP and power supply, through the breakout openings (6) on the backbox.
  4. Screw the backbox tightly in place.
  5. Connect the cable to the terminal (11) in accordance with the connection diagram.
  6. Configure Dip-switch (8) and EOL jumper (10).
  7. Connect the green earth ground cable from front panel (12) to backbox (3).
  8. Hook the front panel with the holes (7) over the stubs (1) on the backbox.
  9. Press the front panel down over the backbox, screw (9) upwards and fix the front panel in place.

Dip-switch
8-digit Dip-switch is used for setting address and baud rate.
The first 1-4 digits are for setting address and the 7, 8 digits are for setting UFP communication baud rate. The 5 and 6 digits are reserved for future use.

Add. Dip-switch
1 2
1 On
2 Off
3 On
4 Off
5 On
6 Off
7 On
8 Off
Baud Rate Dip-switch
--- ---
7 8
9600 bps Off
19200 bps On
38400 bps Off
57600 bps On

Technical data

| FT2018| FT2019
---|---|---
Weight| 3.064 lb| 4.021 lb
Dimensions (W x H x D) (In: inch)| 8.110×7.362 x1.949| 11.417×7.362 x1.949
Storage temperature| 14…140 °F
Operating temperature| 32…120.2 °F
Humidity| 93`)/0 rel.
Housing| IP30
Operating voltage| 24 VCD Nominal 18.8…27.2 VCD
Operating current (quiescent)| 25 mA| 25 mA
Action current| 65 mA| 105 mA

Issued by Siemens Industry, Inc.
Smart Infrastructure 8 Fernwood Road
Florham Park, NJ 08932
Tel. +1 973-593-2600
www.sbt.siemens.com/FIS
© Siemens Industry, Inc., 2019
Technical specifications and availability subject to change without notice.
Doc No. A6V11269908_—-_c
102061952
firealarmresources.com