SIEMENS FDA241 ASD Aspirating Smoke Detector Instructions

June 9, 2024
SIEMENS

SIEMENS FDA241 ASD Aspirating Smoke Detector

Siemens aspirating smoke detector (ASD) for the addressed FDnet/C-NET de- tector line or for standalone operation

  • Patented technology
  • Early detection of a wider spectrum of particle sizes in the air
  • Configuration using the USB interface or the control panel via FDCC221S (op-tional)
  • ‘ASD Asyst-Tool’ software to assist with pipe configuration
  • Unique dust-resistant detection chamber
  • Intuitive front indicator for airflow and smoke value
  • Access to service functions
  • Different event protocols
  • Offline/online configuration supported
  • Cleaning function (FDA241)
  • 4…20 mA output

Properties

  • Extended optical detection thanks to dual wavelengths (blue and infrared): The aspirat-ing smoke detectors FDA241 and FDA221 use dual-wavelength technology to trigger an alarm at the earliest possible moment. They are designed to protect small and medium-sized business-critical environments for monitoring areas of up to 800 m2 (FDA241) or 500 m2 (FDA221). The detectors continually suck in air through a pipe system via their aspirating holes. The air is fed into a uniquely designed detection chamber, in which tiny smoke particles are detected by scattered light.
  • Lower mounting and service costs: The aspirating smoke detectors FDA241 and FDA221 can be used on an FDnet/C-NET detector line. For this purpose, communication transponder FDCC221S is required.
  • Configuration using the USB interface or the control panel via FDCC221S (optional): All detector configurations, maintenance work, and alarm and fault management processes can be carried out at a central location – the fire control panel. This ensures better con-trol while also reducing the costs of the overall solution.
  • Out-of-the-box’ mounting and commissioning: Installation is simple thanks to combined functions for normalizing smoke values and airflow, as well as appropriate presettings for alarm and fault thresholds.
  • ASD filter box FDAZ292 available as an accessory: Dust and other dirt is filtered out of the aspirated air and does not get into the aspirating smoke detector. The filters in the ASD filter box are easy to replace.

Use

Aspirating smoke detectors are used for early detection of smoke-generating fires in rooms and equipment. They are especially suited to applications in which point detectors are pushed to their limits, cannot be used or can only be used with restrictions.
The aspirating smoke detector continually takes air from the monitored room using a connec-ted pipe system with defined aspirating holes. The air is supplied to the detection chamber and is analyzed for smoke particles using the detector installed there. The sensitivity of the detector can be adjusted.
The position and size of the aspirating holes is calculated using the ‘FXS2056 ASD Asyst Tool V2’ software. The calculation ensures that the air passes from the aspirating hole to the detector in the time specified and with the required calculated sensitivity.

The ‘FXS2056 ASD Asyst Tool V2’ software replaces the ‘FXS2055 ASD Asyst Tool’ soft-ware.

Examples of application

  • Cavities such as false ceilings or false floors
  • Clean rooms
  • Rooms the height of which is greater than that permitted for point detectors
  • Rooms with electromagnetic fields which influence the function of point detectors
  • Large rooms up to 800 m²
  • Separate monitoring of control cabinets and electronics cabinets
  • Data centers
  • Telecommunication centers
  • Mounting lines
  • Cable tunnels
  • Conveyor belts

Applications with a filter box

  • Rooms with polluted air, in which the pollution has impaired the performance of optical point detectors
  • Mounting lines
  • Recycling facilities
  • Cement factories
  • Mining industry
  • Subway stations
  • Agricultural operations
  • All other applications with visible dust load

Functions

Indication
The display contains clear, comprehensible bar graphs for smoke and airflow, as well as an alarm indicator, an error indicator, and a dust indicator (FDA241).
When the housing cover is open, the operator has access to the ‘Reset’, ‘Normalize Smoke’, and ‘Normalize Flow’ functions, as well as the mini USB connector.

SIEMENS FDA241 ASD Aspirating Smoke Detector-fig2

Legend for the response indicators

SIEMENS FDA241 ASD Aspirating Smoke Detector-fig3 SIEMENS FDA241 ASD Aspirating Smoke Detector-fig4

Opening the detector

CAUTION
Damage to the connection cable
In order to prevent damage to the connection cable when positioning the housing cover, make sure that the connection cable has been routed correctly.

The service area for the detector can be accessed in two ways.

  • Partial access:
    • Remove the two screws on the top of the detector.
    • Slide the housing cover up until you hear it snap into place.
  • Full access:
    • Remove the two screws on the top of the detector.
    • Slide the housing cover up until you hear it snap into place.
    • Pull the housing cover out slightly at the sides and lift it up.
    • Remove the housing cover.

Service LED indicators and buttons

  • Flow OK
    As soon as the selftest for normal operation has been completed successfully, the ‘Flow OK’ LED starts to flash.

  • Smoke OK
    As soon as the selftest for normal operation has been completed successfully, the
    ‘Smoke OK’ LED starts to flash.

  • Alarm
    In the event of a smoke alarm, the ‘Alarm’ LED starts to flash.

  • Normalization of the airflow
    To determine the nominal airflow of the detector, perform this function during commissioning. The nominal value established during normalization of the airflow forms the setpoint value for monitoring the airflow during normal operation.
    To perform this function, use a thin object (such as a paper clip or a watchmaker’s screw-driver) to press the button in the opening.
    Once you have finished with this function, press the button in the opening again.
    The smoke detector uses standard values for monitoring during normalization.

  • Normalization of the smoke density

    • To determine the nominal air quality in relation to the smoke density, perform this function during commissioning. \
    • The nominal value established during normalization forms the set-point value for monitoring the smoke density during normal operation.
    • To perform this function, use a thin object (such as a paper clip or a watchmaker’s screw-driver) to press the button in the opening.
    • Once you have finished with this function, press the button in the opening again.
    • The smoke detector uses standard values for monitoring during normalization.

The detector provides information about the current normalization process via FDnet/C-NET (no distinction is made between smoke and airflow).

  *  **Reset button**  

Use the reset button to reset all of the detector’s status indicators. These indicators can refer to fire alarms or airflow events. Resetting the fire alarm also resets the associated relay.
If the detector is operated on the FDnet/C-NET, the alarms and the associated relays are not reset.

  *  **USB connection**  

You can use a mini USB cable to connect the detector to a Windows PC. To set up the de-tector, use the configuration tool ‘FXS2051 ASD Configuration Tool’.

  *  **Test function LED**  

Hold the ‘Buzzer silence’ button down for 5 seconds. The LEDs on the display are tested with 3 different brightness settings.

If the aspirating smoke detector is to be operated on the FDnet/C-NET, the communication interface FDCC221S (S24218-A201-A2) must be ordered separately.

Accessories

SIEMENS FDA241 ASD Aspirating Smoke Detector-fig9 SIEMENS FDA241 ASD Aspirating Smoke Detector-fig10 SIEMENS FDA241 ASD Aspirating Smoke Detector-
fig11

Type Overview

Type Designation Order number Weight [kg]
FDA241 Aspirating smoke detector (8H) S54333-F17-A1 1.495
FDA221 Aspirating smoke detector (5S) S54333-F15-A1 1.495

Accessories
FDCC221S| Communications interface| S24218-A201-A2| 0.019
FP120-Z1| Power supply kit A (70 W)| S54400-S122-A1| 3.920
FA2003-A1| Battery (12 V, 7 Ah, VdS)| A5Q00019353| 2.450
FA2004-A1| Battery (12 V, 12 Ah, VdS)| A5Q00019354| 3.930
FA2005-A1| Battery (12 V, 17 Ah, VdS)| A5Q00019677| 5.640
FDAZ292| ASD filter box| S54333-C92-A1| 0.220
Spare parts
FDAZ292-AA| ASD filter set| S54333-S91-A1| 0.009
FDAZ291| Aspirator (FDA241/FDA221)| S54333-G1-A1| 0.106

Product documentation

Document ID Title
A6V10334410 Technical manual Aspirating smoke detector FDA241, FDA221
A6V10393194 Technical manual Power supply kit A 70 W FP120-Z1
A6V10345654 Installation, Mounting Aspirating smoke detector FDA241, FDA221
A6V10340094 User Manual ‘ASD Asyst Tool FXS2055’
A6V10728226 User Manual ‘ASD Asyst Tool V2 FXS2056’
A6V10334435 Planning, Installation ASD Pipe system
A6V10332759 Installation, Operation Manual, Configuration ‘ASD Configuration

Tool FXS2051’
A6V10877841| Installation ASD Filterbox FDAZ292
A6V10916591| Installation Aspirator (FDA241/FDA221) FDAZ291

Related documents such as environmental declarations, CE declarations, etc., can be down- loaded at the following Internet address: http://siemens.com/bt/download

Notes

Disposal

The device is considered an electronic device for disposal in accordance with the European Guidelines and may not be disposed of as domestic garbage.

  • Dispose of the device through channels provided for this purpose.
  • Comply with all local and currently applicable laws and regulations.

Technical data

  FDA241 FDA221
Operating voltage DC 19.5…30 V
Operating current at DC 24 V 150 mA (nominal), 250 mA (during alarm)
Dimensions (W x H x D) 162 x 285 x 120 mm
Protection category IP30
Installation position Vertically upward, vertically downward
Sound power level LWA [dBA]: 1)

At suction speed

–  High

–  Medium

–  Low

| ****

37

33

30

| ****

33

30

26

Operating temperature| -20…+60 °C
Air humidity| 5…95 % (no moisture condensation)
Dust indicator| Yes| –
Maximum pipe length

–  Single line

–  Branched lines

| ****

60 m

2x 60 m

| ****

30 m

2x 25 m

Options for aspirating holes| Prefabricated option or the maximum pipe length must correspond to the calculation made using the software ‘FXS2056 ASD Asyst Tool V2’
Air intake/exhaust pipe| Metric: 25 mm outer diameter (OD)
Monitoring area (dependent on local provisions and standards)| Up to 800 m²| Up to 500 m²
System compatibility| Compatible with all Siemens FC20/FC720 (FS20/FS720 systems)
Relay alarm outputs

Can be selected with/without self- retention

Nominal current 2.0 A at DC 30 V. Contact: NO/NC

| 4| 3
Fault relay| 1| 1
Cable inlet| 10 cm x 2.5 cm on the rear or from above
Terminal configuration| Screw terminals
Conductor cross section| 0.2…2.5 mm2 (AWG 12– 30)
Other interfaces| Power supply, 4…20 mA
Alarm threshold for parameter sets:|  |
Fire 1| 10 sets

0.05…2.0 %/m obs

| 5 sets

0.20…2.0 %/m obs

Fire 2| 10 sets

2.0…20 %/m obs

| 5 sets

6.0…20 %/m obs

Alarm delay, can be set individually| 0…300 seconds: default value 0 seconds smoke density and 15 seconds flow
Indication| ●     4x alarm status indicators (FDA241)

●     3x alarm status indicators (FDA221)

●     Faults

●     Blowing out (FDA241)

●     Dust (FDA241)

●     Smoke density and flow indicator

  FDA241 FDA221
Service area ●     ‘Status OK’ LED

●     USB

●     Settings for reset functions

●     Settings for smoke density and airflow

Event log| Non-volatile event memory with time and date stamp for: smoke density, airflow, detector status, and faults
Event memory entries| 20000| 8000
Modification memory entries| 20000| 8000
Normalization of smoke value and airflow| ●     Setting of threshold values for smoke alarms and faults

●     User setting for normalization of smoke density and airflow

●     Preset values are retained during the normalization period

Warranty period| 2 years
Approvals

●     VdS

| FDA241

G213050

| FDA221

G213050

1 A-weighted sound power level in [dB] as per DIN EN ISO 3744-2009, measured with a pipe piece at the air inlet and at the air outlet

Dimensional drawings

SIEMENS FDA241 ASD Aspirating Smoke Detector-fig8

Issued by
Siemens Switzerland Ltd
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
+41 58 724 2424
www.siemens.com/buildingtechnologies

© Siemens Switzerland Ltd, 2013
Technical specifications and availability subject to change without notice.

firealarmresources.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals