SIEMENS MS-151 Manual Fire Alarm Stations Instruction Manual

June 9, 2024
SIEMENS

SIEMENS MS-151 Manual Fire Alarm Stations

INTRODUCTION

Model-151 from Siemens Industry, Inc., is a single-action, single-pole manual station; Model-157 is a single-action, double pole manual station. Both models operate with an internal toggle switch (See Figure 3).
When an alarm condition occurs, pull down on the cover of the manual station until the word ALARM appears. The interior toggle switch moves to ALARM at the same time.
When the manual station is reset, the toggle switch returns to NORMAL. See the instructions below for resetting the manual station.

INSTALLATION

  1. Distribute the manual station boxes throughout the protected area so that they are unobstructed, readily accessible, and located in the normal exit path.

  2. Place the manual station according to the regulations of the authorities having jurisdiction.

  3. For surface mounting, mount the backplate to a Model SB-15 Backbox as shown in Figure 3. For flush mounting, mount the backplate to a user supplied single gang switchbox.
    CAUTION: Do not overtighten the screws. Overtightening may distort the backplate.

  4. Wire the manual stations, referring to Figure 1 or Figure 2, as appropriate. Follow all regulations of the authorities having jurisdiction.SIEMENS-MS-151-Manual-Fire-Alarm-Stations-1

  5. Before installing the cover, check that the toggle switch is in the NORMAL position (See Figure 3).

  6. To position the cover, turn the reset screw up by turning the Allen key counterclockwise a quarter turn. The backplate then holds the cover in position.

  7. To indicate an alarm, pull down on the cover. (The word ALARM should be visible.)

  8. TO RESET THE MANUAL STATION: Turn the Allen key counterclockwise a quarter turn. The station resets automatically. (Do not hold the cover when the Allen key is turned.)

  9. If you have to remove the cover, turn the Allen key one quarter turn counterclockwise while pushing the cover up. Then pull the cover away from the backplate.SIEMENS-MS-151-Manual-Fire-Alarm-Stations-2

Contact Ratings
Main switch MS-151 and MS-157:

  • 125 VAC, 3A
  • 20-125 VDC, 3A
  • 250 VAC/VDC, 1 A

Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview Boulevard
Brampton, Ontario
L6T 5E4 Canada
firealarmresources.com