SIEMENS TSP-XC TSP-40A Cable Kit for FireFinder-XLS
INTRODUCTION
The Model TSP-XC Cable Kit from Siemens Industry, Inc., is used to wire TSP-
40A printers to FireFinder-XLS Systems. The two cables in the TSP-XC kit
replace the cables (P/Ns 600-290606 and 600-290607) that are shipped with the
TSP-40A. For additional information on the FireFinder-XLS System, refer to the
FireFinder-XLS Control Panel Installation, Operation and Maintenance Manual,
P/N 315-033744. For information on installing the TSP-40A in a FireFinder-XLS
System, refer to installation instructions, P/N 315-049949.
Installation of the TSP-40A in a FireFinder-XLS System requires the following
kits:
P/N 500-634933 TSP-40A Printer Module
P/N 500-849949 TSP-XB U-Shaped Bracket and Front Plate
P/N 500-849950 TSP-XC Cable Kit
WIRING
The TSP-40A printer modules comes with two cables, P/N 600-290607 and P/N 600-
290606. These cables are used only in MXL/MXLV System installations. The two
cables used in FireFinder-XLS Systems installations—a two-conductor power
cable and a data cable—are contained in the TSP-XC cable kit, P/N 500-849950.
The two-conductor power cable has a plug on one end that connects to P1 on the
TSP-40A. The power cable is provided at a length of 5 feet. Cut the wire to
the length needed and strip the insulation from the end of the wire 1/4” –
3/8”. The wired end connects to the terminals on TB-4 of the PSC-12 or PSX-12,
with the red wire going to the positive (+) terminal and the black wire going
to the negative (-) terminal. The data (ribbon) cable connects to P3 on the
TSP-40A and to either JP4 on the back of the PMI (note that the silk screen on
the PMI indicates NIM-1M) or to J13 on the back of the PMI-2 (note that the
silk screen on the PMI-2 indicates TSP-40A). Both ends of the data cable have
the same keyed plug that fits only one way onto the connectors.
Refer to Figure 1 for the location of the terminals on the TSP-40A, Figure 2
for the location of the connection to JP4 on the back of the PMI and Figure 3
for the location of the connection to J13 on the back on the PMI-2.
DIAGRAM
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
Siemens Canada Limited
Building Technologies Division
2 Kenview Boulevard
Brampton, Ontario L6T 5E4 Canada