SIEMENS OpenAir GVD-GKD Series Electronic Damper Actuator Instruction Manual

June 9, 2024
SIEMENS

SIEMENS OpenAir GVD-GKD Series Electronic Damper Actuator Instruction Manual
SIEMENS OpenAir GVD-GKD Series Electronic Damper
Actuator

Overview

Overview
Figure 1. GVD/GKD Actuator Parts

  • a. Actuator
  • b. Eyelet and 1/4-inch hex head screw

Product Description

Step-by-step description for direct-coupled mounting of the OpenAir GVD/GKD fast-acting, two-position, spring return, rotary electronic damper actuators. These actuators are intended for control of approved fire and smoke leakage- rated HVAC dampers.

Product Numbers

GKD121.1U: GVD121.1U
GKD126.1U: GVD126.1U
GKD221.1U: GVD221.1U
GKD226.1U: GVD226.1U
GKD321.1U: GVD321.1U
GKD326.1U: GVD326.1U

Warning/Caution Notations

WARNING:
Personal injury or loss of life may occur if you do not follow a procedure as specified.

CAUTION:
Equipment damage or loss of data may occur if you do not follow a procedure as specified.

Required Tools

  • 6 mm hex wrench
  • No. 2 Phillips screwdriver
  • Drill
  • 1/4-inch (6.4 mm) hex driver
  • 10 mm socket or box wrench

Prerequisites

WARNING:
Do not open the actuator housing.

CAUTION:
Continuous use at voltages above the recommended tolerances may damage the actuator.

Installation

Installation Instruction
Figure 2. Actuator Mounting Orientation.

Figure 3. Shaft Length and Proper Shaft Adapter Location.

Figure 4. Fasten the Shaft Adapter to the Damper Shaft.

CAUTION:

  • Use a 6 mm hex wrench to center the damper shaft by turning the socket head screw.
  • Use a 10 mm socket or box wrench to apply 97 in-lb to 115 in-lb (11 Nm to 13 Nm) of  torque to both coupling nuts to clamp the actuator to the shaft.

Installation Instruction
Figure 5.

  1. Insert eyelet up through housing ear.
  2. Insert screw through eyelet and tighten using 1/4-inch (6.4 mm) hex driver.

Installation Instruction

Figure 6. Tighten Conduit Screws
(No. 2 Phillips Screwdriver)

Wiring

NOTE: All wiring must conform to NEC and local codes and regulations.

24 Vac
Wiring

Function Color
Supply Red
Neutral Black
Ground Green/Yellow

**120 Vac

**

Function Color
Line Black
Neutral White
Ground Green/Yellow

**230 Vac

**

Function Color
Line Brown
Neutral Blue
Ground Green/Yellow

CAUTION:
These AC powered actuators must be wired with Line referenced with respect to Neutral, as indicated. The ground lead must be connected for proper protection of the actuator. Any other connection, such as phase-to-phase, can damage the actuator.

Fixed Dual End Switches.

NOTE:
Both sets of contacts are open when actuator is between 5° and 85°.

Switch Wire Color Switch Makes Switch Breaks
Gray < 5° > 5°
85° Yellow > 85° < 85°

CAUTION:
Mixed switch operation to the switching outputs of both fixed dual end switches (5° and 85°) is not permitted.

Either AC line voltage from the same phase must be applied to all four outputs of the fixed dual end switches, or UL-Class 2 voltage must be applied to all four outputs.

Electronic Fusible Link (EFL)

All GVD/GKD Electronic Damper Actuators are EFLcapable. EFLs are purchased separately. See Table 1.

Table 1. Electronic Fusible Link Product Numbers.

Part Number Operation
ASK791.165 165°F (74°C)
ASK791.212 212°F (100°C)
ASK791.250 250°F (121°C)
ASK791.350 350°F (177°C)

NOTE:
All EFLs are low voltage and do not need to be wired in conduit.

To install an EFL, do the following:

  1. Remove and discard the cover marked EFL.To install an EFL

  2. Use a small, needle-nose pliers to squeeze the release lock of the jumper plug and remove the jumper plug.
    NOTE: Remove the entire jumper plug, including the wire loop.
    To install an EFL

  3. Insert the quick connect plug from the EFL and ensure that the cable is secure.
    To install an EFL
    NOTE:
    If you are not using an EFL, do not modify the actuator. An EFL or jumper plug must be installed for actuator to work properly.

Maintenance

CAUTION:
The GVD/GKD actuators do not require any periodic cycling to function properly as an integral part of an active smoke control damper system. The National Fire Alarm Code NFPA 72 states that all life safety systems are to be functionally checked at least annually. Check the smoke control damper/actuator every time you functionally check your smoke detectors, emergency lights, and/or power generators for operation.

Dimensions

Dimensions
Figure 7. Dimensions of the GVD/GKD OpenAir Actuators in Inches (mm).

References

Technical Instructions A6V11959744
OpenAir® GVD/GKD Series Electronic Damper Actuator UL Listed Fire/Smoke and Smoke Control
Dampers

Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. OpenAir is a registered trademark of Siemens Schweiz AG. Product or company names mentioned herein may be the trademarks of their respective owners. © 2020-2022 Siemens Industry, Inc.


Siemens Industry, Inc.

Smart Infrastructure
1000 Deerfield Parkway
Buffalo Grove, IL 60089
+ 1 847-215-1000

Your feedback is important to us. If you have comments about this document, please send them to [email protected]

Document No. A5W00094027
Printed in the USA

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

SIEMENS User Manuals

Related Manuals