SIEMENS OpenAir GVD-GKD Series Electronic Damper Actuator Instruction Manual
- June 9, 2024
- SIEMENS
Table of Contents
SIEMENS OpenAir GVD-GKD Series Electronic Damper Actuator Instruction
Manual
Overview
Figure 1. GVD/GKD Actuator Parts
- a. Actuator
- b. Eyelet and 1/4-inch hex head screw
Product Description
Step-by-step description for direct-coupled mounting of the OpenAir GVD/GKD fast-acting, two-position, spring return, rotary electronic damper actuators. These actuators are intended for control of approved fire and smoke leakage- rated HVAC dampers.
Product Numbers
GKD121.1U: GVD121.1U
GKD126.1U: GVD126.1U
GKD221.1U: GVD221.1U
GKD226.1U: GVD226.1U
GKD321.1U: GVD321.1U
GKD326.1U: GVD326.1U
Warning/Caution Notations
WARNING:
Personal injury or loss of life may occur if you do not follow a procedure
as specified.
CAUTION:
Equipment damage or loss of data may occur if you do not follow a procedure
as specified.
Required Tools
- 6 mm hex wrench
- No. 2 Phillips screwdriver
- Drill
- 1/4-inch (6.4 mm) hex driver
- 10 mm socket or box wrench
Prerequisites
WARNING:
Do not open the actuator housing.
CAUTION:
Continuous use at voltages above the recommended tolerances may damage the
actuator.
Installation
Figure 2. Actuator Mounting Orientation.
Figure 3. Shaft Length and Proper Shaft Adapter Location.
Figure 4. Fasten the Shaft Adapter to the Damper Shaft.
CAUTION:
- Use a 6 mm hex wrench to center the damper shaft by turning the socket head screw.
- Use a 10 mm socket or box wrench to apply 97 in-lb to 115 in-lb (11 Nm to 13 Nm) of torque to both coupling nuts to clamp the actuator to the shaft.
Figure 5.
- Insert eyelet up through housing ear.
- Insert screw through eyelet and tighten using 1/4-inch (6.4 mm) hex driver.
Figure 6. Tighten Conduit Screws
(No. 2 Phillips Screwdriver)
Wiring
NOTE: All wiring must conform to NEC and local codes and regulations.
24 Vac
Function | Color |
---|---|
Supply | Red |
Neutral | Black |
Ground | Green/Yellow |
**120 Vac
**
Function | Color |
---|---|
Line | Black |
Neutral | White |
Ground | Green/Yellow |
**230 Vac
**
Function | Color |
---|---|
Line | Brown |
Neutral | Blue |
Ground | Green/Yellow |
CAUTION:
These AC powered actuators must be wired with Line referenced with respect to
Neutral, as indicated. The ground lead must be connected for proper protection
of the actuator. Any other connection, such as phase-to-phase, can damage the
actuator.
Fixed Dual End Switches.
NOTE:
Both sets of contacts are open when actuator is between 5° and 85°.
Switch | Wire Color | Switch Makes | Switch Breaks |
---|---|---|---|
5° | Gray | < 5° | > 5° |
85° | Yellow | > 85° | < 85° |
CAUTION:
Mixed switch operation to the switching outputs of both fixed dual end
switches (5° and 85°) is not permitted.
Either AC line voltage from the same phase must be applied to all four outputs of the fixed dual end switches, or UL-Class 2 voltage must be applied to all four outputs.
Electronic Fusible Link (EFL)
All GVD/GKD Electronic Damper Actuators are EFLcapable. EFLs are purchased separately. See Table 1.
Table 1. Electronic Fusible Link Product Numbers.
Part Number | Operation |
---|---|
ASK791.165 | 165°F (74°C) |
ASK791.212 | 212°F (100°C) |
ASK791.250 | 250°F (121°C) |
ASK791.350 | 350°F (177°C) |
NOTE:
All EFLs are low voltage and do not need to be wired in conduit.
To install an EFL, do the following:
-
Remove and discard the cover marked EFL.
-
Use a small, needle-nose pliers to squeeze the release lock of the jumper plug and remove the jumper plug.
NOTE: Remove the entire jumper plug, including the wire loop.
-
Insert the quick connect plug from the EFL and ensure that the cable is secure.
NOTE:
If you are not using an EFL, do not modify the actuator. An EFL or jumper plug must be installed for actuator to work properly.
Maintenance
CAUTION:
The GVD/GKD actuators do not require any periodic cycling to function properly
as an integral part of an active smoke control damper system. The National
Fire Alarm Code NFPA 72 states that all life safety systems are to be
functionally checked at least annually. Check the smoke control
damper/actuator every time you functionally check your smoke detectors,
emergency lights, and/or power generators for operation.
Dimensions
Figure 7. Dimensions of the GVD/GKD OpenAir Actuators in Inches (mm).
References
Technical Instructions A6V11959744
OpenAir® GVD/GKD Series Electronic Damper Actuator UL Listed Fire/Smoke and
Smoke Control
Dampers
Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. OpenAir is a registered trademark of Siemens Schweiz AG. Product or company names mentioned herein may be the trademarks of their respective owners. © 2020-2022 Siemens Industry, Inc.
Siemens Industry, Inc.
Smart Infrastructure
1000 Deerfield Parkway
Buffalo Grove, IL 60089
+ 1 847-215-1000
Your feedback is important to us. If you have comments about this document, please send them to sbt_technical.editor.us.sbt@sbt.siemens.com
Document No. A5W00094027
Printed in the USA