Please take the time to read this installation guide. The guide contains
important information and notes regarding the installation and operation.
IMPORTANT!
- Always switch off the power supply before commencing work!
- Only to apply in dry indoor usage and environments, outdoor applications requires an IP rated fixture.
- Philips LEDtube is designed to fit in standard IEC compliant GI 3 bi-pin lampholders.
- Philips LEDtube should be installed by qualified professionals in accordance with relevant electrical codes.
DISCLAIMER:
Signify disclaims liability for any direct, indirect or incidental damages in
case of installation performed either not according to this guide or not
performed by a professional electrician.
- “This lamp is not suitable to be used in emergency luminaires designed for double-capped fluorescent lamp(s)
Does your luminaire have a starter?
This illustration shows its typical location in an open or closed luminaire
with the length of 1200 and 1500 mm tubes. Yes, the luminaire does have a
starter.
The luminaire works on ElectromMagnetic ballast. Go to the Electromagnetic
ballast section 2.1 Instructions on Electromagnetic ballast
No, the luminaire does not have a starter.
The luminaire works on High Frequency electronic ballast (HF). You need first
to check if the the HF ballast is compatible. To check if your ballast is
compatible, always refer to the latest update of the Philips LEDtube
compatibibility list on
www.philips.com/ledtube
- Yes, the ballast is compatible. Go to section 2.2 Instructions on HF compatible ballast
- No, the ballast is not compatible. Go to section 2.3 Instructions for non compatible HF ballast
Instructions on Electormagnetic ballast
Simply replace the old starter with the new (EM) LED starter included in
the packaging and follow the instructions below Instructions on HF
compatiblr ballast
It’s a plug and play solution that works straight out of the box. No need
to change drivers or rewire. Quick and easy installation, follow the
instructions below Instructions for non compatible HF ballast
Your luminaire works on High Frequency (HF) ballast, but the ballast is not
compatible.
Cut wires, remove the ballast and connect direct to mains. Follow the
instructions below
- In this application, LED replacement starter is not used.
- Always switch off the power supply before commencing work!
- Philips LED tube should be installed by qualified professionals in accordance with relevant code.
Make sure to connect ln on the lamp side with ln mark otherwise, lamp may damage
SYMBOL | MEANING | APPLICATION |
---|---|---|
DO NOT USE WITH DIMMERS | EM and MAINS | |
LAMP SUITABLE FOR 50Hz OR 60 Hz OPERATION | EM and MAINS | |
NEED TO BE USED WITH LED REPLACEMENT STARTER EMP | EM only | |
NEED TO BE USED IN DRY CONDITIONS OR IN A LUMINAIRE THAT PROVIDES | ||
PROTECTION | ALL | |
LAMP SUITABLE FOR HIGH FREQUENCY OPERATION | HF only | |
LAMP NOT SUITABLE FOR EMERGENCY OPERATION | ALL |
- This lamp may not be suitable for use in all applications where a traditional fluorescent lamp has been used. The temperature range of this lamp is more restricted. In cases of doubt regarding the suitability of the application the manufacturer of this lamp should be consulted
- This lamp is designed for general lighting service (excluding e.g. explosive atmospheres)
© 2019 Signify Holding
ignify
All rights reserved. Reproduction in whole or in part is prohibited without
the prior written consent of the copyright owner.
The information presented in this document does not form part of any quotation
or contract, is believed to be accurate and reliable and may be changed
without notice.
No liability will be accepted by the publisher for any consequence of its use.
Publication thereof does not convey nor imply any license under patent or
other industrial or intellectual property rights.
www.phillips.com/lighting
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>