Honeywell Y8196A Heating Cooling New Construction Thermostat Subbas Instruction Manual
- June 9, 2024
- Honeywell
Table of Contents
Y8196A (T8196A Thermostat/
Q682A Subbase) Heating/Cooling New
Construction Thermostat/Subbase
Package—Installation Instructions
Instruction Manual
Preparation
Check thermostat and subbase suitability for the heat-ing, cooling, or
heating/cooling system. Refer to Table 1. Assemble tools required: flat bladed
screwdriver, hand or power drill with 3/16-in. drill bit, wire cutter/stripper
or sharp knife, bubble level or plumb bob and line.
Assure power is off to the heating, cooling, or heating/cooling system at the
main fuse panel. Most buildings have a separate switch box or circuit breaker
for disconnecting power to the heating and cooling (if applicable) equipment.
This thermostat is compatible with virtually all heating, cooling or
heating/cooling systems. Refer to Table 1 for additional thermostat
compatibility information.
TABLE 1—THERMOSTAT AND SYSTEM COMPATIBILITY.
Type of Heating System to be Controlled | Conditions/Compatibility |
---|
Electric (Line Voltage)—typical baseboard and
radiant| • The R8239D1015 Isolating Relay or R841 Silent Switching Center must
be installed in the thermostat control circuit.a
Heat Pump| • Compatible. Assure correct subbase identity is selected for fan
control and changeover control (O terminal for cool and B terminal for heat).
Jumper Y to W for heat pump compressor control.
Hot Water Zone| • Honeywell 2-wire valves are compatible.
• Some non-Honeywell 2-wire valves require an R8239D1015 Isolating Relay in
the thermostat control circuit.a
• Some 3-wire valves require an R8239A1052 Isolating Relay in the thermostat
control circuit.a, b
Oil| • Compatible.
Vent Damper| • Honeywell damper motors are compatible.
• Some non-Honeywell damper motors require an R8239D1015 Isolating Relay in
the thermostat control circuit.a Check control amperage requirement.
Warm Air Zone| • Most are compatible.
a If thermostat is not compatible with the system being controlled, the system
will not operate. No hazard exists. The thermostat will not be damaged unless
it is used to directly control a line voltage system. A Honeywell R841 or
R8239D1015 Isolating Relay must be added to the thermostat control circuit for
proper system operation.
b Consult manufacturer for installation requirements.
Recycling Notice
This control contains mercury in a sealed tube. Do not place control in the
trash at the end of its useful life.
If this control is replacing a control that contains mercury in a sealed tube,
do not place your old control in the trash.
Contact your local waste management authority for instructions regarding
recycling and the proper disposal of this control, or of an old control
containing mercury in a sealed tube.
Installation
WHEN INSTALLING THIS PRODUCT…
- Read these instructions carefully. Failure to follow them could cause a hazardous condition.
- Installer must be a trained experienced service technician.
- After installation is complete, check out product operation as provided in these instructions.
IMPORTANT: An incorrectly leveled subbase will cause the temperature control to deviate from setpoint. It is not a calibration problem.
CAUTION
- Disconnect power supply to prevent electrical shock or equipment damage.
- To prevent interference with the thermostat linkage, keep wire length to a minimum and run wires as close as possible to the subbase.
- Do not overtighten thermostat captive mounting screws because damage to subbase threads can result.
- Do not short across coil terminals on relay.
This can burn out the thermostat heat anticipator.
LOCATION
Locate thermostat about 5 ft (1.5m) above the floor in an area with good air
circulation at average temperature. Do not mount the thermostat where it may
be affected by—
— drafts, or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from the sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall behind the thermostat.
Run wires from the heating, cooling, or heating/cooling equipment to the new
thermostat location.
UNPACK THERMOSTAT
Handle your new thermostat carefully; rough handling may interfere with its
accuracy. Before unpacking, refer to Fig. 1.
Remove and discard the shipping wrap.
IMPORTANT: Save package of screws and instructions for the homeowner.
Remove the thermostat cover by lifting from the bottom.
Set aside cover until needed later.
Carefully remove the material protecting the mercury switch bulb.
Loosen two captive mounting screws.
Fig. 1—Unpack thermostat.
MOUNT SUBBASE
Wall Mounting (Fig. 2)
Hold the subbase in position on wall (Fig. 2).
Mark holes on the wall for anchors. Use spirit level to make sure the
wallplate or subbase is level.
Drill 3/16-in. holes, and gently tap anchors into holes until flush with the
wall.
Pull wires through the large wiring hole in the subbase.
Loosely fasten the subbase to the wall with the three
screws. Do not completely tighten the screws.
Carefully level the subbase (Fig. 3), and firmly tighten the screws.
Fig. 2—Mounting subbase to wall.
Outlet Box Mounting (Fig. 4)
Use a horizontally mounted outlet box if possible. If a vertical outlet box is
used, the subbase must be mounted on a 202689A Cover Plate Assembly (ordered
separately).
Follow the instructions provided with the cover plate assembly.
Align the subbase mounting holes on the outlet box and loosely fasten with the
two screws.
Carefully level the subbase (Fig. 3) and firmly tighten the screws.
Fig. 3—Leveling methods for subbase.
Fig. 4—Mounting subbase on outlet box.
WIRE SUBBASE
Follow the instructions provided by the heating, cool-ing, or heating/cooling
equipment manufacturer. If not available, refer to the Typical Wiring Diagrams
section at the end of this publication.
Disconnect the power supply before making wiring connections to prevent
electrical shock or equipment damage.
NOTE: All wiring must comply with local electrical codes and ordinances.
Refer to Fig. 5 and strip thermostat wire insulation as necessary.
Fig. 5—Methods of connecting terminals.
Connect the wires to corresponding terminals on the subbase.
If labels do not agree with your new subbase, refer to Table 2 or Fig. 11.
TABLE 2—TERMINAL DESIGNATIONS.
Subbase Terminal | Control Function |
---|---|
R | Control transformer power. |
W | Heating control circuit. |
Y | Cooling control circuit (jumper to W for |
heat pump compressor control).
G| Fan control circuit.
0| Cooling damper or changeover/reversing
valve, makes continuously in cool.
B| Heating damper or changeover/reversing
valve, makes continuously in heat.
Push excess wire back into the wall.
Plug the hole in the wall with nonhardening caulk, putty, or nonflammable
insulation to prevent drafts from affecting thermostat operation.
MOUNT THE THERMOSTAT
Note the tabs on the top inside edge of the thermostat base. These tabs fit
the slots molded into the top of the subbase.
Hang thermostat base on subbase.
Insert the two captive mounting screws located in the bottom corners of the
base (Fig. 6).
Firmly tighten the screws.
Fig. 6—Thermostat mounting.
INSERT TIMER BATTERIES
Power is supplied to the timer by two AAA alkaline batteries (not included).
Install the batteries in the thermostat (Fig. 7).
Once a year or when batteries are dead, replace with two new AAA alkaline
batteries. We recommend Energizer® batteries.
Fig. 7—Insert timer batteries.
SET TIMER
Adjust the timer by moving the knob clockwise .
Do NOT reverse the knob.
When time is correctly set, the time indicator arrow (Fig. 8) must point to
the corresponding daytime (light) or nighttime (dark) portion of the program
dial.
Fig. 8—Set timer.
ATTACH THERMOSTAT COVER
Make sure the packing inserts in the thermostat base are removed.
Place the two tabs on the upper edge of the cover into the mounting slots in
the thermostat base (Fig. 9).
Swing the cover downward until it catches at the bottom of the base.
Fig. 9—Attach cover.
SET TEMPERATURE CONTROL LEVERS
The two levers on top of thermostat control the low and high temperatures for
energy savings and comfort control (Fig. 10). The lever on the left (blue
mark) controls the lower temperature. The lever on the right (red mark)
controls the higher temperature.
We recommend pushing the levers together at an appropriate temperature for
either heat or cool until the occupant programs the thermostat and makes the
final temperature selections.
Fig. 10—Temperature control levers.
SET SUBBASE SWITCHES
The subbase system switch controls system operation as follows:
HEAT: Heating system is controlled by the thermostat.
Cooling system is off.
COOL: Cooling system is controlled by the thermostat.
Heating system is off.
OFF: Both the heating and cooling systems are off. If the fan switch is in the
AUTO position, the fan is also off.
The subbase fan switch controls fan operation as follows:
ON: Fan operates continuously.
AUTO: Fan operates with the cooling equipment as controlled by the thermostat
or with the heating equipment as controlled by the plenum switch. In electric
heat, heat pump and fan coil systems, the fan is controlled by the thermostat
in heating and cooling.
To switch positions, use thumb or index finger to slide lever to the desired
position. Switch lever must stop in detent over the desired function indicator
mark for proper circuit operation.
CHECK OUT THERMOSTAT OPERATION
CAUTION
Do NOT check operation by shorting across terminals of relay or valve coil;
this will burn out the thermostat heat anticipator.
HEATING/COOLING SYSTEM
Turn on power to the furnace and cooling system.
Place the system switch lever to HEAT and fan switch lever to AUTO.
Push both temperature setting levers together at least 5°F (3°C) above room
temperature. The main burner should come on. The fan will start when the
furnace heats up. (If central electric heat or heat pump system, fan starts
immediately.)
Move both levers 5°F (3°C) below room temperature.
The burner should shut off.
Place the system switch lever at COOL and the fan switch lever at AUTO. The
cooling equipment should operate, and the fan will start. Allow for any time
delay that may be built into the compressor control circuit.
NOTE: To avoid compressor damage, do not operate the system if outdoor
temperature is below 50°F (10°C).
Refer to manufacturer recommendations.
Move both temperature setting levers together at least 5°F (3°C) above room
temperature. The cooling equipment should shut off.
Place the fan switch to ON. The fan should run continuously with the system
switch in any position.
Place the system switch to OFF. Move both temperature setting levers to
various positions. The heating and cooling systems should not operate.
Operate the entire system for at least one complete cycle with the system
switch at COOL and one complete cycle with the switch at HEAT.
If thermostat fails any test, refer to the Troubleshooting Guide in the
Owner’s Manual.
Reset both temperature setting levers to the desired temperatures.
Leave Owner’s Manual and Assistance Information in a convenient place for the
building occupant or provide with other appliance manuals.
TYPICAL WIRING DIAGRAMS
For wiring, follow the hookup diagram supplied with your heating, cooling or
heating/cooling equipment. If not available, use Fig. 11 as a guide.
REMEMBER: Your wiring must follow local electrical codes and ordinances.
Fig. 11—Typical hookup for Y8196A Package (T8196A Thermostat/Q682A Subbase) in heating/cooling system.
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Honeywell Limited—Honeywell Limitée
35 Dynamic Drive
Scarborough, Ontario M1V 4Z9
Printed in U.S.A. on recycled paper containing at least 10% post-consumer
paper fibers.
D. F. • Rev. 12-94 • ©Honeywell Inc. 1994
• Form Number 69-0637—2
firealarmresources.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>