Honeywell T8190A Heating or Cooling Thermostat Installation Guide
- June 9, 2024
- Honeywell
Table of Contents
- Preparation
- Recycling Notice
- Installation
- WHEN INSTALLING THIS PRODUCT…
- LOCATION
- UNPACK THERMOSTAT
- MOUNT WALLPLATE OR SUBBASE Wall Mounting (Fig. 2)
- Outlet Box Mounting (Fig. 4)
- WIRE WALLPLATE OR SUBBASE
- Subbase (Heating/Cooling Systems)
- MOUNT THE THERMOSTAT
- INSERT TIMER BATTERIES
- SET TIMER
- SET HEAT ANTICIPATOR
- ATTACH THERMOSTAT COVER
- SET TEMPERATURE CONTROL LEVERS
- SET SUBBASE SWITCHES (IF APPLICABLE)
- Checkout
- Calibration
- Typical Wiring Diagrams
- CUSTOMER SUPPORT
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Honeywell T8190A Heating or Cooling Thermostat
Preparation
Check thermostat and subbase (if used) suitability for the heating, cooling,
or heating/cooling system. Refer to Table 1.
Assemble tools required: flat-bladed screwdriver, hand or power drill with
3/16-in. drill bit, wire cutter/stripper or sharp knife, bubble level or plumb
bob and line.
Assure power is off to the heating, cooling, or heating/ cooling system at the
main fuse panel. Most buildings have a separate switch box or circuit breaker
for disconnecting power to the heating and cooling (if applicable) equipment.
This thermostat is compatible with all heating, cooling or heating/cooling
systems when thermostat is powered by batteries. If thermostat is not powered
by batteries, refer to Table 1 for thermostat and system compatibility
information.
NOTE: Order Q682B Subbase separately.
Recycling Notice
This control contains mercury in a sealed tube. Do not place control in the
trash at the end of its useful life.
If this control is replacing a control that contains mercury in a sealed tube,
do not place your old control in the trash.
Contact your local waste management authority for instructions regarding
recycling and the proper disposal of this control, or of an old control
containing mercury in a sealed tube.
If you have questions, call Honeywell Inc. at 1-800- 468-1502.
TABLE 1—SYSTEM COMPATIBILITY FOR NON-BATTERY POWERED THERMOSTATS.
Type of Heating System to be Controlled | Conditions/Compatibility |
---|---|
Electric (Line Voltage)—typical baseboard and radiant |
- The R8239D1015 Isolating Relay or R841 Silent Switching Center must be installed in the thermostat control circuit. a
Fan Coil Unit|
- Compatible. Assure correct subbase identity is selected for fan control.
Gas—Direct Spark Ignition (DSI), Intermittent Pilot (IP), and Standing Pilot (SP)|
- Compatible. If not using battery backup, assure that 24V control transformer common is accessible for connection to thermostat cable conductor and power to the transformer is not regularly interrupted by high temperature or limit operation.
Heat Pump|
- Compatible. Assure correct subbase identity is selected for fan control and changeover control (O terminal for cool and B terminal for heat).
Hot Water Zone|
- Honeywell 2-wire valves are compatible.
- Some non-Honeywell 2-wire valves require an R8239D1015 Isolating Relay in the thermostat control circuit. a
- Some 3-wire valves require an R8239A1052 Isolating Relay in the thermostat control circuit. a, b
Oil|
- If not using battery backup, assure that the 24V control transformer common is accessible for connection to thermostat cable conductor and power to the transformer is not regularly interrupted by high temperature, purge cycle, or limit operation.
Vent Damper|
- Honeywell damper motors are compatible.
- Some non-Honeywell damper motors require an R8239D1015 Isolating Relay in the thermostat control circuit. a Check control amperage requirement.
Warm Air Zone|
- Most are compatible.
Installation
WHEN INSTALLING THIS PRODUCT…
- Read these instructions carefully. Failure to follow them could cause a hazardous condition.
- Installer must be a trained experienced service technician.
- After installation is complete, check out product operation as provided in these instructions.
IMPORTANT: An incorrectly leveled subbase will cause the temperature control to deviate from setpoint. It is not a calibration problem.
CAUTION
- Disconnect power supply to prevent electrical shock or equipment damage.
- To prevent interference with the thermostat linkage, keep wire length to a minimum and run wires as close as possible to the subbase.
- Do not overtighten thermostat captive mounting screws because damage to subbase threads can result.
- Do not short across coil terminals on relay. This can burn out the thermostat heat anticipator.
LOCATION
Locate thermostat about 5 ft [1.5m] above the floor in an area with good air
circulation at average temperature.
Do not mount the thermostat where it may be affected by:
— drafts, or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from the sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall behind the thermostat.
Run wires from the heating, cooling or heating/cooling equipment to the new
thermostat location.
Refer to the Typical Wiring Diagrams section to determine the number of wires
required for your application.
UNPACK THERMOSTAT
Handle your new thermostat carefully; rough handling may interfere with its accuracy. Before unpacking, refer to Fig. 1.
Remove and discard the shipping wrap.
IMPORTANT: Save package of screws and instructions for the homeowner.
Remove the thermostat cover by lifting from the bottom.
Set aside cover until needed later.
Carefully remove the material protecting the mercury switch bulb.
Loosen two captive mounting screws and separate wall plate (if provided) from
back of thermostat base.
MOUNT WALLPLATE OR SUBBASE Wall Mounting (Fig. 2)
Hold the wall plate or subbase in position on wall (Fig. 2).
Mark holes on the wall for anchors. Use spirit level to make sure the wall
plate or subbase is level.
Drill 3/16-in. holes, and gently tap anchors into holes until flush with the
wall.
Pull wires through the large wiring hole in the wall plate or subbase.
Loosely fasten the wall plate or subbase to the wall with the three screws. Do
not completely tighten the screws.
Carefully level the wall plate or subbase (Fig. 3), and firmly tighten the
screws.
Outlet Box Mounting (Fig. 4)
Use a horizontally mounted outlet box if possible. If a vertical outlet box is
used, mount the wall plate or subbase on a 193121A (beige) Cover Plate
Assembly (ordered separately). Follow the instructions provided with the cover
plate assembly.
Align the wall plate or subbase mounting holes on the outlet box and loosely
fasten with two screws.
Carefully level the wall plate or subbase (Fig. 3), and firmly tighten the
screws.
WIRE WALLPLATE OR SUBBASE
Follow the instructions provided by the heating, cooling, or heating/cooling
equipment manufacturer. If not available, refer to the Typical Wiring Diagrams
section at the end of this publication.
Disconnect the power supply before making wiring connections to prevent
electrical shock or equipment damage.
NOTE: All wiring must comply with local electrical codes and ordinances.
This thermostat clock can be powered by a 24 Vic transformer with battery
backup. Refer to Figs. 15 through 19 for hookup diagrams of typical powering
applications.
For Wall plate (Heating or Cooling Systems)
Refer to Fig. 5 and strip the thermostat wire insulation as necessary.
For heating-only systems, connect wires to R, W, and C (if applicable)
terminals (Fig. 20). For cooling-only systems, connect wires R, Y, and C (if
applicable) terminals. Firmly tighten the screws.
Push excess wire back into the wall.
Plug the hole in the wall with nonhardening caulk, putty, or nonflammable
insulation to prevent drafts from affecting thermostat operation.
Subbase (Heating/Cooling Systems)
Refer to Fig. 5 and strip the thermostat wire insulation as necessary.
Connect the wires to the corresponding terminals on the subbase. If labels do
not agree with your new subbase, refer to Table 2 and the installation
instructions furnished with the subbase.
NOTE: If wiring a dual transformer system, only the O or the B terminal
may be used. Push excess wire back into the wall.
Plug the hole in wall with nonhardening caulk, putty, or nonflammable insulation to prevent drafts from affecting the thermostat operation.
TABLE 2—SUBBASE TERMINAL DESIGNATIONS.
Subbase Terminal | Control Function |
---|---|
R | Control transformer power. |
R c | Line side of 24V power supply; cooling side, 2 transformer heat/cool |
system.
Rh| Line side of 24V power supply; heating side, 2 transformer heat/cool
system.
W| Heating control circuit.
Y| Cooling control circuit; jumper to W for heat pump compressor control if no
P terminal on subbase.
G| Fan control circuit.
C| Clock control (transformer common).
O| Cooling damper or changeover/reversing valve, makes continuously in cool.
B| Heating damper or changeover/reversing valve, makes continuously in heat.
P| Heat pump contactor; P terminal on some models only.
MOUNT THE THERMOSTAT
Note the tabs on the top inside edge of the thermostat base. These tabs
fit the slots molded into the top of the wall plate or subbase.
Hang the thermostat base on the wall plate or subbase. Insert the two captive
mounting screws located in the bottom corners of the base (Fig. 6). Firmly
tighten the screws.
INSERT TIMER BATTERIES
Power is supplied to the clock by the 24 Vac transformer or two AAA alkaline batteries (included), or by the heating or cooling control circuit. Backup batteries may be installed to supply power to the clock if power is interrupted when using 24 Vac powering method. Install the batteries in the thermostat (Fig. 7).
Once a year or when batteries are dead, replace with two new AAA alkaline
batteries. Properly dispose of old batteries. We recommend Energizer®
batteries.
SET TIMER
Adjust the timer by moving the knob clockwise . Do not reverse the knob .
When time is correctly set, the time indicator arrow (triangle shape) points
to the correct time and the corresponding daytime (light) or nighttime (dark)
portion of the program dial (Fig. 8).
SET HEAT ANTICIPATOR
Adjust the heat anticipator lever to match the current rating of the primary control for the proper cycle rate (Fig. 9).
Adjustable anticipation must be set for total current of heat and fan control.
The current rating is usually stamped on the control or valve (Fig. 10), or a
setting may be given in the device instructions.
If no current rating or heat anticipator setting is given, measure the current
with an ammeter. Proceed with the following steps.
Remove the thermostat from the wall plate or subbase. Connect an ac ammeter of
appropriate range (about 0A to 2A) between the R and W terminals on the wall
plate or subbase, except for electric heat and heat pump systems.
Let the system operate for one minute. Adjust the heat anticipator lever to
match the number that reads on the ammeter.
ATTACH THERMOSTAT COVER
Make sure the packing inserts in the thermostat base are removed.
Place the two tabs on the upper edge of the cover into the mounting slots in
the thermostat base (Fig. 11). Swing the cover downward until it catches at
the bottom of the base.
SET TEMPERATURE CONTROL LEVERS
The two levers on the top of the thermostat control the low and high temperatures for energy savings and comfort control (Fig. 12). The lever on the left (blue mark) controls the lower temperature. The lever on the right (red mark) controls the higher temperature.
We recommend pushing the levers together at an appropriate temperature for
either heat or cool until the occupant programs the thermostat and makes the
final temperature selections.
SET SUBBASE SWITCHES (IF APPLICABLE)
The subbase system switch controls system operation as follows:
HEAT: Heating system is controlled by the thermostat. Cooling system is
off.
COOL: Cooling system is controlled by the thermostat. Heating system is
off.
OFF: Both the heating and cooling systems are off. If the fan switch is
in the AUTO position, the fan is also off. The subbase fan switch controls fan
operation as follows:
ON: Fan operates continuously.
AUTO: Fan operates with the cooling equipment as controlled by the
thermostat or with the heating equipment as controlled by the plenum switch.
In electric heat, heat pump, and fan coil systems, the fan is controlled by
the thermostat in heating and cooling
To switch positions, use thumb or index finger to slide lever to the desired position. Switch lever must stop in detent over the desired function indicator mark for proper circuit operation.
Checkout
CAUTION Do not check operation by shorting across the terminals of the system controls. This will damage the heat anticipator.
HEATING-ONLY SYSTEM
Turn on power to the furnace. Push both temperature setting levers together at
least 5° F [3° C] above the room temperature. The main burner should come on.
The fan will start when the furnace heats up. Move both levers 5° F [3° C]
below the room temperature. The burner should shut off.
Operate the entire heating system at least one complete cycle.
If thermostat fails any test, refer to the Troubleshooting Guide in the
Owner’s Manual.
Reset both temperature setting levers to the desired temperatures.
COOLING-ONLY SYSTEM
Turn on power to the cooling equipment. Push both temperature setting levers
together at least 5° F [3° C] below the room temperature. The cooling
equipment will operate, and the fan will start. Allow for any time delay that
may be built into the compressor control circuit.
NOTE: To avoid compressor damage, do not operate the system when outdoor
temperature is below 50° F [10° C].
Refer to manufacturer recommendations.
Move both levers 5° F [3° C] above room temperature.
The cooling equipment and the fan should shut off.
Operate the entire cooling system at least one complete cycle.
If thermostat fails any test, refer to the Troubleshooting Guide in the
Owner’s Manual.
Reset both temperature setting levers to the desired temperatures.
HEATING/COOLING SYSTEM
Turn on power to the furnace and cooling system. Place the system switch lever
to HEAT and fan switch lever to AUTO.
Push both temperature setting levers together at least 5° F [3° C] above room
temperature. The main burner should come on. The fan will start when the
furnace heats up. (If central electric heat, fan coil or heat pump system, fan
starts immediately.)
Move both levers 5° F [3° C] below room temperature. The burner should shut
off.
Place the system switch lever to COOL and the fan switch lever to AUTO. The
cooling equipment will operate, and the fan will start. Allow for any time
delay that may be built into the compressor control circuit.
NOTE: To avoid compressor damage, do not operate the system when outdoor
temperature is below 50° F [10° C]. Refer to manufacturer recommendations.
Move both temperature setting levers together at least 5° F [3° C] above the
room temperature. The cooling equipment should shut off.
Place the fan switch to ON. The fan should run continuously with the system
switch in any position.
Place the system switch to OFF. Move both temperature setting levers to
various positions. The heating and cooling systems should not operate.
Operate the entire system for at least one complete cycle with the system
switch at COOL and one complete cycle with the switch at HEAT.
If thermostat fails any test, refer to the Troubleshooting Guide in the
Owner’s Manual.
Reset both temperature setting levers to the desired temperatures.
Leave Owner’s Manual and Assistance Information in a convenient place for the
building occupant or provide with other appliance manuals.
Calibration
THERMOMETER
The thermometer in your thermostat was accurately calibrated at the factory. The thermometer should need adjustment only if it has been dropped or shifted due to mishandling. If the setpoint lever and the thermometer reading do not agree:
-
Remove the thermostat cover by pulling up from the bottom of cover until it clears the mounting slots.
-
Set the thermostat cover on a table near an accurate thermometer.
-
Allow five minutes for cover thermometer to sense area temperature; compare the readings. Be careful not to ouch thermometer or breathe on it.
-
If the readings are the same, replace cover and put the system into operation.
-
If the readings are different, insert a small screwdriver in the thermometer and turn it until the thermometers have the same reading (Fig. 13).
-
Replace thermostat cover and put the system into operation.
THERMOSTAT
This thermostat was calibrated at the factory and should not need
recalibration in the field. If recalibration seems necessary, first be sure
wall plate or subbase is accurately leveled. Then check thermometer
calibration.
To check thermostat calibration, allow several hours of operation after
installation. Then read thermometer and remove cover. Push temperature levers
together to a setting below room temperature. Slowly move them up the scale
together until the mercury slides across the tube. If the thermometer reading
and the high temperature lever position are approximately the same at the
instant the mercury moves to the other end, no recalibration is needed.
If calibration is necessary, proceed as follows:
-
Remove the cover.
-
Place open-end calibration wrench, part no. 104994A (ordered separately), on the hex nut under the bimetallic coil controlled by the red lever (Fig. 14). Hold lever so it does not move, and gently turn the wrench clockwise until the mercury rests securely in the right end of the tube.
-
Put the thermostat cover on and wait ten minutes.
-
Read the thermometer. Then remove the cover. Moving both levers, place the HIGH lever at the thermometer reading. Hold lever so it does not move, and gently turn the wrench counterclockwise until the mercury just slides to the left end of the tube but no farther. Try to do this quickly so the heat from your hands does not affect the thermostat.
-
Repeat this procedure for the blue lever.
Typical Wiring Diagrams
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
BATTERY BACKUP MAY BE USED IF POWER TO TIMER IS INTERRUPTED.
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
JUMPER RH-RC TERMINALS WHEN ONE TRANSFORMER POWERS BOTH HEATING AND COOLING.
FOR POWER STEALING ON HEATING, JUMPER C-RH AND C-W TERMINALS.
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
JUMPER RH-RC TERMINALS WHEN ONE TRANSFORMER POWERS BOTH HEATING AND COOLING.
FOR POWER STEALING ON COOLING, JUMPER C-RC AND C-Y TERMINALS.
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
CUSTOMER SUPPORT
Home and Building Control
Honeywell Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Home and Building Control
Honeywell Limited—Honeywell Limitée
740 Ellesmere Road
Scarborough, Ontario
M1P 2V9
Helping You Control Your World