Honeywell Q539A Home/Bldg Center Rnd Thermostat Subbase Instruction Manual
- June 9, 2024
- Honeywell
Table of Contents
Q539A, H and J Subbases
Installation Instruction for the Trained Service Technician.
Application
Q539 Subbases provide cooling anticipators, and mounting for T87F Thermostats. Q539 Subbases also provide system and fan switching for heating, cooling, and heating-cooling thermostats. For subbase specifications, refer to Tables 1 and 2.
TABLE 1—SUBBASE SPECIFICATIONS.
Model Description | System Switch | Fan Switch | Terminals | See Fig. |
---|
Q539A provides system and fan switching and cooling anticipator for heating
cooling systems. Includes indicator LOCKOUT LED for use in oil burner
systems.| HEAT OFFCOOL| AUTO-ON| RH -RC-W-Y-G-X| 3
Q539H provides fan switching with Z terminal for low voltage fan switch to
control fan in AUTO position.| NONE| AUTO-ON| R-W-Y-G-X-Z| 4
Q539J provides system switching for control of heating and cooling for heat
pump and electric heating. Auto fan operates through fan relay on both heating
and cooling.| HEAT OFFCOOL| AUTO-ON| R-W-Y-G-X-P-O-B| 5
TABLE 2—TERMINAL DESIGNATIONS.
Terminal | Connection |
---|---|
R | Transformer. |
Cooling Transformer. | |
Heating Transformer. | |
W | Heating Relay or Valve Coil. |
Y | Cooling Contactor Coil. |
Heating Damper Motor or Changeover Valve (if used). | |
Cooling Damper Motor or Changeover Valve (if used). | |
G | Fan Relay Coil. |
Clogged Filter Switch or Lockout Switch (primary control). |
a Cooling transformer in systems with separate heating and cooling circuits.
b Heating transformer in systems with isolated heating and cooling circuits.
c Circuit only completed between R and B with system switch in HEAT position.
d Circuit only completed between R and O with system switch in COOL position.
e Only available on subbases with indicator LEDs.
Mercury Notice
This control contains mercury in a sealed tube. Do not place control in the
trash at the end of its useful life. If this control is replacing a control
that contains mer cury in a sealed tube, do not place your old control in the
trash.
Contact your local waste management authority for instructions regarding
recycling and the proper disposal of this control, or of an old control
containing mercury in a sealed tube.
Installation
WHEN INSTALLING THIS PRODUCT…
- Read these instructions carefully. Failure to follow instructions can damage product or cause a hazardous condition.
- Check ratings given in instructions and on product to make sure product is suitable for your application.
- Make sure installer is a trained, experienced service technician.
- After completing installation check out product opera tion as provided in these instructions.
LOCATION
Locate the subbase about 5 ft (1.5m) above the floor in an area with good air
circulation at average temperature.
Do not mount the subbase where it may be affected by:
- drafts or dead spots behind doors or in corners.
- hot or cold air from ducts.
- radiant heat from the sun, fireplaces, or appliances.
- concealed pipes and chimneys.
- unheated (uncooled) areas such as an outside wall.
CAUTION
- Disconnect power supply to prevent electri cal shock or equipment damage.
- Do not short across coil terminals on relay, this can burn out the thermostat heat anticipator.
- Do not overtighten captive mounting screws because damage to subbase threads can result.
MOUNTING AND WIRING
Disconnect power supply before beginning installation to prevent electrical
shock or equipment damage.
All wiring must comply with local codes and ordinances.
-
In replacement applications, check the existing sub base wires for cracked or frayed insulation. Replace any wires in poor condition. If the wire is plastered into the wall, make a hole next to the wires and loosen the wires so that the wires can be pushed back into the wall later.
-
In new installations, run wiring (if necessary) to the subbase location.
IMPORTANT: To prevent interference with the thermostat linkage, keep wire length to a minimum and run wires as close as possible to the subbase. -
Connect the wires to the terminals inside the subbase.
Refer to equipment manufacturer instructions for Q539 wiring diagrams. If not available, refer to Fig. 1 through 5. -
Push excess wire back through the hole and plug any opening with insulation to prevent drafts that can affect performance.
-
Loosely fasten the thermostat subbase to the wall with a screw through the left mounting hole. Adjust the subbase so it is approximately level and start the second screw through the right mounting slot. Do not tighten.
-
Level the thermostat subbase using a spirit level as shown in Fig. 1.
-
Tighten mounting screws.
IMPORTANT: An incorrectly leveled subbase will cause the temperature control to deviate from setpoint. -
Mount and wire the thermostat to the thermostat sub base using the equipment manufacturer’s instructions.
Fig. 2—Barrier configuration.
Fig. 3—Typical hookup for Q539A in heating cooling application with remote lockout indication.
Settings
SUBBASE SETTING
The subbase switching positions control the system operation as described
below.
SYSTEM SWITCH (some subbases do not have all of the following functions):
COOL—cooling system is automatically controlled by the thermostat. Heating
system is off.
OFF—both the heating and cooling systems are off. If the fan switch is at AUTO
position, the cooling fan is also off.
HEAT—heating system is automatically controlled by the thermostat. Cooling
system is off.
FAN SWITCH:
ON—fan operates continuously.
AUTO—fan operates with cooling equipment as con trolled by the thermostat or
with the heating equip ment as controlled by the plenum switch.
To move the subbase switches to the desired control positions, use thumb and
index finger to slide lever. Stop lever must stop over desired function
indicator position for proper circuit operation.
Fig. 4—Typical hookup for Q539H in heating cooling application with remote
switching required to select heating or cooling and to provide automatic fan
operation.
X TERMINAL IS USED ON Q539 MODELS WITH FACTORY-INSTALLED MALFUNCTION LIGHT.
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
Fig. 5—Typical hookup for Q539J in heating cooling applications. Fan relay
operates automatically on heat or cool with fan in AUTO position
X TERMINAL IS USED ON Q539 MODELS WITH FACTORYINSTALLED MALFUNCTION LIGHT.
WITH NO O TERMONAL LOAD, THERMOSTAT CURRENT DURING HEATING CYCLE VARIES
DEPENDING ON WHETHER FAN SWITCH IS IN THE ON OR AUTO POSITION. HEATER SHOULD
BE SET FOR COMBINED CURRENT LEVEL OF HEAT RELAY AND FAN RELAY COILS. WITH O
TERMINAL LOAD, SET THERMOSTAT HEAT ANTICIPATOR TO ITS MAXIMUM SETTING. (LIMIT
THE THERMOSTAT HEATING LOAD CURRENT TO 0.8 AMPS TO ASSURE GOOD PERFORMANCE.)
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
Checkout
When installation is complete, turn on power supply and check system operation.
HEATING
Move the system switch on the Q539 to HEAT and the fan switch to AUTO. Move
the heating setpoint dial to about 6°AC (10°AF) above room temperature.
Heating equipment should start and the fan should run. Change the setpoint to
about 6°AC (10° AF) below the room temperature. The heating equipment and fan
should shut off.
NOTE: In heat pump applications, a minimum off-timer provides a five-
minute time delay before starting com pressor when the thermostat last turned
off the compres sor, or when the system first received power. This delay
prevents compressor short cycling.
COOLING
CAUTION
If outside air or heat exchange medium (water) is below 10° AC (50° AF), do
not operate cooling.
Move the system switch on the Q539 to COOL and the fan switch to AUTO. Move
the cooling setpoint dial to about 6° AC (10° AF) below room temperature.
Cooling equipment should start and the fan should run. Change the setpoint to
about 6° AC (10° AF) above the room temperature. The cooling equipment and fan
should shut off.
FAN
Move the subbase switch to OFF and the fan switch to ON. The fan should run
continuously. Move the fan switch to AUTO. In this position, fan operation is
controlled by the heating or cooling system control circuit.
Operate the entire system one complete cycle with switches in each position
before leaving installation. Turn thermostat dial to the desired setting and
set the system and fan switches.
Automation and Control Solutions
Honeywell
1985 Douglas Drive North
Golden Valley, MN 55422
Honeywell Limited
35 Dynamic Drive
Scarborough, Ontario
M1V 4Z9
Printed in U.S.A. on recycled paper containing at least 10% post-consumer
paper fibers.
95-6486–9 G.H. Rev. 8-02
www.honeywell.com/yourhome
firealarmresources.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>