POTTER RA-6500 LCD Annunciator Owner’s Manual

June 9, 2024
POTTER

POTTER RA-6500 LCD Annunciator Owner’s Manual
POTTER RA-6500 LCD Annunciator

Features

  • Industry leading 4 line by 40 Character LCD
  • Common buttons for navigation
  • Common LEDs for status indication
  • 31 annunciator per panel
  • Maximum wire length of 6,500 feet
  • Available in 4 colors
  • Product includes a 5 year warranty

Description

The RA-6500 is a LCD remote annunciator for the PFC-6000 series fire control panels. The RA-6500 communicates using a RS-485 connection to the main panel providing common indication of Alarms, Supervisory, Trouble and other system status and control functions.

The RA-6500 features a 4×40 LCD display with LED’s for Power,  Alarm, Supervisory, Trouble, and Silenced conditions. It can bemounted on a single gang electrical box or a four square electrical box.
The annunciator is enclosed in a sheet metal enclosure and has a Potter lock securing the keypad.

Technical Specifications

Standby Current 20 mA
Alarm Current 25 mA
Operating Temperature 0°C-49°C (32°F-120°F)
Operating Humidity Range 10%-93% @ 30°C (86°F) noncondensing humidity
Maximum Wire Length 6500 ft.
Maximum Annunciators 31
Size (WxHxD) 10” x 7-7/8” x 1-5/8”
Wire Gauge 14 AWG-22 AWG

Installation

The RA-6500 is connected to the PFC-6000 series fire control panels using a four wire RS-485 connection. The connection is power limited and supervised. Up to thirty-one (31) RA-6500 LCD annunciators can be connected using Class B or Class A wiring. Class A wiring requires an optional Class A Expander.

RA-6500 Class B Wiring Example Fig 1
Wiring Diagram

RA-6500 Class A Wiring Example Fig 2
Wiring Diagram

Address Settings

The RA-6500 address is set by dip switch S1 located on the back of the RA-6500. The address must be set in the range of 1 to 31 to be recognized by the control panel.

**RA-6500 Remote (Panel View) Fig 3

**

RA-6500 Enclosure Fig 4

Dimensions

Dimensions
Dimensions

Dip Switch Settings

Refer to the table below for dip switch settings per Annunciator Address.

Annunciator Address Dip Switch Settings
SW-1 SW-2
1 On
2 Off
3 On
4 Off
5 On
6 Off
7 On
8 Off
9 On
10 Off
11 On
12 Off
13 On
14 Off
15 On
16 Off
17 On
18 Off
19 On
20 Off
21 On
22 Off
23 On
24 Off
25 On
26 Off
27 On
28 Off
29 On
30 Off
31 On

Ordering Information

Model Description Stock No.
RA-6500 LCD Annunciator – RED 3992660
RA-6500 LCD Annunciator – BLACK 3992744
RA-6500 LCD Annunciator – GRAY 3992745
RA-6500 LCD Annunciator – LIGHT GRAY 3992746

POTTER Logo

Potter Electric Signal Company, LLC
St. Louis, MO
Phone: 800-325-3936
www.pottersignal.com
firealarmresources.com

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals