COMPOR KPM31 Single Phase DIN Rail Energy Meter Instruction Manual

June 9, 2024
COMPOR

KPM31 Single Phase DIN Rail Energy Meter

1.4

Power frequency withstand voltage: In line with GB /T13729-2002 provisi

ons, Power frequency voltage 2KV,Insulation resistance 1 minute.Insulat

ion resistance: In line with GB / T13729-2002 provisions, Insulation resis

tance 50M Impulse voltage: In line withGB / T13729-2002 provisions,

can bear the impact of 1.2 / 50US, 5KV peak standard lightning.

1.5
Vibration response: IEC255-21-1:1998, level 1

Vibration durability: IEC255-21-1:1998, level 1

Impact response: IEC 255-21-2, level 1

Impact durability: IEC 255-21-2, level 1

A

Collision: IEC 255-21-2, level 1

1.6
Electrostatic discharge immunity: IEC61000-4-4,level 4 Fast pulse group immunity: IEC61000-4-5, level 4 Surge immunity: IEC61000-4-2, level 4 Power frequency magnetic field immunity: IEC61000-4-8, level 4

Working temperature: -10+55
Relative humidity: 5%~95% non-condensing
Storage temperature: -20+75 Altitude: Below 3000 meters
Input voltage: Rated 220V Input current: 5-60A Power consumption: Whole set power consumption < 0.5VA Overload capacity:
AC voltage loop: 1.2 times rated voltage, continuous work 2 times rated voltage, allow 10s
AC current loop: 1.2 times rated current, continuous work 20 times rated current, allow 1s

KPM31 is designed with advanced microprocessor and digital signal processing technology. It integrates comprehensive sing le- phase power measurement, display, energy accumulation, and network communication. It has strong anti- interference abil ity and can still work stably in situations with severe electromagn etic interference.

Parameters U I P Q

Accuracy 0.2% 0.2% 0.5% 0.5%

Parameters PF kWh kVar F

Accuracy ±0.5% 0.5s Class 2 ±0.02

Optional functions WIFI wireless communication
K-DI Dual source power metering(DI)
A-Standard B-Relay control
Product series
Compere Power Meter For example, KPM31A: Standard ,Rated 220V, 5(60)A, Standard model, multi-rate energy statistics, historical electric energy statistics, single-phase rail smart energy meter.

Measure and monitor electric energy parameters in the distribution system Energy efficiency management system Statistical analysis of internal power consumption and basis for charging statistics Automatic meter reading system for electric energy me asurement Intelligent power distribution management system

Pulse output: KPM31A&B provides active/reactive energy measurement, active energy pulse output function, adopts the output of the optocoupler open collector, the method of energy accuracy inspection refers to the national measurement regulation: the pulse error comparis on method of the standard meter.
4.5 Prepayment The user needs remote pre stored electric energy. When the pre stored electric energy is 0, it will prompt the user to purchase electric energy (automatic power transmission after 10 seconds of power failure). The instrument defaults to an overdraft limit of 5 degrees, and the user can set and read the overdraft limit remotely. 4.6 Load control The user can set / read the load threshold remotely, and view the load threshold locally in the p-val display item. The default is 65535kW. When the active power is greater than the load threshold for 30 seconds, the instrument will cut off the power. After the power is cut off, the power can only be transmitted through the local interface operation (the “Relay” option of the setting interface). 4.7 Relay control mode The relay control mode is divided into local mode and remote mode, and the default is remote mode. Local mode: the default prepayment and load control functions are turned on. The control of the relay is controlled by the local instrument according to the state of the electricity meter, and the remote control does not work . Remote mode: the default prepayment and load control func-tions are turned off, and the relay is controlled remotely. Note: switch between remote and local modes through

Real-1
U: I: F:

220.0V Voltage 004.9A Current
50 HZ Frequency

ENTER

Real-1
P: Q: S:

000.0W Active power 000.0var Reactive power 000.0VA Apparent power

ENTER
Real-1 PF: DO:

+0.00 Power factor

NO

Relay status

ENTER

EP1(kWh) +: 00000000.0

First positive and negative and

-:

00000000.0 total active

C:

00000000.0

powerelectric energy

ENTER

ENTER

Second

EP2(kWh)

positive and

+:

00000000.0 negative and

-:

00000000.0 total active

C:

00000000.0

powerelectric energy

ENTER

EQ1(kvarh)

First positive

+: -:
C:

00000000.2 and negative

00000000.0

and total reactive electric

00000000.2 energy

ENTER

EQ2(kvarh)

Second positive

+:

00000000.2

and negative and total rea-

-: 00000000.0 ctive electric

C: 00000000.2 energy

ENTER

Date2000-00-00 Time00-00-00

Adr: 001

Modbus adress

S-EP: 00000.0kWh Residual elec-

tric energy

ENTER

P-Val65535kW Load threshold R-ModL&N-P Running mode V2.1-20220310 Software version

Set01 PASS6666
Adr001 Baud9600
Set02 ParityNONE
ClrENO R S T WN O
Set03 Date2000-00-00 Time00-00-00 V2.1-20220310
Set04 W i f i – MM QT T ClrS-EPNO
F-Set50Hz
Set05 CTR-MRemote
RelayNO

Please make settings before starting measurement. When entering the setting screen, you need to press and hold for 3 seconds to enter the password input interface. The default password is 6666. the password correctly. Long press key to enter the parameter setting interface, and then press key to select the item to be set, after long press key, the first number from left of the set value will start to flash, short press key to select the digit to be modified, short press the key to increase modified bit value. After finish the modification, long press key to confirm. In the setting interface, if there is no operation for 30s, it will return to the measurement display screen, or short press the and keys at the same time to return directly to the

8. WiFi mode setting
:MQTT:Data uploadDebugConfigwifi Wifi-MMQTT ENTER :Short press the “Enter ” key to mod-
ify, and then long press the “Enter ” key to stop flashing. The modification is s u c c e s s f u l . D e f a u l tM QT T. Note:In the debug mode, the instrument configures the WiFi
module networking parameters. After the configuration is com-
pleted, it needs to switch to the mqtt mode before the instrume-
nt can normally connect to the mqtt ser ver. 9. Clear residual electric energy

Swtich between Yes and no
ClrS-EP:NO ENTER Short press the “Enter “key to mod-
ify, long press the “Enter ” key does
10. Frequency setting not flash, and the modification is successful.

:Can be switched to 50Hz or 60Hz F-Set50Hz ENTER :Short press the “Enter ” key to mod-
ify, and then long press the “Enter ” key to stop flashing. The modification is successful.Default50Hz 11. Relay control mode setting

:Can be switched to remote mode or local

CTR-M:Remote

mode

ENTER :Short press the “Enter ” key to mod-

ify, and then long press the “Enter ”

12. Relay control

key to stop flashing. The modification is successful.Default:Remote.

Relay: ON

Control the opening or closing of relay ENTER :Short press the “Enter ” key to mod-

ify, and then long press the “Enter ” key to stop flashing. When you hear the relay action, the modification is successful.

5.4 Parameter setting The parameter setting menu structure menu is as follows
Default value list

7.Reset WIFI module

Clr-E

NO

Reset WIFI RSTW NO Used to reset WIFI and configure WIFI module

WiFi mode Wifi-M MQTT Switch WiFi mode: MQTT or Debug

Clear residual electric energy Frequency
setting

ClrS-EP F-Set

NO 50Hz

Used to clear residual energy Switching frequency to 50Hz or 60Hz

Relay control mode CTR-M Remote Switch the control mode to local or remote

Relay control

Relay

ON Control the opening or closing of relay

6.1 RS485 KPM31 single-phase DIN rail meter provides MODBUS-RTU communication protocol, 1 start bit, 8 data bits, 1 parity bit, 1 stop bit, each byte length is 11 bits. Supported baud rate: 1200, 2400, 4800, 9600 (bps). Factory default communication parameters: 9600bps, even parity The format of each byte in RTU mode: 1 start bit + 8 data bits + 1 parity bit + 1 stop bit The format of the data frame is as follows: Address field + command field + data field + CRC check field
16

FAQ for network connection
1. Issuing timeout: data communication timeout. It means the settings are not successfully or setting is succeeded but data return is failed. Solution: Click OK’ to stay on the device information page and wait for 30 seconds to see if the device is showing offline. If yes (offline), that means the setting is succeeded. If notonline), pls submit again. 2\. Parameter lost: Data lost during communication. Solution: ClickOK’ to stay on the device information page and wait for 30 seconds to see if the device is showing offline. If yes (offline), that means the setting is succeeded. If notonline), pls submit again.

6.2 Wireless communication KPM31 supports WiFi wireless communication mode and can be connected to enterprise wireless AP. The uplink adopts mqtt protocol for data communication with the master station. The specific configuration steps are as follows:
Step 1: Set mobile hotspot Set the WiFi hotspot account to compere-debug and the password to kpm-debug for the meter to connect. Then
start the settings on Touch Energy APP.
Step 2: Set the meter to debug mode
Enter the setting interface of the meter, find the “Wifi-M” option and set it to the “Debug” mode.
Wifi-M:Debug

Input private server address (support domain name and IP address), server port, MQTT account, MQTT password, etc. If using WIFI meter, the local WIFI name and Password are required. WPA2 for enterprise level WIFI can be set too. If using 4G meter, the WIFI name and Password is not required.
4.2 4G communication setting Input server address (support domain name and IP address), port, MQTT account, MQTT password and submit. The default information is for sending data to T@ENERGY cloud platform.
4.3 WIFI communication setting Input server address (support domain name and IP address), port, MQTT account, MQTT password, local WiFi name and password (WPA2 for enterprise level WIFI can be set too) and submit. The default information is for sending data to T@ENERGY cloud platform.

The server configuration of both modes needs to use Touch Energy APP-meter setting function. The configuration steps are 5. Wait for about 20 seconds for the meter to return status

as follows:

information.

Step 3: `Touch Energy’ APP meter setting

If the configuration is successful, it will display “Successfully issued, please continue “, click `exist’ to return to the device

1. Download `Touch Energy’ from Google play or Apple store. As Fig 1.

ID search interface.

2. Click `Meter setting’ to enter the code search page. As shown in Fig 2.

Click “next” for bulk quantity meters settings. It will enter the last setting page and retain the data set last time. Users only need to change the meter number and submit.

3. Search for devices: Input the production number to search If the number is wrong, the search button will be grayed and cannot be clicked. If the number is correct, click the “code search” button to identify the device.
4. Input the configuration parameters and submit: After entered the device details page, click refresh button in Device status until it’s online. 4.1 Private server settings This page is for the meters sending data to the customers’ private server.

Note: The device status will be offline after submitted successfully.
Step 4: Set the meter to MQTT mode
Wifi-M: MQTT