POTTER RA-6006 LCD Annunciator Installation Owner’s Manual
- June 9, 2024
 - POTTER
 
Table of Contents
POTTER RA-6006 LCD Annunciator Installation
Features
- 
Standby Current 20 mA
 - 
Alarm Current 25 mA
 - 
Operating Temperature 0°C-49°C (32°F-120°F) 10%-93%
@ 30°C (86°F) non-condensing humidity - 
Maximum Wire Length 6500 FT
 - 
Maximum Annunciators 31
 - 
Dimensions (WxHxD) 8” x 6-1/4” x 1-5/8” (Cabinet)
 - 
Wire Gauge 14 AWG-22 AWG
 - 
Display 2 lines x 16 characters
 - 
Product includes 5 year warranty
 
Canadian listed remote annunciator for the Potter PFC-6006 Sprinkler Monitoring Panel.
Description
The RA-6006 is a LCD remote annunciator for the PFC-6006 Sprinkler Monitoring
Panel. The RA-6006 communicates using a RS-485 connection to the main panel
providing common indication of Alarms, Supervisory, Trouble and other system
status and control functions.
The RA-6006 features a 32 character, 16×2 LCD display with LED’s for Power,
Alarm, Supervisory, Trouble, and Silenced conditions.
It can be mounted on a single gang electrical box or a four square electrical
box. The annunciator is enclosed in a sheet metal enclosure and has a Potter
lock securing the keypad.
Installation
The RA-6006 is connected to the PFC-6006 using a four wire RS-485 connection. The connection is power limited and supervised. Up to four (4) RA-6006 LCD annunciators can be connected using Class B wiring.
NOTICE
Install in accordance with compatible fire alarm panel.

Address Settings
The RA-6006 address is set by dip switch S1 located on the back of the
RA-6006. The address must be set in the range of 1 to 31 to be recognized by
the control panel.
Dip Switch Settings
Refer to the table below for dip switch settings per Annunciator Address.
| Annunciator Address | Dip Switch Settings | 
|---|---|
| SW-1 | SW-2 | 
| 1 | On | 
| 2 | Off | 
| 3 | On | 
| 4 | Off | 
| 5 | On | 
| 6 | Off | 
| 7 | On | 
| 8 | Off | 
| 9 | On | 
| 10 | Off | 
| 11 | On | 
| 12 | Off | 
| 13 | On | 
| 14 | Off | 
| 15 | On | 
| 16 | Off | 
| 17 | On | 
| --- | --- | 
| 18 | Off | 
| 19 | On | 
| 20 | Off | 
| 21 | On | 
| 22 | Off | 
| 23 | On | 
| 24 | Off | 
| 25 | On | 
| 26 | Off | 
| 27 | On | 
| 28 | Off | 
| 29 | On | 
| 30 | Off | 
| 31 | On | 
Potter Electric Signal Company, LLC • St. Louis, MO • Cust Service: 866-956-1211 • Tech Support: 866-240-1870 • Canada: 888-882-1833 • www.pottersignal.com
MFG. #5406081 – REV A
References