POTTER TTS Tank Temperature Supervisory Switch Owner’s Manual
- June 9, 2024
- POTTER
Table of Contents
POTTER TTS Tank Temperature Supervisory Switch
CUL, UL and CSFM Listed, FM Approved, and NYMEA Accepted
2 1/2″ DIA x 17 1/2″L
(63,5mm DIA x 445mm L)
Ordering Information
Model Number Stock Number
TTS-S (steel) 1010040
TTS-W (wood) 1010041
Accessories
1″ Flange 5020012
Buttress Nut 5020105
Gasket 5330035
The Model TTS is a water tank temperature supervisory switch preset to give a low temperature signal at 40°F/4,5°C and a high temperature signal at 140°F/60°C (±5°F/3°C). It is UL Listed and FM Approved. A bi-metal thermostat is used for low temperature sensing and a bi-metal thermostat for high temperature sensing. A diode is used in this unit as a testing aid. When the polarity of DC current is reversed at the feed wires to a TTS, the diode in the circuit prevents the flow of current, proving the absence of a short circuit fault in the wiring or the device itself.
Testing
To test for a short or open in the TTS, connect an ohmmeter across the white
and black TTS leads. With the meter connected positive to white and negative
to black, the meter will read continuity (about 1 meg ohm). With the meter
connected reverse polarity, the meter will read open. If using the diode
tester setting on the meter, the meter will read .5 observing polarity and
open with reverse polarity.
To test the thermostat, the device must be exposed to temperatures of 40°F and
140°F. The appropriate thermostat will open creating an open circuit
regardless of polarity.
Wiring
The TTS is normally closed device that opens when the probe is exposed to the
operating temperature of the thermostats. The device is polarity sensitive.
The positive leg of the initiating device circuit must be connected to the
white wire lead. The negative leg of the initiating device circuit must be
connected to the black wire lead. If the TTS is the last or only device on the
initiating circuit, the EOLR must be wired in series with the TTS. It can be
wired in series with either the black or white wire.
Contacts: .15 Amp at 115 VDC
The TTS, tank temperature switch is supplied with a one inch pipe thread for steel tanks (Model TTS-S) or with a buttress thread for wood tanks (Model TTS-W).
A buttress thread nut and gasket are available for use with the TTS-W for installations where the inside of the tank is accessible and it is not convenient to weld a flange on the tank.
The nut and gasket can also be used on a wood tank, which is not sound enough to hold a thread (see Fig. 1). Locate the switch at a point 24″ (60cm) below the required water level of the tank.
For steel tanks, weld in a No. 282-1 pipe flange or drill and tap tank to receive the one inch pipe thread of the bushing (see Fig. 2).
For wood tanks, drill a 1 3/16″ (30mm) hole in the center of a stave and thread the bushing into the tank allowing the buttress bushing to cut its own thread (see Fig. 3).
Installation
Important: Observe lead polarity for use in normally closed circuit.
Important: Observe lead polarity for use in normally open circuit.
Potter Electric Signal Company, LLC • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936/Canada 888-882-1833• www.pottersignal.com
CUSTOMER SUPPORT
References
- Fire Alarm Resources | Download fire alarm documents
- Potter Electric: Fire Alarms & Fire Sprinkler Systems
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>