POTTER SH-1224 Series Wall Mount Select A Strobe Horn Owner’s Manual

June 9, 2024
POTTER

POTTER SH-1224 Series Wall Mount Select A Strobe Horn Owner's Manual

POTTER SH-1224 Series Wall Mount Select A Strobe Horn Owner's
Manual

  • UL and cUL listed · 12 VDC with 15, 35 or 60 cd setting
  • 24 VDC with 15, 35, 60, 75, 95 or 110 cd settings
  • 6 distinct candela settings
  • Candela selection view window
  • 15/75 ADA compliant on 60cd setting
  • 33 sound output settings
  • Horn or chime sound output
  • Pre-wire back plate
  • Universal back plate mounting (single gang, double gang, octagon, or 4″ square)
  • Single screw mounting
  • Indoor only
  • Low current draw

The SH-1224 Strobe/Horn Series provides a wide range of candela light output options in a single device. The candela settings include a 12 or 24 volt DC operation for the 15, 35 and 60 (75 on axis) candela settings and 24 volt DC operation for the 15, 35, 60, 75, 95 and 110 candela settings. The candela setting is displayed through the front window and is selectable using a drum wheel.

The horn settings include Temporal, Non-Temporal, March Time and a Chime sound. The horn also has Low, Mid and High volume settings for each pattern and tone. The tones include 2400 Hz, Electro Mechanical, Broadband and Chime.

The voltage input can be either regulated DC or full wave rectified (FWR) 12 volt or 24 volt operation with an operating range from 8 to 33 V DC. The strobes can be synchronized using a control panel with the Potter (Amseco) sync protocol or a SMD10-3A sync module.

The SH-1224 utilizes a universal mounting plate that will mount on a single gang, double gang, octagon and 4″ square electrical boxes. The back plate allows the installer to mount the plate and connect the wire connections. The strobe attaches in a hinge fashion from the top and is secured by a single mounting screw. The strobe completely covers the mounting back plate, therefore it can be mounted before other trades work is completed and not affect the final look.

Installation

POTTER SH-1224 Series Wall Mount Select A Strobe Horn Owner's Manual -
Installation

Note: Installation must comply in accordance with applicable standards.

Ordering Information

POTTER SH-1224 Series Wall Mount Select A Strobe Horn Owner's Manual -
Ordering Information

Dimensions: inches (mm)

Light output in precentage when measured from the following directions per UL 1971.

POTTER SH-1224 Series Wall Mount Select A Strobe Horn Owner's Manual - Light
output in percentage

⚠ WARNING High voltage may be present inside the light assembly even though power is not connected. If access to teh coponent board is required (removal or replacement), the capacitor must be discharged by touching a wire to both ends of the flashtube.
DO NOT attempt to touch or move the assembly until the capacitor has been discharged.

Specifications

Strobe Current

POTTER SH-1224 Series Wall Mount Select A Strobe Horn Owner's Manual -
Specifications

Note: To determine total current draw, add desired strobe setting and horn selection. Refer to the installation instructions for further information.

Horn Dipswitch
Pattern
1 ON – Non-temporal
1 OFF – Temporal
Both 2 = OFF
1 and 2 ON = March Time
Tone
3 and 4 ON = 2400Hz
3 ON and 4 OFF = Electromechanical
3 and 4 OFF = Chime
3 OFF and 4 ON = Broadband
Volume
5 and 6 ON = High
5 ON and 6 OFF = Mid
5 and 6 OFF = Low
7 and 8 ON = Horn/strobe on 2 wires
7 and 8 OFF = Horn and strobe on 4 wires

Non-Temporal Horn Current

POTTER SH-1224 Series Wall Mount Select A Strobe Horn Owner's Manual - Non-
Temporal Horn Current

Temporal Horn Current

POTTER SH-1224 Series Wall Mount Select A Strobe Horn Owner's Manual -
Temporal Horn Current

March Time Horn Current

POTTER SH-1224 Series Wall Mount Select A Strobe Horn Owner's Manual - March
Time Horn Current

Wiring Diagram

Wiring observe Polarity use both terminals or lead for connection. Break wire run to provide electrical supervision.

POTTER SH-1224 Series Wall Mount Select A Strobe Horn Owner's Manual -
Wiring Diagram

Refer to the SMD 10-3A Sync Module instruction manual for Class “A” wiring or other application diagrams.

Engineering Specifications

The installer shall provide and install the Potter SH-1224 selectable strobe/horn. The strobe shall have six (6) candela settings. The candela settings shall be selectable using a drum roller and shall display the candela setting on the front of the device. The horn shall have 33 selectable settings configurable by dip switches. The sounder shall be capable of ANSI Temporal Code 3, March Time and produce a chime output. The horn shall have three distinct volume levels. The strobe/horn shall operate at 12 or 24 VDC regulated or full wave rectified. The strobe/horn shall have an operating range between 8 and 33 VDC. the strobes an by synchronized using a control panel with the Potter sync protocol or the SMD10-3A sync module. The strobe shall utilize a mounting plate that allows the installer to pre-wire the mounting plate. The mounting plate shall be universal and mount on a single gang, double gang, octagon or 4 inch square box. The mounting plate shall be completely covered by the strobe and shall be secured by a single screw. The strobe shall be UL listed to standard 1638, General Signaling, and standard 1971, Signaling Devices for the Hearing Impaired. In addition, the strobes shall be cUL listed to CANULC S526. The horn shall be UL listed to standard 464, Audible Signaling Devices.

Potter Electric Signal Co., LLC • St. Louis, MO • Cust Service: 866-240-1870 • Tech Support:866-956-1211• Canada 888-882-1833www.pottersignal.com

firealarmresources.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

POTTER User Manuals

Related Manuals