POTTER LCD-AN LCD Annunciator Owner’s Manual

June 9, 2024
POTTER

POTTER logo LCD-AN LCD Annunciator
Owner’s ManualPOTTER LCD-AN LCD Annunciator LCD-AN
LCD ANNUNCIATOR

Product includes a 5 year warranty

Features

Standby Current 35 mA
Alarm Current 65 mA
Ambient Operating Temp 0°C-49°C (32°F-120°F)
Maximum Wire Length 4000°
Maximum Annunciators 31
Size (H x W x D) 5-7/8″x7″x1-1/2″
Wire Gauge 14 AWG-22 AWG
Compatible Control Panels PFC-8060 & PFC-8500

Description

The LCD-AN is a LCD remote annunciator for the PFC-8060 and PFC-8500 addressable fire control panel. The LCD-AN communicates using a RS-485 connection to the main panel providing common indication of Alarms, Supervisory, Trouble and other system status and control functions. The LCD-AN features a 20×4 LCD displaywith LED’s for Power, Alarm, Supervisory, Trouble, and Silenced conditions. It can be mounted on a 2-gang electrical box or a standard 4″ sqaure electrical box. The keypad is only operable when a keylocked security switch is set to the enable position.

Installation

The LCD-AN is connected to the PFC-8500 using a four wire RS-485 connection. The connection is power limited and supervised. Up to thirty-one (31) remote annunciators can be connected using Class B (Style 4) wiring.

Configuration Characteristics

  • The RS-485 maimum wire length is 4000 feet (1219.2 meters)
  • Maximum wiring resistance is less than 40 ohms
  • Maximum capacitance between wiring is less than 0.4 micro F

Notes

  1. JP of the farthest annunciator must be shorted, and JP of other annunciators shall be open
  2. Any connection to ground of 10,000 ohms will be annunciates a ground fault
  3. Remote annunciators must be mounted on either a 2-gang or standard 4-inch square electrical box

LCD-AN Class B Wiring Example Address Settings

  1. Switch 1 of Dip Switch S1 set on, after that input 24 VDC to TB1.POTTER LCD-AN LCD Annunciator - fig 2
  2. The LCD-AN shows LCD display as follows. Set the assigned number by 0 -9 key. After that, pust ENT key.
  3. Swtich 1 of Dip Switch S1 set off, LCD-AN will proceed to initializing.

POTTER logoPotter Electric Signal Co., LLC
St. Louis, MO
Cust Service: 866-240-1870
Tech Support: 866-956-1211
Canada 888-882-1833
www.pottersignal.com
MKT. #8830025 – REV B1
firealarmresources.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals