POTTER SL-1224WP Series Wall Mount Weather Proof Select-A-Strobe Owner’s Manual

June 9, 2024
POTTER

POTTER logo SL-1224WP Series Wall Mount Weather Proof Select-A-Strobe
Owner’s ManualPOTTER SL-1224WP Series Wall Mount Weather Proof
Select-A-Strobe SL-1224WP SERIES
WALL MOUNT WEATHER PROOF
SELECT-A-STROBE®

SL-1224WP Series Wall Mount Weather Proof Select-A-Strobe

  • 12 VDC with 15, 35 or 60 cd setting
  • 24 VDC with 15, 35, 60, 75, 95 or 110
  • Outdoor or indoor
  • 6 distinctive candela settings
  • Candela selection view window
  • 15/75 ADA compliant on 60cd setting
  • Pre-wire back plate
  • Universal back plate mounting (single gang, double gang, octagon, or 4” square)
  • Single screw mounting
  • Low current draw
  • UL and cUL listed Patents pending

The SL-1224WP Strobe Series provides a wide range of candela light output options in a single device. The candela settings include a 12 or 24 volt operation for the 15, 35  and 60 (75 on axis) candela settings and 24 volt operation for the 15, 35, 60, 75, 95 and 110 candela settings. The candela setting is displayed through the front window and is selectable using a drum wheel. The voltage input can be either regulated DC or full wave rectified (FWR). The strobes can be synchronized using a control panel with the Potter (Amseco) sync protocol or a SMD10-3A sync module.
The SL-1224WP utilizes a universal mounting plate that will mount on a single gang, double gang, octagon and 4” square electrical boxes.
The back plate allows the installer to mount the plate and terminate the wire connections. The strobe attaches in a hinge fashion from the top and is secured by a single mounting screw. The strobe completely covers the mounting back plate, therefore it can be mounted before other trades work is completed and not affect the final look.
The Potter SL-1224WP is listed for both outdoor and indoor applications. For outdoor installations, the device must be mounted on a matching BBX-5 back box or BBK-1 outdoor bell back box.

Installation

Note: Installation must comply in accordance with applicable standards. Outdoor installations require the use of the optional BBX-5 or BBK-1 bell back box.

Ordering Information

Stock Number Model Number Description Color
4700050 SL-I224WP-R Selectable strobe only Red
4700051 SL- I224WP-W Selectable strobe only White
4670017 SMD10-3A Sync Module
4270048 BBX-5 Back box (included) Red
4270049 White
1500001 BBK-1 Bell back box Red

Wiring Diagram
Wiring Observe Polarity Use both terminals (or Lead) for connection. Break wire run to provide electrical supervision.
Strobe Only
WARNING
High voltage may be present inside the light assembly even though power is not connected. If access to the component board is required (removal or replacement), the capacitor must be discarged by touching a wire to both ends of the flashtube.
DO NOT attempt to touch or move the assembly until the capacitor has been discharged.
Dimensions: inches (mm)

Specifications

Strobe Current

Setting| Light
Output| Max. RMS Operating Current (mA RMS)
---|---|---
Reg. 12 VDC| Reg. 12 FWR| Reg. 24 VDC| Reg. 24 FWR
I| 15cd| 129| 185| 100| 102
| 35cd| 160| 214| 135| 161
3| 60/75cd| 193| 239| 171| 202
4| 75cd| NA| NA| 190| 228
5| 95cd| NA| NA| 211| 255
6| 110cd| NA| NA| 225| 284

Note: All current draw shown is worst case at -40°F (-40°C).

Voltage 12/24V
UL Designation Regulated 12 DC/FWR
Operating Voltage Range 8 – 17.5V
Flash Rate 60 times/min.
Sync Module (SMD10-3A) NA

Operating Temperature
Range| Indoor installations: 32°F to 120°F (0°C to 49°C)
Outdoor installations: -40°F to 151°F (-40°C to 66°C)

Light output in percentage when measured from the following directions per UL1971.
Wall mount vertical dispersion

Degrees % of Rating Horizontal % of Rating Vertical
0 100 100
5-25 90 90
30 75 90
35 75 65
40 75 46
45 75 34
50 55 27
55 45 22
60 40 18
65 35 16
70 35 15
75 30 13
80 30 12
85-90 25 12

Engineering Specifications
The installer shall provide and install the Potter SL-1224WP selectable strobe. The strobe shall have six (6) candela settings. The candela settingshall be selectable using a drum roller and shall display the candela setting on the front of the device. The strobe shall operate at 12 or 24 VDC regulated or full wave rectified (FWR) and shall have an operating range between 8 and 33 VDC. The strobes can be synchronized using a control panel with the Potter (Amseco) sync protocol or a SMD10-3A sync module. The strobe shall utilize a mounting plate that allows the installer to pre-wire the mounting plate. The mounting plate shall be universal and mount on a single gang, double gang, octagon or 4 inch square box. The mounting plate shall be completely covered by the strobe and shall be secured by a single screw. The SL-1224WP can be mounted outdoor and is listed for such applications. In outdoor installations, the SL-1224WP shall be mounted on either a matching BBX-5 or BBK-1 weatherproof back box. The operating range shall be 32°F to 120°F (0°C to 49°C) for the indoor installations and -40°F to 151°F (-40°C to 66°C) for the outdoor installations. The strobe shall be UL listed to standard 1638, General Signaling, and standard 1971, Signaling Devices for the Hearing Impaired. In addition, the strobes shall be cUL listed to CANULC S526.

POTTER logoPotter Electric Signal Co., LLC
St. Louis, MO
Cust Service: 866-240-1870
Tech Support: 866-956-1211
Canada 888-882-1833
MKT. #8910007 – REV G
www.pottersignal.com