POTTER SL24W-75110 Select A Strobe Owner’s Manual

June 9, 2024
POTTER

SL24W-75110
SELECT-A-STROBE

SL24W-75110 Select A Strobe

  • Meets or exceeds NFPA/ANSI Standards and ADA  Accessibility Guidelines
  • UL Listed for wall mounting
  • Screw terminal capacity up to AWG12
  • Universal mounting plate included
  • 24V DC strobe with two field selectable settings: 75cd or 110cd
  • Polarized strobes with wide operating voltage range using filtered DC or unfiltered FWR input voltage
  • Mounts to 4” square, single gang, double gang, or octagonal back box
  • Tamper­proof candela selector switch
  • Synchronization requires Sync Module (SMD10­3A)
  • Available in red or white housing

Amseco’s SelectAStrobe Series is designed to comply with the Americans with Disabilities Act (ADA) and meet UL standard 1971 requirements for emergency signaling devices for the hearing impaired. The SelectAStrobe SL24W series features a unique candela intensity field selector switch for alternating the candela output 75cd to 110cd. The strobe housing is clearly labeled with vertical “FIRE” lettering. The strobe is polarized for connecting to supervised fire alarm circuits and is designed with a xenon flashtube to provide maximum performance with a candela intensity field selector switch. The SL24W-75110 can be synchronized by using the SMD10-3A Sync Module to comply with NFPA recommendations concerning photosensitive epilepsy when installing two or more visual appliances within the field of view. The strobe signals are listed for indoor use, wall mount, under UL 1971 standard.

Ordering Information

Model Nwnber| Stock Number| Housing Color| Input Voltage| Operating Voltage Range| Selectable Strobe Output| Flash Rate| Wiring Type| Mounting Type| Operating Temperature Range
---|---|---|---|---|---|---|---|---|---
SL24W-75110R| 4560019| Red| Regulated 24V DC/FWR| 16 – 33V DC
16 – 33V FWR| 75cd or
110cd| 60 times/
min.| Terminals| Wall Mount| 32°F – 120°F (0°C – 49°C)
SL24W-75110W| 4560020| White

Engineering Specifications

The visual alarm indicating appliance shall be Amseco model SL24W-75110 or equivalent device. The strobe shall be listed under UL 1971 standard for signaling devices for the hearing impaired and shall be approved for fire protective service. For outdoor applications and in UL NEMA-4X rated or UL Haz Dust Tight condition, use Amseco UL/ULC ESH1229/1229HTR polycarbonate covers. The candela output shall be field selectable, having a dual setting of 75cd or 110cd output. The signaling strobe shall operate on 24V DC from a noncoded regulated DC supply or fullwave rectified, unfiltered supply. The strobe shall be designed to produce one signal flash per second with continuously applied minimum voltage. The strobe shall have a universal back mounting plate, capable of wall mounting to a back box. When strobe synchronization is required, the strobe shall be compatible with Amseco SMD10-3A (daisy chain) or other source of Amseco sync protocol. Visual signaling devices shall be installed in accordance with current NFPA guidelines.

WARNING
Strobes must be used only on circuits with continuously operating voltage. DO NOT use strobe on coded or interrupted circuits in which the applied voltage is interrupted ON and OFF as the strobe may fail to flash. The applied voltage must be within its rated input voltage range. Fuse ratings on signaling circuits must handle peak currents from all devices connected to those circuits.

Installation

Dimensions: inches (mm)

Wiring Diagram

Strobe Light
Specifications| Max. RMS Operating Current
---|---
Regulated 24V DC| Regulated 24V FWR
75cd| 137
(typical 90)| 190
(typical 135)
110cd| 189
(typical 120)| 256
(typical 172)
Sound Output Dispersion| Horizontal
dB| Vertical
(111
---|---|---
| +90| -6| -3
+60| -2| -2
+30| -1| -I
0| 0| 0
-30| -1| -3
-60| -2| -5
-90| -6| -6

Under ULC 525/526 ULC Current at 24V DC (mA)
75cd 93
110cd 120

UL Required
Minimum Light Output| Horizontal| Vertical
---|---|---
| | 75 cd| 110cd| 75cd| 110cd
0| 75.00| 110.00| 75.00| 110.00
5-25| 67.50| 99.00| 67.50| 99.00
30| 56.| 82.50| 67.50| 99.00
35| 56.| 82.50| 49.| 71.50
40| 56.| 82.50| 34.50| 50.60
45| 56.| 82.50| 25.50| 37.40
50| 41.| 60.50| 20.| 29.70
55| 34.| 49.50| 16.50| 24.20
60| 30.00| 44.00| 13.50| 19.80
65| 26.| 38.50| 12.00| 17.60
70| 26.| 38.50| 11.| 16.50
75| 22.50| 33.00| 10.| 14.30
80| 22.50| 33.00| 9.00| 13.20
85-90| 19.| 27.50| 9.00| 13.20
Compound 45| 18.00| 26.40| –| –

Potter  Electric  Signal  Company  •  2081  Craig  Road,  St.  Louis,  MO, 63146­4161  •  Phone:  800­325­3936/Canada  888­882­1833
•  www.amseco­kai.com

PRINTED IN USA
MKT. #8850014 – REV B 9/07
firealarmresources.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals