POTTER PAD100-PSSA-PSDA Addressable Pull Station Single-Dual Action Owner’s Manual

June 9, 2024
POTTER

POTTER PAD100-PSSA-PSDA Addressable Pull Station Single-Dual Action

POTTER-PAD100-PSSA-PSDA-Addressable-Pull-Station-Single-Dual-Action-
PRODUCT

PAD100-PSSA/PSDA
Addressable Pull Station Single/Dual Action

Features

  • Single or Dual Action versions
  • Durable die-cast construction
  • Reset key matches the fire alarm control panels
  • Compatible with IPA Series panels
  • SLC Class A, Class X & Class B
  • Product includes a 5 year warranty
  • UUKL Listed for Smoke Control

Description

The PAD100-PSSA (Single Action) is activated by simply pulling the white “T” bar handle down. The PAD100-PSDA (Dual Action) is activated by lifting the front cover and then pulling the white “T” bar handle down. Once activated, the “T” bar cannot be reset without opening the front cover. Opening the front cover will also activate the pull station. To reset the PAD100-PS Series, use the Potter WS-93 key to unlock and open the front cover. Once the cover is open, push the “T” bar back into the normal position and re-secure the front cover.

Application

The PAD100-PSSA/PSDA is compatible with Potter’s IPA and AFC/ARC series addressable fire alarm control panels. It is a non-coded addressable pull station available in either a single or dual action model and installs on a single gang box or surface mounts using the P32-BB or P32-DBB (deep) back box.

Technical Specifications

Operating Voltage 24.0 VDC
Max SLC Standby Current 200ua
Max SLC alarm Current 200ua
environmental Limitations 32°F – 120°F (0° – 49°C)

Indoor Only

Dimensions| 4.75” H x 3.25” W x 1.75” D
Relative Humidity Range| 0 – 93% (non-condensing)
Mounting Options| Single gang box or potter p32-BB/DBB
Shipping Weight| apS-Sa – 1.22 lbs. apS-Da – 1.46 lbs.

Setting the Address

The PAD100-PS Series uses one SLC address assigned to the device. The address is set using the DIP switch located on the back of the PAD100-PS device.
Pull Station Front ViewPOTTER-PAD100-PSSA-PSDA-Addressable-Pull-Station-
Single-Dual-Action-FIG-3 Pull Station Back View and Wiring
Fig 2POTTER-PAD100-PSSA-PSDA-Addressable-Pull-Station-Single-Dual-Action-
FIG-4

Ordering Information

Model Description Stock No.
paD100-pSSa addressable pull Station, Single action 3992721
paD100-pSDa addressable pull Station, Dual action 3992720

Potter Electric Signal Company, LLC
St. Louis, MO
Phone: 800-325-3936
www.pottersignal.com