POTTER PAD100-NAC Notification Appliance Circuit Owner’s Manual
- June 9, 2024
- POTTER
Table of Contents
POTTER PAD100-NAC Notification Appliance Circuit
Features
- Monitored output module that provides an additional supervised output
- Can be used as either a NAC or Releasing Output
- NAC can be wired Class A or Class B
- Monitors presence of 24 VDC Aux Power
- SLC Class A, Class X & Class B
- Mounts in a standard 4” or double gang box
- Wiring terminals accessible when mounted in box
- All wiring terminals accept 22 to 12 AWG
- Product includes a 5 year warranty
- UUKL Listed for Smoke Control
Description
The PAD100-NAC module uses one (1) address on an SLC Loop. The module provides a programmable source of power to supervise and control one (1) Class B or Class A Notification Appliance or one (1) Class B Releasing Circuit. The module requires and supervises a 24 VDC auxiliary power connection. The PAD100-NAC includes one red LED to indicate the module’s status. In normal condition, the LED flashes when the device is being polled by the control panel.
Application
The PAD100-NAC is compatible with Potter’s IPA and AFC/ARC series addressable fire alarm control panels. The PAD100-NAC is a monitored Notification Appliance Circuit that wires to the SLC loop to provide an additional notification circuit. When used with a Potter addressable releasing panel, the PAD100-NAC can provide an additional releasing circuit.
Setting the Address
Each addressable SLC device must be assigned an address. The address is set using the DIP switches on the PAD100-NAC module. Before connecting a device to the SLC loop, take the following precautions to prevent potential damage to the panel or device:
- Power to the device is removed.
- Field wiring is correctly installed.
- Field wiring has no open or short circuits.
Technical Specifications
Operating Voltage | 24.0V |
---|---|
Max SLC Standby Current | 200μA |
Max SLC alarm Current | 200μA |
aux power Required | 16-33 VDC |
Output Ratings | 24 VDC, 2a |
eOL Resistor | 5.1K Ω |
eOL Resistor Diode | Stock #3005012 Releasing applications (Not Included) |
Operating Temperature Range | 32 to 120ºF (0 to 49ºC) |
Operating Humidity Range | 0 to 93% (non-condensing) |
Max no. of Module per Loop | 127 units |
Dimensions | 4.17” (106mm)L × 4.17” |
(106mm)W × 1.14” (29mm)D
Mounting Options| Standard 4” Square or Double gang Box
Shipping Weight| 0.6 lbs
Installation Using Compatible Electrical Box
Wiring Diagrams
Output Connected to a Notification Appliance CircuitTypical Class B Wiring Diagram Fig 2
NOTICE
It is possible that the internal relay in the PAD100-NAC may be shipped in the non-normal / activated state. To ensure that the internal relay is set to the normal state, connect the module to the SLC loop and reset the control panel before terminating the wiring to the modules output.
Ordering Information
Model | Description | Stock No. |
---|---|---|
paD100-NaC | Notification Appliance Circuit | 3992707 |
Read User Manual Online (PDF format)