POTTER PAD100-LFSB Addressable Low Frequency Sounder Base Owner’s Manual
- June 9, 2024
- POTTER
Table of Contents
POTTER PAD100-LFSB Addressable Low Frequency Sounder Base
Features
- Addressable low frequency sounder base, allows for single station, grouped or all call activation
- May be mapped to any device connected to the control panel
- Terminals accept 18 to 12 AWG wire sizes
- Supports Class A, Class X and Class B wiring
- Does not require SLC Loop address, uses PAD sub point addressing feature
- Complies with the Low Frequency Signal Requirements per NFPA 72 and UL 464 for Audible Signaling Devices
- 24 VDC Sounder base power connection supervised internally by each sounder base. No external power supervision relays required.
Description
The Addressable Low Frequency Sounder Base (PAD100-LFSB) is a sounder base
that may be utilized in a variety of applications. The base has a locking
feature for the sensor that may be used or removed in the field. Once the head
is removed, the sounder is accessible in the bottom of the unit. The
PAD100-LFSB low frequency sounder base is designed to meet NFPA 72 sleeping
space requirements to produce a frequency of 520 Hz +/- 10% with a square
wave. It is shown that a lower frequency, centered around 520 Hz, is the ideal
to awaken sleeping occupants, even those with mild to severe hearing loss. The
base has an independent sounder module that may be programmed as a single
station, zone or all call sounder. The PAD100-LFSB passes through the sound
pattern sent to the sounder, therefore it may reproduce in any pattern the
power supply provides.
The PAD100-LFSB does not consume an address on the loop and is fully
programmable to operate with any input. Once activated the sounder will also
follow the input from the power source and de-activate accordingly.
Technical Specifications
External PWR Voltage | 16-33 VDC |
---|---|
External PWR Standby Current | 4.1 mA |
External PWR Active Current | 33 VDC -86.7 mA |
24 VDC – 96.5 mA
16 VDC – 156.6 mA
SLC Operating Voltage| 24 VDC
SLC Standby Current| 200 µA
Installation temperature range| 32°F to 120°F (0°C to 49°C)
Operating relative humidity range| 0% to 93% (Non-condensing)
Sound Pressure Level| 85 DBA minimum
Start-up time| Max. 1 sec.
Maximum number of devices per zone| 127
Color| Eggshell White
Dimensions (without detector)| Height: 2.75 in (70mm) Diameter: 6 in (153 mm)
Mounting| Ceiling or wall
Detector Base Mounting
PAD100-LFSB can be mounted directly on an electrical box or the LFSBBB-W back box. The mounting holes are configured for a 4” x 2-1/8” deep square box. See Fig. 1 for electrical box mounting and Fig. 2 for back box mounting. Fig. 1
Detector Base Wiring
The SLC supports NFPA wiring Class B, A and X. (See device installation sheet for wiring details). The device also requires 24VDC power. 12 to 18 AWG conductors can be used. Fig. 3
Ordering Information
Model | Description | Stock No. |
---|---|---|
PAD100-LFSB | Addressable Low Frequency Sounder Base | 3992760 |
LFSBBB-W | Back Box | 3992761 |