POTTER PFC-5008 Fire Alarm Control Panel Owner’s Manual
- June 9, 2024
- POTTER
Table of Contents
PFC-5008
FIRE ALARM CONTROL PANEL
Stock No. 3992175
*Call for Additional Listings
Optional Modules
- ARM-4 Quad Relay Module
- 8 Class B (Style B) 4 Class A (Style D) Initiating Circuits 4 Class A (Style D) circuits.
- Predefined Initiating Circuits can be configured as Waterflow or Latching/Non- Latching Supervisory
- Selectable Alarm Verification on Initiating Circuits
- Zone Disconnect Switches
- 5 Amp Power Supply
- 4 Class A/B (Style Z/Y) Indicating Circuits (1.7 Amps max. per circuit.)
- Audibles may be configured as Steady, Temporal Code, California Code, or March Time
- Auto Signal Silence
- Auxiliary relay contacts for Common Alarm, Common Trouble, and Common Supervisory.
- Built-in RS-485 Interface for RA8F Multiplexed Remote Annunciators (Up to 3 Annunciators)
- Built-in Walk Test operation
- Output for 4-wire resettable regulated smoke power.
- Easy configuration via DIP switches
Electrical Specs
AC Main:
2.0 Amps @ 120 VAC 60 HZ
1.0 Amp @ 240 VAC 50 HZ
Battery:
155 mA Standby (PFC-5008)
340 mA Alarm (PFC-5008)
200 mA Standby (PFC-5008 with AFCT)
460 mA Alarm (PFC-5008 with AFCT)
Potter’s PFC-5008 Fire Alarm Control Panel is a microprocessor based unit
designed for small to medium commercial, residential, multifamily,
institutional and industrial occupancies. Fully configurable using DIP
switches, it enables the user to configure the system to meet their specific
requirements. The PFC-5008 is a PFC-5004E with the ZA42 expansion card factory
installed. In addition, the preassembled kit contains a UDACT-9100 for digital
communication.
The PFC-5008 comes standard with 8 Class B (Style B) Initiating Circuits which
may be configured as 4 Class A (Style D) circuits. In addition, it comes
equipped with 4 Class A/B (Style Z/Y) Indicating circuits which are each rated
at 1.7 amps. The panel also includes a 5 Amp Power Supply
which powers the system and supplies a 4-wire resettable regulated smoke power
supply of 24 VDC 100mA maximum.
The PFC-5008 utilizes a simple DIP switch configuration for programming
initiating and indicating circuits as well as the enabling and disabling of
system functions such as Signal Silence, Fire Drill and Auxiliary Disconnect.
Some predefined initiating circuits can optionally be configured Waterflow or
Latching/Non-Latching Supervisory. In addition, the PFC-5008 allows for Alarm
Verification on the initiating circuits. The indicating circuits may be
configured as Silenceable or Non-Silenceable with the audibles configured for
Steady, March-Time, Temporal Code, or California Code. Sync module required
for strobe synchronization.
The PFC-5008 is equipped with auxiliary relay contacts for Common Alarm,
Trouble and Supervisory. If no Supervisory circuits are enabled, the
Supervisory relay becomes a second Alarm relay. The cabinet is available in a
beige color for the Canadian market and a red exterior for the U.S. and
International markets.
Specifications
Charging Capability: 4 – 24 AH Batteries
Space is provided for up to 12 AH batteries.
24 AH Batteries require a separate battery cabinet.
Dimensions
14 7/8″H x 14 1/2″W x 5″D
Ordering Information
Stock No. | Model No. | Description |
---|---|---|
3992175 | PFC-5008 | 8 Zone Microprocessor Based Fire Alarm Control Panel c/w 8 |
Class B (Style B) or 4
Class A (Style D) Initiating Circuits, 4 Class A/B (Style Z/Y) Indicating
Circuits and
a 5 Amp Power Supply. Standard with one UDACT-9100 Communicator.
3992505
3002120| Adder Modules
CFG-LCD
ARM-4| Programmer for UDACT
Auxiliary Relay Module c/w 4 configurable relays
3002135| Remote Annunciator
A8F| Remote Multiplex Annunciator c/w Common Control Features, Indicators and
8 BiColored
LEDs
Controls: Signal Silence, Buzzer Silence, Lamp Test & System Reset
Indicators: A.C. On, Common Trouble & Signal Silence
5130092
5130084
5130090| Batteries
BT-40
BT-80
BT-120| 12 Volt, 4 Amp/Hr. Battery – 2 pcs required per panel
12 Volt, 8 Amp/Hr. Battery – 2 pcs required per panel
12 Volt, 12 Amp/Hr. Battery – 2 pcs required per panel
Potter Electric Signal Co., LLC • St. Louis, MO • Cust Service: 866-240-1870 • Tech Support:866-956-1211• Canada 888-882-1833 • www.pottersignal.com
PRINTED IN U.S.A.
MFG. #8900106 – REV G
4/18