POTTER PFC-5002 Fire Alarm Control Panel Owner’s Manual
- June 9, 2024
- POTTER
Table of Contents
PFC-5002
FIRE ALARM CONTROL PANEL
Stock number: 3992010
Optional Modules
- UDACT-9100 Digital Communicator
- PR-5000 Polarity Reversal and City Tie Module
- ARM-4 Quad Relay Module
- ARM-8 Eight Relay Module
- 2 Class B (Style B) Initiating Circuits which may be configured as 1 Class A (Style D) circuit.
- 2 Class A/B (Style Z/Y) Indicating Circuits with individual trouble indicators 1.7 Amp max. per circuit (2.0 Amp total)
- Each Indicating Circuit can be configured as Silenceable or Non-Silenceable
- Audibles may be configured as Steady, Temporal Code, California Code or March time
- A.C. ON LED (Green)
- Ground Fault LED (Amber)
- Battery Trouble LED (Amber)
- Individual Zone Disconnect Switches Interface for Remote Trouble Indicator
- Built-in Walk Test operation
- Selectable Alarm Verification on Initiating Circuits
- Auxiliary relay contacts for Common Alarm and Common Trouble
- 2.75 Amp Power Supply
- Output for 4-wire resettable regulated smoke power supply of 24 VdC 100mA maximum.
- Output for PRTI of 24VDC, 300mA max, unfiltered
- Extensive Transient Protection
- Easy configuration via DIP switches
Potter’s PFC-5002 FireAlarm Control Panel is a microprocessor based unit
designed for small commercial, residential, multi-family, institutional and
industrial occupancies. Fully configurable using DIP switches, it enables the
user to configure the system to meet their specific requirements.
The PFC-5002 comes standard with 2 Class B (Style B) Initiating Circuits which
may be configured as 1 Class A (Style D) circuit. In addition it comes
equipped with 2 Class A/B (Style Z/Y) Indicating circuits which are each rated
at 1.7 Amps. the panel also includes a 2.75 Amp Power
Supply which powers the system and supplies a 4-wire resettable regulated
smoke power supply of 24 VDC 100mA maximum.
The PFC-5002 utilizes a simple DIP switch configuration which allows for the
programming of the initiating and indicating circuits as well as the enabling
and disabling of system functions such as Signal Silence, Fire Drill and
Auxiliary Disconnect. In addition the PFC-5002 allows for Alarm Verification
on the Initiating circuits. The Indicating circuits may be configured as
Silenceable or Non-Silenceable with the audibles configured for Steady, March-
Time, Temporal Code, or California Code.
The cabinet is available in a red exterior only. A Fire Retardant Lexan Window in the door allows for viewing of the status LEDs.
Specifications
Electrical Requirements
Primary Input Power: 120 volts, 60 Hz, 2 Amp maximum Indicating
Current: 24VDC unfiltered, 2.5 Amps maximum Standby
Power: 24VDC Standby Batteries Charging
Capability: 4 – 12 AH Batteries
Space is provided for two 8 AH batteries.
Dimensions
12 3/4″H x 13 3/4″W x 3 1/8″D
Architects & Enitineering Specification
The fire alarm control panel shall be a two-zone fire panel UL listed to meet
the requirements of UL Standard 864. The panel shall also have the CSFM
listing and New York MEA approval. The panel shall utilize a microprocessor
and be configurable via selectable dipswitches. The panel shall have two Class
B initiating zones that may be configured as one Class A initiating zone.
Also, the panel shall have two 24 VDC unfiltered Class A/B indicating zones
that may be configured as selectable or nonsilencable. The audibles shall be
capable of being configured as steady, march time, temporal or California
Code.
The panel shall have common LED’s to indicate AC power on, common alarm,
common supervisory, common trouble, battery trouble, ground fault, remote
trouble and test. Switches shall be provided to disconnect each initiating
zone individually. In addition, switches shall be provided for signal silence,
fire drill, auxiliary disconnect, system reset, buzzer silence and lamp test.
The panel shall have three sets of form C relays for common trouble, common
supervisory and common alarm.
The panel shall be capable of supporting one DACT, Polarity Reversal/ City Tic
Module or Relay Module. The cabinet shall be constructed of I8 gauge cold
rolled steel and have a removable door. In addition, the door shall have a
lock installed. Provisions shall be provided for a remote trouble indicator.
In addition, the panel shall have resettable power for four wire smoke
detectors.
Ordering Information
Part No. | Model No. | Description |
---|---|---|
3992010 | PFC-5002 | Two Zone Microprocessor Based Fire Alarm Control Panel c/w |
2 Class B (Style B) or1 Class A (Style D) Initiating Circuit(s), 2 Class A/B
(Style Z/Y) Indicating Circuits and a 2.75 Amp Power Supply. Allows for one
UDACT-9100 Digital Communicator or one PR-5000 Polarity Reversal Module or one
ARM-4 or ARM-8 Relay Adder Module. Red enclosure c/w keylock door.
3002140| PRTI-1| Remote Trouble Indicator
Adder Modules
3992500| UDACT-9100| Digital Alarm Communication Transmitter/Dialer Module
(Requires CFG-LCD)
---|---|---
3002100| PR-5000| Polarity Reversal/City Tie Module
3992505| CFG-LCD| Programmer for UDACT
3002120| ARM-4| Auxiliary Relay Module c/w 4 configurable relays
3002125| ARM-8| Auxiliary Relay Module c/w 8 configurable relays
(Note: Only one adder module can be used with the PFC-5002)
Batteries
5130092 | BT-40 | 12 Volt, 4 Amp/Hr. Battery – 2 pcs required per panel |
---|---|---|
5130084 | BT-80 | 12 Volt, 8 Amp/Hr. Battery – 2 pcs required per panel |
Printed in U.S.A.
Mkt. #8900102 – reV J