POTTER PFC-3005T Conventional 5 Zone Fire Panel Owner’s Manual

June 9, 2024
POTTER

PFC-3005T
FIVE ZONE FIRE ALARM
CONTROL PANEL

PFC-3005TW Stock No. 3002006
PFC-3005TR Stock No. 3002007

*Call for additional listings

Features

  • Five Class ‘B’ initiating circuits
  • Two Class ‘B’ indicating circuit
  • Individual Zone Silence/Disconnect switches
  • Powerful 3mA capacity per zone for 2-wire smoke detectors
  • Common alarm Relay contact, Form C, 28 VDC @ 3 AMP (Resistive)
  • Selectable ‘N.O’or ’N.C’ common trouble contact 28 VDC @ 3 Amp (Resistive)
  • A.C. ON LED (Green)
  • Zone Alarm LED (Red)
  • Signal Trouble LED (Amber)
  • Remote Lamp Fail LED (Amber)
  • Ground Fault LED (Amber)
  • Battery Fault LED (Amber)
  • Alarm Silenced LED (Amber)
  • Common Trouble LED & Silence switch
  • Remote Trouble Indicator output
  • Remote A.C. On output
  • Selectable 1 minute Signal silence inhibit
  • Extensive Transient Protection on all circuits
  • Exterior color: Red or Beige
  • Annunciator Outputs available
  • All circuits are power limited

The PFC-3005T panel is designed for non-coded fi re alarm systems in small commercial, institutional, and industrial occupancies. A slim-line design and a neutral beige exterior color offers an unobtrusive appearance to complement any interior. The PFC-3005T includes one circuit board providing all the essentials for a complete fi re alarm system. Five Class ‘B’ initiating circuits and two Class B indicating circuits are provided by the PFC-3005T. The indicating circuit is protected from shorts by self-restoring circuitry.
Supervision includes ground fault detection, battery low level or open wire fault, initiating and indicating circuit wiring faults and loss of A.C. power. Initiating circuits are supervised for opens and ground faults. Indicating circuits are supervised for opens, shorts and ground faults. LED indicators are provided for Zone Alarm, Zone Trouble, A.C. On, Battery Fault, Ground Fault, Common Trouble, Signal Trouble and Signal Silenced.
Switches are provided for Zone disconnect/silence, trouble silence and reset.

Upon a trouble condition, the trouble LED will fl ash and the trouble audible signal will pulse. Activating the “Trouble Silence” switch silences the trouble signal and the “Trouble” LED remains fl ashing.
When the trouble condition clears, the common trouble LED restores to normal and the common trouble buzzer resounds steady until the Trouble Signal silence switch is returned to normal. The alarm signals cannot be silenced for one minute if the one minute inhibit feature has been selected jumper selectable.
The PFC-3005T has selectable audible tones which can be confi gured via DIP switches for Steady and Temporal Code. The common alarm relay can follow the signal circuit or lock on until the alarm has been reset. This option is jumper selectable. Annunciation outputs are provided for alarm, remote trouble indicator and buzzer. Lamp supervision is jumper selectable. The PFC-3005T controls are behind a durable locked door. The cabinet will accommodate a 4 or 8AH battery pack.

Technical Specifications

Initiating Circuits

Output Voltage| 22 VDC, fi ltered and regulated.
Current Limited| 50 mA
Supervisory Current| 3 mA (up to 30, 2-wire smoke detectors @ 100 uA each)
Loop Resistance| 100 ohms, max
End of Line Resistor| 3.9Kohm + 5%,1/2W
Indicating Circuits
Output Voltage| 24 VDC
Output Current| 3.4A Total Current (1.7 ea x 2)
End of Line Resistor| 3.9Kohm + 5%,1/2W
Auxiliary Contacts| 28 VDC, 3A (Resistive)
Dimensions| 13.7″(347mm)W x 12.7″(322mm)H x 2.8″(71 mm)D

Ordering Information

Stock No. Model Description
3002006  PFC-3005TW  Five Zone Fire Alarm Panel (Beige cabinet)
3002007 PFC-3005TR Five Zone Fire Alarm Panel (Red cabinet)
3002140 PRTI-1 Remote Trouble indicator, mounts onto a single gang

electrical box
3002145| PFC-3000TR| Flush Mounting Trim Ring
5130092| BT-40| 12V / 4.0 AH Battery (2 Required)

Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936
www.pottersignal.com
PRINTED IN U.S.A.
MFG. #8900121 – REV A