POTTER PFC-3002T Conventional 2 Zone Fire Panel Owner’s Manual

June 9, 2024
POTTER

POTTER PFC-3002T Conventional 2 Zone Fire Panel

POTTER-PFC-3002T-Conventional 2-Zone Fire Panel

Features

  • Two Class ‘B’ initiating circuits
  • One Class ‘B’ indicating circuit
  • Individual Zone Silence/Disconnect switches
  • Powerful 3mA capacity per zone for 2-wire smoke detectors
  • Common alarm Relay contact, Form C, 28 VDC @ 3 AMP (Resistive)
  • Selectable ‘N.O’or ’N.C’ common trouble contact 28 VDC @ 3 Amp (Resistive)
  • A.C. ON LED (Green)
  • Zone Alarm LED (Red)
  • Signal Trouble LED (Amber)
  • Ground Fault LED (Amber)
  • Battery Fault LED (Amber)
  • Alarm Silenced LED (Amber)
  • Common Trouble LED & Silence switch
  • Remote Trouble Indicator output
  • Remote A.C. On output
  • Selectable 1 minute Signal silence inhibit
  • Extensive Transient Protection on all circuits
  • Exterior color: Red or Beige
  • All circuits are power limited

The PFC-3002T panel is designed for non-coded fi re alarm systems in small commercial, institutional and industrial occupancies.
The PFC-3002T includes one circuit board providing all the essentials for a complete fi re alarm system. Two Class ‘B’ initiating circuits and one Class ‘B’ indicating circuit are provided by the PFC-3002T. The indicating circuit is protected from shorts by self-restoring circuitry.

Supervision includes ground fault detection, battery low level or open wire fault, initiating and indicating circuit wiring faults and loss of A.C. power. Initiating circuits are supervised for opens and ground faults. Indicating circuits are supervised for opens, shorts and ground faults. LED indicators are provided for Zone Alarm, Zone Trouble, A.C. On, Battery Fault, Ground Fault, Common Trouble, Signal Trouble and Signal Silenced.
Switches are provided for Zone disconnect/silence, trouble silence and reset.

The PFC-3002T has selectable audible tones which can be configured via DIP switches for Steady and Temporal Code.

The panel also includes a common alarm relay which is confi gurable (via jumper) to follow the signal circuit or lock on until the alarm has been reset.
The controls are behind a durable locked door. The cabinet will accommodate a 4 or 8 AH battery pack.

DIAGRAM

NOTE: ALL CIRCUITS ARE POWER LIMITED

POTTER-PFC-3002T-Conventional 2-Zone Fire Panel-3

INITIATING AND INDICATING WIRING INSTRUCTIONS

NOTE: ALL CIRCUITS ARE POWER LIMITED

POTTER-PFC-3002T-Conventional 2-Zone Fire Panel-2

ALARM AND TROUBLE RELAY CONTACTS, AND REMOTE ANNUNCIATION WIRING INSTRUCTIONS

Technical Specifications

Initiating Circuits

  • Output Voltage 22 VDC, fi ltered and regulated.
  • Current Limited 50 mA
  • Supervisory Current 3 mA (up to 30, 2-wire smoke detectors @ 100 uA each)
  • Loop Resistance 100 ohms, max
  • End of Line Resistor 3.9Kohm + 5%,1/2W

Indicating Circuits

  • Output Voltage 24 VDC
  • Output Current 1.7A
  • End of Line Resistor 3.9Kohm + 5%,1/2W
  • Auxiliary Contacts 28 VDC, 3A (Resistive)
  • Dimensions 13.7″(347mm)W x 12.7″(322mm)H x 2.8″(71 mm)D

Ordering Information

POTTER-PFC-3002T-Conventional 2-Zone Fire Panel-4

Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936www.pottersignal.com

MFG. #8900120 – REV A
10/05

firealarmresources.com