POTTER PFC-3002T Conventional 2 Zone Fire Panel Owner’s Manual
- June 9, 2024
- POTTER
Table of Contents
POTTER PFC-3002T Conventional 2 Zone Fire Panel
Features
- Two Class ‘B’ initiating circuits
- One Class ‘B’ indicating circuit
- Individual Zone Silence/Disconnect switches
- Powerful 3mA capacity per zone for 2-wire smoke detectors
- Common alarm Relay contact, Form C, 28 VDC @ 3 AMP (Resistive)
- Selectable ‘N.O’or ’N.C’ common trouble contact 28 VDC @ 3 Amp (Resistive)
- A.C. ON LED (Green)
- Zone Alarm LED (Red)
- Signal Trouble LED (Amber)
- Ground Fault LED (Amber)
- Battery Fault LED (Amber)
- Alarm Silenced LED (Amber)
- Common Trouble LED & Silence switch
- Remote Trouble Indicator output
- Remote A.C. On output
- Selectable 1 minute Signal silence inhibit
- Extensive Transient Protection on all circuits
- Exterior color: Red or Beige
- All circuits are power limited
The PFC-3002T panel is designed for non-coded fi re alarm systems in small
commercial, institutional and industrial occupancies.
The PFC-3002T includes one circuit board providing all the essentials for a
complete fi re alarm system. Two Class ‘B’ initiating circuits and one Class
‘B’ indicating circuit are provided by the PFC-3002T. The indicating circuit
is protected from shorts by self-restoring circuitry.
Supervision includes ground fault detection, battery low level or open wire
fault, initiating and indicating circuit wiring faults and loss of A.C. power.
Initiating circuits are supervised for opens and ground faults. Indicating
circuits are supervised for opens, shorts and ground faults. LED indicators
are provided for Zone Alarm, Zone Trouble, A.C. On, Battery Fault, Ground
Fault, Common Trouble, Signal Trouble and Signal Silenced.
Switches are provided for Zone disconnect/silence, trouble silence and reset.
The PFC-3002T has selectable audible tones which can be configured via DIP switches for Steady and Temporal Code.
The panel also includes a common alarm relay which is confi gurable (via
jumper) to follow the signal circuit or lock on until the alarm has been
reset.
The controls are behind a durable locked door. The cabinet will accommodate a
4 or 8 AH battery pack.
DIAGRAM
NOTE: ALL CIRCUITS ARE POWER LIMITED
INITIATING AND INDICATING WIRING INSTRUCTIONS
NOTE: ALL CIRCUITS ARE POWER LIMITED
ALARM AND TROUBLE RELAY CONTACTS, AND REMOTE ANNUNCIATION WIRING INSTRUCTIONS
Technical Specifications
Initiating Circuits
- Output Voltage 22 VDC, fi ltered and regulated.
- Current Limited 50 mA
- Supervisory Current 3 mA (up to 30, 2-wire smoke detectors @ 100 uA each)
- Loop Resistance 100 ohms, max
- End of Line Resistor 3.9Kohm + 5%,1/2W
Indicating Circuits
- Output Voltage 24 VDC
- Output Current 1.7A
- End of Line Resistor 3.9Kohm + 5%,1/2W
- Auxiliary Contacts 28 VDC, 3A (Resistive)
- Dimensions 13.7″(347mm)W x 12.7″(322mm)H x 2.8″(71 mm)D
Ordering Information
Potter Electric Signal Company • 2081 Craig Road, St. Louis, MO, 63146-4161 • Phone: 800-325-3936 • www.pottersignal.com
MFG. #8900120 – REV A
10/05