POTTER PFC-6006 Conventional Fire Panel Owner’s Manual
- June 9, 2024
- POTTER
Table of Contents
PFC-6006
Conventional Fire Panel
Features
- 6 programmable Initiating Device Circuits
- Class A or Class B Waterflow Initiating Circuit
- 2 Wire Smoke Detector Compatibility
- 1.0 Amp Power Supply
- 1 Notification Circuit rated at 0.5 Amps Regulated
- Strobe Synchronization for potter/aMSECO, gentex, System Sensor and Cooper/Wheelock
- 0.5 Amp Auxiliary Power, Programmable as Constant or Resettable
- 2 x 16 LCD display with system LEDs for clear system status
- Keypad for system features
- P-Link for Remote Annunciator Connections
- Capacity to charge and house 18AH batteries
- Onboard Dual Line Digital Alarm Communicator
- Built-in Ethernet Connection with listed IP Communicator
- Ability to E-mail system status, reports and system configuration
- Service Reminder E-mails
General Description
The PFC-6006 is a listed small conventional fire system ideally suited to
monitor a small fire system such as a fire sprinkler system. The first input
is selectable as a Class A or Class B water flow input and the other five
zones are selectable from a menu of options including two-wire smoke
detection. The panel has a 1.0 amp power supply that powers the panel, charges
the batteries and supplies 0.5 amps to a notification appliance circuit and
0.5 amps of auxiliary power. The auxiliary power is programmable as constant
or resettable.
The control panel is in a metal cabinet with a key lock and lexan window for
viewing the system status. The printed circuit assembly is mounted for quick
removal and installation to allow the cabinet to be installed with minimal
effort. The cabinet houses up to two 12VDC, 18 AH batteries.
The display is a thirty-two (32) character LCD with system status LEDs. The
system status is clearly displayed and the panel includes a history buffer for
past events. The key pad allows navigation into the system menu, limited
programming and system control. The condition and events on the panel are
clearly displayed to allow the user and installer to determine the system
status.
The panel has a dual telephone line digital alarm communicator transmitter
(DACT) built on-board. One or both telephone lines may be enabled to allow
communication to a remote monitoring station. In addition, an updated panel
configuration may be sent to the panel through the telephone lines. The panel
has line in and line out to allow the panel to be installed ahead of other
telephone equipment on the premises.
Technical Specifications
Size (H x W x D) | 18-1/2″ x 14-1/4″ x 4-3/4″ |
---|---|
enclosure | Eighteen (18) gauge sheet steel with hinged, removable locked |
door
AC Mains| 1.0 amp @ 120 VAC 60 Hz
Battery| 105 mA Standby
160 ma alarm
Temperature| 32° to 120°F, humidity 93% non-condensing
Standards/approvals| UL-864
NFPA-70, 72
The panel will support up to four (4) of the RA-6075 remote annunciators on
the P-Link bus. These annunciators include a metal enclosure with a key lock
and provide full functionality of the system.
The panel is pre-programmed from the factory for monitoring a typical wet or
dry fire sprinkler system. The programming may be changed using the Potter
Fire Panel Programmer (available free from
www.pottersignal.com) and a standard Ethernet
cable. The default program is as follows:
Input 1 – Waterflow
Input 2 – Smoke Detection (two-wire)
Input 3 – Manual Pull Station
Input 4 – Non-Latching Supervisory
Input 5 – Valve Tamper
Input 6 – Valve Tamper
In the standard program, Input 1 is defaulted as a Water flow zone. Input 1 is
the only Class A/Class B zone. The panel will automatically determine Class A
or B based on wiring and the presence of the end of line resistor. All of the
inputs may be programmed for General Alarm, Waterflow, TwoWire Smoke Detector,
Heat Detector, Manual Pull Station, Non-latching Supervisory, Latching
Supervisory, or Valve Tamper.
The NAC is listed for strobe synchronization and the panel is listed with
Potter/AMSECO, Gentex, System Sensor, and Cooper Wheelock signals.
Please refer to the Potter Notification Compatibility Document for the maximum
number of strobe devices that may be connected. The maximum output is 0.5
amps.
The Ethernet connection may be connected to a building network with Internet
to provide e-mail notifications of system status, reports, or system
configuration. In addition, the Ethernet connection is listed for IP reporting
to a monitoring station.
Primary AC
120VAC, 60Hz, .75 AMP
Min Low AC Detect 98VAC
Battery Charging
27.3VDC @ .5A
Low Battery Detect @20.4VDC
All Circuit Impedance Values
Short Circuit: 0 Ohms
Open Circuit: >10K
Earth Fault to any terminal: 0 Ohms
Main Fuse Specification
1.6A-250VAC
Batt. Fuse Specification
2.5A-250VAC
F.C.C.
This device has been veri¡ed to comply with FCC Rules Part 15, Class A
Operation is subject to the following conditions:
1. This device may not cause radio interference.
2. This device must accept any interference received including any that may
cause undesired operation.
Acknowledgements
Gentex ®, Cooper Wheelock ®, and System Sensor ® synchronization protocols
used with permission. Cooper Wheelock Patent Nos. 5,400,009.
Potter Electric Signal Company LLC PFC-6006
US: POTAL01BSMP
Complies with 47 CFR Part 68.
Made in USA.
See board for Serial #.
P/N 5406280 (4/1/2019)
Requirements
System must be fully tested after installation.
Intended for indoor use in dry locations only.
Separation of power limited wiring from non-power limited wiring must be at
least 1/4″.
Install in accordance with installation manual Part Number 5403559 – , and
Operating instructions – Part #5406282 – .
See Smoke Detector Compatibility Identifer “A”
NFPA Commercial Protected Premises Control Unit for UL Installations: 13, 70,
and NFPA 72.
NYC Fire Dept. Certificate of Approval #6159 & 6184
Alarm activation requiring activation of two or more automatic detection
devices shall not utilize any time delay.
Service Use for UL Installations:
– Local
– Remote Station
– Proprietary
– Central Station
Ordering Information
Model | Description | Stock No. |
---|---|---|
pFC-6006 | Conventional Fire Panel | 3992334 |
Replacement Board | 3992346 |