POTTER PNA Portable Nitrogen Analyzer Owner’s Manual
- June 9, 2024
- POTTER
Table of Contents
POTTER PNA Portable Nitrogen Analyzer
Features
- Durable N2 analyzer
- One-button calibration
- Auto-off
- 3-digit display
- Maintenance free
Description
The Portable Nitrogen Analyzer is an easy way to determine the purity of nitrogen that the Potter Nitrogen Generator is producing. Since the analyzer is portable, it gives you the ability to check the end of the line purity of the fire sprinkler system, ensuring the system is protected. Store the N2 analyzer in a temperature similar to its ambient environment of daily use.
Operation
Prior to turning on the unit, wait 5 minutes to allow the sensor to reach equilibrium. Using the “ON/OFF” key, make sure the unit is in the power “ON” mode. Press and hold the Calibration Key for 3 seconds until the display reads “CAL”. This will calibrate the N2 Analyzer to room air. A new calibration is required when the measured N2 percentage is above 80.1% N2 or below 78.1% N2. The N2 Analyzer is ready to use.
Ordering Information
Model | Description | Stock No. |
---|---|---|
PNA | Portable Nitrogen Analyzer | 1119504 |
Technical Specifications
Measurement Range | 0-99.9% |
---|---|
Resolution | 0.1% Nitrogen |
Operating Temperature | 15°C to 40°C (59°F to 104°F) |
Storage Temperature | -15°C to 50°C (5°F to 122°F) |
Sensor Type | Galvanic fuel cell |
Battery Type | 3V Lithium button cell (non-replaceable) |